16AX 250V 2 Gang 2 Way Switch KB32
range |
Vivace
|
|
---|---|---|
product or component type |
Switch
|
|
device short name |
KB32
|
|
device presentation |
Complete mechanism
|
switch function |
2-way
|
|
---|---|---|
actuator |
Rocker
|
|
number of gangs |
2 gangs
|
|
colour tint |
White
|
|
material |
Polycarbonate: grid plate
Polycarbonate: surround Polycarbonate: base |
|
projecting depth |
8 mm
|
|
device mounting |
Flush
|
|
mounting support |
Wall mounted
|
|
fixing mode |
By screw M3.5
|
|
fixing center |
60.3 mm
|
|
embedding depth |
35 mm
|
|
rated current |
16 AX at 250 V AC, inductive
16 AX at 250 V AC, fluorescent |
|
[Ue] rated operational voltage |
250 V AC
|
|
network frequency |
50 Hz
|
|
contacts material |
Brass and phosphor bronze
|
|
connections – terminals |
pillar terminal
|
|
terminal identifier |
COM
L1 L2 |
|
tightening torque |
0.4 N.m
|
|
clamping connection capacity |
2.5 mm²
|
|
width |
87 mm
|
|
height |
87 mm
|
₦1,450.00
Compare-
ELECTRICAL INDUSTRIAL, TRANSFORMER
ABB Transformer 800kVA 400/11 ABB Cu/Cu Oil Filled Ground-mounting
ELECTRICAL INDUSTRIAL, TRANSFORMERABB Transformer 800kVA 400/11 ABB Cu/Cu Oil Filled Ground-mounting
Distribution transformers are typically oil-immersed and suitable for pole-, pad- or ground-mounting. They represent an economical option for certain networks, particularly those with low population densities. Depending upon requirements, transformers may be connected between two phases of a three-phase system (two high voltage bushings) or from one phase to ground (single high voltage bushing). The units are suitable for residential overhead distribution loads, as well as light commercial or industrial loads and diversified power applications. Product scope Primary voltage: up to 36 kV Typical fluid: mineral oil.
Technical Specification
Product Name: Liquid-Filled Groundmount Transformer; 800 kVA
Rated Power 800[kVA]
Insulation Liquid: Mineral Oil
Low Voltage at no Load: 415[V]
Number of phases 3
Max. average temperature rise (Oil/Winding): 60 / 65[C/C]
Location Indoor/Outdoor
Rate Voltage: 11-0,415KV
Total Weight: 2100[kg]
SKU: dts80033-1 -
Schneider Circuit Breakers, SCHNEIDER SECTIONS
Acti9 iC60N 1P 63A C Miniature Circuit breaker A9F44163
Schneider Circuit Breakers, SCHNEIDER SECTIONSActi9 iC60N 1P 63A C Miniature Circuit breaker A9F44163
Main range Acti 9product name Disbo iC60product or component type Miniature circuit-breakerdevice short name IC60Npoles description 1Pnumber of protected poles 1[In] rated current 63 Anetwork type ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 15 kA Icu at 12…48 V DC conforming to EN/IEC 60947-2
6 kA Icu at 72 V DC conforming to EN/IEC 60947-2
6000 A Icn at 240 V AC 50/60 Hz conforming to EN/IEC 60898-1
36 kA Icu at 10…60 V AC 50/60 Hz conforming to EN/IEC 60947-2
20 kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2
10 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2utilisation category Category A conforming to EN/IEC 60947-2Complementary network frequency 50/60 Hz[Ue] rated operational voltage 240 V AC 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 27 kA 75 % conforming to EN/IEC 60947-2 – 10…60 V AC 50/60 Hz
15 kA 75 % conforming to EN/IEC 60947-2 – 100…133 V AC 50/60 Hz
7.5 kA 75 % conforming to EN/IEC 60947-2 – 220…240 V AC 50/60 Hz
6000 A 100 % conforming to EN/IEC 60898-1 – 240 V AC 50/60 Hz
15 kA 100 % conforming to EN/IEC 60947-2 – 12…48 V DC
6 kA 100 % conforming to EN/IEC 60947-2 – 72 V DClimitation class 3 conforming to EN/IEC 60947-2[Ui] rated insulation voltage 500 V AC 50/60 Hz[Uimp] rated impulse withstand voltage 6 kV conforming to EN/IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Clip-onmounting support Rail9 mm pitches 2height 85 mmwidth 18 mmdepth 78.5 mmnet weight 0.125 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesprovision for padlocking Padlockableconnections – terminals Single terminal (top or bottom) 1…35 mm² rigid
Single terminal (top or bottom) 1…25 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 3.5 N.m top or bottomearth-leakage protection Separate blockSKU: n/a -
COMPUTING, LAPTOPS
Notebook Lenovo IdeaPad 300 – 330 81D100J5AK, Black
Brand LENOVO Model IdeaPad 330 Family IdeaPad Series 300 Product type Notebook Form factor Clamshell Colour name Onyx black Product colour Black DISPLAY Display diagonal 15.6″ Display resolution 1366 x 768 pixels Touchscreen NO HD type HD Aspect ratio 16/9 LED backlight YES HDMI version 1.4a Display brightness 200 cd/m² CPU Processor frequency 1.10 GHz Processor family Intel® Celeron® Processor model N4000 Processor cores 2 Processor threads 2 Processor cache 4 MB Processor socket BGA 1090 Processor lithography 14 nm Processor operating modes 64-bit Processor codename Gemini Lake Thermal Design Power (TDP) 6 W Tjunction 105 °C Maximum number of PCI Express lanes 6 PCI Express slots version 2.0 ECC supported by processor NO Processor package size 25 x 24 mm CPU configuration (max) 1 3D NO Processor boost frequency 2.60 GHz Scenario Design Power (SDP) 4.8 W MEMORY Internal memory 4 GB Internal memory type DDR4-SDRAM Maximum internal memory 8 GB Memory slots 1x SO-DIMM Memory clock speed 2400 MHz Maximum internal memory (64-bit) 8 GB Memory form factor SO-DIMM STORAGE Total storage capacity 500 GB Storage media HDD Card reader integrated YES Compatible memory cards MMC,SD,SDHC,SDXC Total HDDs capacity 500 GB Number of HDDs installed 1 HDD capacity 500 GB HDD interface SATA III HDD speed 5400 RPM HDD size 2.5″ SKU: n/a -
Schneider Circuit Breakers, SCHNEIDER SECTIONS
IC60H – miniature circuit breaker – 1P – 40A – C curve A9F84140
Schneider Circuit Breakers, SCHNEIDER SECTIONSIC60H – miniature circuit breaker – 1P – 40A – C curve A9F84140
Main device application Distributionrange Acti 9product name Acti 9 iC60product or component type Miniature circuit-breakerdevice short name IC60Hpoles description 1Pnumber of protected poles 1[In] rated current 40 Anetwork type AC
DCtrip unit technology Thermal-magneticcurve code Cbreaking capacity 10000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
15 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
42 kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2
30 kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2
15 kA Icu at 60…72 V DC conforming to EN/IEC 60947-2
20 kA Icu at 12…60 V DC conforming to EN/IEC 60947-2utilisation category Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2suitability for isolation Yes conforming to EN 60898-1
Yes conforming to EN 60947-2
Yes conforming to IEC 60898-1
Yes conforming to IEC 60947-2standards IEC 60947-2
IEC 60898-1
EN 60898-1
EN 60947-2Complementary network frequency 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 21 kA 50 % conforming to EN 60947-2 – 12…60 V AC 50/60 Hz
7.5 kA 50 % conforming to EN 60947-2 – 220…240 V AC 50/60 Hz
21 kA 50 % conforming to IEC 60947-2 – 12…60 V AC 50/60 Hz
7.5 kA 50 % conforming to IEC 60947-2 – 220…240 V AC 50/60 Hz
7500 A 75 % conforming to EN 60898-1 – 230 V AC 50/60 Hz
7500 A 75 % conforming to IEC 60898-1 – 230 V AC 50/60 Hz
15 kA 50 % conforming to IEC 60947-2 – 100…133 V AC 50/60 Hz
15 kA 50 % conforming to EN 60947-2 – 100…133 V AC 50/60 Hz
15 kA 100 % conforming to EN 60947-2 – 72 V DC
15 kA 100 % conforming to IEC 60947-2 – 72 V DC
20 kA 100 % conforming to EN 60947-2 – 12…60 V DC
20 kA 100 % conforming to IEC 60947-2 – 12…60 V DClimitation class 3 conforming to EN 60898-1
3 conforming to IEC 60898-1[Ui] rated insulation voltage 500 V AC 50/60 Hz conforming to EN 60947-2
500 V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6 kV conforming to EN 60947-2
6 kV conforming to IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Fixedmounting support DIN railcomb busbar and distribution block compatibility Top or bottom: YES9 mm pitches 2height 85 mmwidth 18 mmdepth 78.5 mmnet weight 0.215 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesconnections – terminals Single terminal (top or bottom) 1…35 mm² rigid
Single terminal (top or bottom) 1…25 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 3.5 N.m top or bottomearth-leakage protection WithoutSKU: n/a -