Acti9 iC60N 2P 6A C Miniature Circuit breaker
range |
Acti 9
|
|
---|---|---|
product name |
Disbo iC60
|
|
product or component type |
Miniature circuit-breaker
|
|
device short name |
IC60N
|
|
poles description |
2P
|
|
number of protected poles |
2
|
|
[In] rated current |
6 A
|
|
network type |
AC
|
|
trip unit technology |
Thermal-magnetic
|
|
curve code |
C
|
|
breaking capacity |
6 kA Icu at 100…133 V DC conforming to EN/IEC 60947-2
6000 A Icn at 415 V AC 50/60 Hz conforming to EN/IEC 60898-1 36 kA Icu at 12…133 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
|
utilisation category |
Category A conforming to EN/IEC 60947-2
|
network frequency |
50/60 Hz
|
|
---|---|---|
[Ue] rated operational voltage |
440 V AC 50/60 Hz
|
|
magnetic tripping limit |
8 x In +/- 20 %
|
|
[Ics] rated service breaking capacity |
27 kA 75 % conforming to EN/IEC 60947-2 – 12…133 V AC 50/60 Hz
15 kA 75 % conforming to EN/IEC 60947-2 – 220…240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 – 380…415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 – 440 V AC 50/60 Hz 6000 A 100 % conforming to EN/IEC 60898-1 – 415 V AC 50/60 Hz 6 kA 100 % conforming to EN/IEC 60947-2 – 100…133 V DC |
|
limitation class |
3 conforming to EN/IEC 60947-2
|
|
[Ui] rated insulation voltage |
500 V AC 50/60 Hz
|
|
[Uimp] rated impulse withstand voltage |
6 kV conforming to EN/IEC 60947-2
|
|
contact position indicator |
Yes
|
|
control type |
Toggle
|
|
local signalling |
Trip indicator
|
|
mounting mode |
Clip-on
|
|
mounting support |
Rail
|
|
9 mm pitches |
4
|
|
height |
85 mm
|
|
width |
36 mm
|
|
depth |
78.5 mm
|
|
net weight |
0.25 kg
|
|
colour |
White
|
|
mechanical durability |
20000 cycles
|
|
electrical durability |
10000 cycles
|
|
provision for padlocking |
Padlockable
|
|
connections – terminals |
Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexible |
|
wire stripping length |
14 mm for top or bottom connection
|
|
tightening torque |
2 N.m top or bottom
|
|
earth-leakage protection |
Separate block
|
₦5,999.00
Vendor Information
- 5.00 rating from 1 review
-
SOCKETS
BG BRASS GEORGIAN SHAVER SOCKET OUTLET DUAL VOLTAGE BLACK INSERT
BG NBG20B Brass Georgian Shaver Socket Outlet Dual Voltage Black InsertAT A GLANCE…- Top quality Brass finish – lightly lacquered to prevent finger marks
- Black plastic insert
- Specification: 115/230V dual voltage
- Supplied with colour coded fixing screws
SKU: Volex socket2 -
ACCESSORIES, CIRCUIT BREAKERS, DISTRIBUTION BOARDS, ELECTRICAL INDUSTRIAL
ABB Contactor AF400-30-22 100-250V
ACCESSORIES, CIRCUIT BREAKERS, DISTRIBUTION BOARDS, ELECTRICAL INDUSTRIALABB Contactor AF400-30-22 100-250V
A 3-phase Contactor suitable for various applications such as Motor starting, Isolation, By-pass and Distribution application up to max 1000 V. Operated with wide control voltage range 100-250 V, AC/DC
Categories
- Products » Low Voltage Products and Systems » Control Products » Contactors » Block Contactors
SKU: n/a -
DISTRIBUTION BOARDS, DISTRIBUTION BOARDS
ABB 12 Way Three Phase Distribution Board
Available in kit form for over-the counter-supply, the latest generation sub-distribution solution from ABB has been tailored to meet the needs of all segments of the building industry.
Main construction features:
• Structure in epoxy coated metal sheets, 1mm thickness
• Wall installation for indoor environments
• Degree of protection – IP43 with door / Mechanical resistance IK 07
• Busbar rating: 250A
• Number of ways: 4, 8, 12, 16, 20, 24
• Compliance with IEC BS EN 61439 1-2
• Simple wiring of all cabinets, both horizontally and vertically
• Easy internal accessibility for wiring operations and maintenance
• Pre-packaged kits for specific applications (e.g. surge protection, metering)SKU: n/a -
-
-
There are no reviews yet.