Acti9 iC60N 3P 10A C Miniature Circuit breaker A9F44310
range |
Acti 9
|
|
---|---|---|
product name |
Disbo iC60
|
|
product or component type |
Miniature circuit-breaker
|
|
device short name |
IC60N
|
|
poles description |
3P
|
|
number of protected poles |
3
|
|
[In] rated current |
10 A
|
|
network type |
AC
|
|
trip unit technology |
Thermal-magnetic
|
|
curve code |
C
|
|
breaking capacity |
6000 A Icn at 415 V AC 50/60 Hz conforming to EN/IEC 60898-1
36 kA Icu at 12…133 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 100…133 V DC conforming to EN/IEC 60947-2 |
|
utilisation category |
Category A conforming to EN/IEC 60947-2
|
network frequency |
50/60 Hz
|
|
---|---|---|
[Ue] rated operational voltage |
440 V AC 50/60 Hz
|
|
magnetic tripping limit |
8 x In +/- 20 %
|
|
[Ics] rated service breaking capacity |
27 kA 75 % conforming to EN/IEC 60947-2 – 12…133 V AC 50/60 Hz
15 kA 75 % conforming to EN/IEC 60947-2 – 220…240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 – 380…415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 – 440 V AC 50/60 Hz 6000 A 100 % conforming to EN/IEC 60898-1 – 415 V AC 50/60 Hz 15 kA 100 % conforming to EN/IEC 60947-2 – 100…133 V DC |
|
limitation class |
3 conforming to EN/IEC 60947-2
|
|
[Ui] rated insulation voltage |
500 V AC 50/60 Hz
|
|
[Uimp] rated impulse withstand voltage |
6 kV conforming to EN/IEC 60947-2
|
|
contact position indicator |
Yes
|
|
control type |
Toggle
|
|
local signalling |
Trip indicator
|
|
mounting mode |
Clip-on
|
|
mounting support |
Rail
|
|
9 mm pitches |
6
|
|
height |
85 mm
|
|
width |
54 mm
|
|
depth |
78.5 mm
|
|
net weight |
0.375 kg
|
|
colour |
White
|
|
mechanical durability |
20000 cycles
|
|
electrical durability |
10000 cycles
|
|
provision for padlocking |
Padlockable
|
|
connections – terminals |
Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexible |
|
wire stripping length |
14 mm for top or bottom connection
|
|
tightening torque |
2 N.m top or bottom
|
|
earth-leakage protection |
Separate block
|
₦7,999.00
Compare-
Electro, LED LIGHTS, LIGHTING, OUTDOOR LIGHTS, SOLAR POWERED
ALL-IN-ONE SOLAR LED STREET LIGHT 80WATT 12800lm
Electro, LED LIGHTS, LIGHTING, OUTDOOR LIGHTS, SOLAR POWEREDALL-IN-ONE SOLAR LED STREET LIGHT 80WATT 12800lm
Quick details
Model:FL-D1-80W
Solar panel:(MONO)105W
High capacity lithium battery (Bull-in):650WH
luminous flux (AII light pattern):12800lm
Mounting Height:6- 8M
Solar panel charge time (with strong sunlight):8 hours by bright sunlight
Rainy Days Support:3-5 days with full charging
Working Time (per day):≥12 hours
Color temperature:3000-7000K (optional)
Light pole diameter:70-114MM
Storage temperature:0-55C
Operating humidity:90RH%≤
Waterproof level:Ip65
Package dimensions:1603*420*230mm
SKU: n/a -
Electro, Schneider, SCHNEIDER SECTIONS
Easy9 distribution board – 3P – 125A – 24 ways- straight with fixlink EZ9ET24L
Electro, Schneider, SCHNEIDER SECTIONSEasy9 distribution board – 3P – 125A – 24 ways- straight with fixlink EZ9ET24L
Main range Easy9product name VTPNproduct or component type Distribution boardprovided equipment 1 x washer
4 x screws
Removable front cover
Copper link
Insulated fishbone
Adjustable pan assembly
Provision for incomer
Blanking plateComplementary enclosure mounting Flush
Surfacenetwork number of phases Three phasenumber of ways 24 waystype of rail DINcable entry 11 knock-outsType of door Plain door[In] rated current 125 Aenclosure material Powder coated steelwidth 466 mm outside:height 568 mm outside:depth 110 mm outside:colour Grey (RAL 7035)Environment standards IEC 61439-3
IEC 61439-1product certifications ASTAIP degree of protection IP40 conforming to IEC 60529 (closed door)IK degree of protection IK08 conforming to IEC 62262ambient air temperature for operation -5…50 °CPacking Units Package 1 Weight 15000.000 kgPackage 1 Height 110.000 mmPackage 1 width 466.000 mmPackage 1 Length 633.000 mmSKU: n/a -
Electro, Schneider, SCHNEIDER SECTIONS
Easy9 distribution board – 1P – 100A – 12 ways – fixed EZ9ES12L
Electro, Schneider, SCHNEIDER SECTIONSEasy9 distribution board – 1P – 100A – 12 ways – fixed EZ9ES12L
Main range Easy9product or component type Enclosureenclosure type Distribution enclosureprovided equipment 1 x washer
Identification label
4 x screws
Removable front coverComplementary enclosure mounting Surface
FlushNb of horizontal rows 1number of plates 5 for plain platenetwork number of phases Single phasenumber of ways 12 waystype of rail DINcable entry 8 knock-outsType of door Plain door[In] rated current 100 Aenclosure material Powder coated steelwidth 470 mm outside:height 232 mm outside:depth 90 mm outside:colour Grey (RAL 7035)Environment standards IEC 61439-1
IEC 61439-3product certifications ASTAIP degree of protection IP40 conforming to IEC 60529 (closed door)IK degree of protection IK08 conforming to IEC 62262ambient air temperature for operation 50 °CPacking Units Package 1 Weight 5250.000 kgPackage 1 Height 95.000 mmPackage 1 width 232.000 mmPackage 1 Length 470.000 mmSKU: n/a -
LIGHT SWITCHES & ELECTRICAL SOCKETS, SCHNEIDER SECTIONS
SHUTTERED WALLPLATE W/O MODULAR JACK E8432RJ_5_WE
LIGHT SWITCHES & ELECTRICAL SOCKETS, SCHNEIDER SECTIONSSHUTTERED WALLPLATE W/O MODULAR JACK E8432RJ_5_WE
Main range ZENceloproduct or component type Central platesocket additional information ShutteredComplementary number of gangs 2 gangsmaterial Polycarbonatedevice mounting Flush
SurfaceEnvironment relative humidity 0…95 %environmental characteristic No UV resistantPacking Units Package 1 Weight 54.110 gPackage 1 Height 14.000 mmPackage 1 width 87.200 mmPackage 1 Length 87.200 mmSKU: n/a -
Schneider Circuit Breakers, SCHNEIDER SECTIONS
Miniature circuit-breaker, Acti9 iC60H, 2P, 4 A, C curve, 10000 A (IEC 60898-1), 70 kA (IEC 60947-2) A9F84204
Schneider Circuit Breakers, SCHNEIDER SECTIONSMiniature circuit-breaker, Acti9 iC60H, 2P, 4 A, C curve, 10000 A (IEC 60898-1), 70 kA (IEC 60947-2) A9F84204
Main device application Distributionrange Acti 9product name Acti 9 iC60product or component type Miniature circuit-breakerdevice short name IC60Hpoles description 2Pnumber of protected poles 2[In] rated current 4 Anetwork type AC
DCtrip unit technology Thermal-magneticcurve code Cbreaking capacity 10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
15 kA Icu at <= 125 V DC conforming to EN/IEC 60947-2
70 kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2
70 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
70 kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2
70 kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2
70 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2utilisation category Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2suitability for isolation Yes conforming to EN 60898-1
Yes conforming to EN 60947-2
Yes conforming to IEC 60898-1
Yes conforming to IEC 60947-2standards IEC 60947-2
IEC 60898-1
EN 60947-2
EN 60898-1quality labels NFComplementary network frequency 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 70 kA 100 % conforming to EN 60947-2 – 220…240 V AC 50/60 Hz
70 kA 100 % conforming to IEC 60947-2 – 220…240 V AC 50/60 Hz
70 kA 100 % conforming to EN 60947-2 – 380…415 V AC 50/60 Hz
70 kA 100 % conforming to IEC 60947-2 – 380…415 V AC 50/60 Hz
7500 A 75 % conforming to EN 60898-1 – 400 V AC 50/60 Hz
7500 A 75 % conforming to IEC 60898-1 – 400 V AC 50/60 Hz
70 kA 100 % conforming to IEC 60947-2 – 12…133 V AC 50/60 Hz
70 kA 100 % conforming to EN 60947-2 – 12…133 V AC 50/60 Hz
50 kA 100 % conforming to EN 60947-2 – 440 V AC 50/60 Hz
50 kA 100 % conforming to IEC 60947-2 – 440 V AC 50/60 Hz
15 kA 100 % conforming to IEC 60947-2 – 72…125 V DC
15 kA 100 % conforming to EN 60947-2 – 72…125 V DClimitation class 3 conforming to EN 60898-1
3 conforming to IEC 60898-1[Ui] rated insulation voltage 500 V AC 50/60 Hz conforming to EN 60947-2
500 V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6 kV conforming to EN 60947-2
6 kV conforming to IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Fixedmounting support DIN railcomb busbar and distribution block compatibility Top or bottom: YES9 mm pitches 4height 85 mmwidth 36 mmdepth 78.5 mmnet weight 0.25 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesconnections – terminals Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 2 N.m top or bottomearth-leakage protection Separate blockSKU: n/a -
CHINT
CHINT NL1-63 2P RCCB
NL1-63 2P
Control electric circuits. Protect people against indirect contacts and additional protection against direct contacts. Protect installations against fire hazard due to insulation faults. Residual current circuit breakers are used in housing, tertiary sector and industry.
DESCRIPTION
- Standard : IEC/EN 61008-1
- Rated Current (A) : 25,40,63,100
- Pole : 2P
- Rated Voltage Ue (V) : 230/400~240/415
- Rated frequency : 50/60
SKU: n/a
There are no reviews yet.