EZC100F3040 – Circuit breaker Easypact EZC100F – TMD – 40 A – 3 poles 3d
range of product |
EasyPact
|
|
---|---|---|
product or component type |
Circuit breaker
|
|
device short name |
Easypact EZC100F
|
|
circuit breaker name |
Easypact EZC100F
|
|
device application |
Distribution
|
|
poles description |
3P
|
|
protected poles description |
3t
|
|
network type |
AC
DC |
|
network frequency |
50/60 Hz
|
|
[In] rated current |
100 A at 40 °C
|
|
[Ui] rated insulation voltage |
690 V AC 50/60 Hz conforming to IEC 60947-2
|
|
[Uimp] rated impulse withstand voltage |
6 kV conforming to IEC 60947-2
|
|
[Ue] rated operational voltage |
550 V AC 50/60 Hz conforming to IEC 60947-2
250 V DC conforming to IEC 60947-2 |
|
breaking capacity code |
F
|
|
breaking capacity |
25 kA Icu at 110…130 V AC 50/60 Hz conforming to IEC 60947-2
25 kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2 5 kA Icu at 125 V DC 1P conforming to IEC 60947-2 5 kA Icu at 250 V DC 2P conforming to IEC 60947-2 5 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 400…415 V AC 50/60 Hz conforming to IEC 60947-2 7.5 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
|
[Ics] rated service breaking capacity |
12.5 kA at 110/130 V AC 50/60 Hz conforming to IEC 60947-2
12.5 kA at 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA at 125 V DC conforming to IEC 60947-2 2.5 kA at 250 V DC conforming to IEC 60947-2 2.5 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2 5 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2 5 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 3.75 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
|
suitability for isolation |
Yes conforming to IEC 60947-2
|
|
utilisation category |
Category A
|
|
trip unit name |
TM-D
|
|
trip unit technology |
Thermal-magnetic
|
|
trip unit rating |
40 A at 50 °C
|
|
protection type |
Short-circuit protection
Overload protection |
|
pollution degree |
3 conforming to IEC 60664-1
3 conforming to IEC 947-1 |
control type |
Toggle
|
|
---|---|---|
mounting mode |
Fixed
|
|
mounting support |
Backplate
|
|
upside connection |
Front
|
|
downside connection |
Front
|
|
mechanical durability |
8500 cycles
|
|
electrical durability |
Category A: 1500 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2
|
|
connection pitch |
25 mm
|
|
local signalling |
Positive contact indication
|
|
neutral protection setting |
Without protection
|
|
earth-leakage protection |
Without
|
|
height |
130 mm
|
|
width |
75 mm
|
|
depth |
60 mm
|
₦17,999.00
Vendor Information
- 5.00 rating from 1 review
-
Schneider Circuit Breakers, SCHNEIDER SECTIONS
Easy9 miniature circuit breaker- 4P – 32 A – C curve – 6000 A – 400 V EZ9F56432
Schneider Circuit Breakers, SCHNEIDER SECTIONSEasy9 miniature circuit breaker- 4P – 32 A – C curve – 6000 A – 400 V EZ9F56432
Main range Easy9device application Distributionproduct or component type Miniature circuit-breakerdevice short name Easy9 MCBPoles 4Pnumber of protected poles 4[In] rated current 32 Anetwork type ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 10000 A Icn at 220 V AC 50/60 Hz conforming to IEC 60898-1
6000 A Icn at 400 V AC 50/60 Hz conforming to IEC 60898-1suitability for isolation Yes conforming to IEC 60898-1Complementary network frequency 50 Hz[Ue] rated operational voltage 220 V AC 50/60 Hz
400 V AC 50/60 Hzmagnetic tripping limit 5…10 x In[Ics] rated service breaking capacity 6 kA 100 % x Icn at 400 V AC 50/60 Hz conforming to IEC 60898-1[Ui] rated insulation voltage 500 V AC 50/60 Hz conforming to IEC 60898-1[Uimp] rated impulse withstand voltage 4 kV conforming to IEC 60898-1contact position indicator Yescontrol type Togglelocal signalling Withoutmounting mode Clip-onmounting support DIN rail9 mm pitches 8height 81 mmwidth 72 mmdepth 66.5 mmcolour Grey (RAL 7035)mechanical durability 10000 cycleselectrical durability 4000 cyclesconnections – terminals Tunnel type terminal (top or bottom) 1…25 mm² flexible
Tunnel type terminal (top or bottom) 1…35 mm² rigidtightening torque 3.5 N.m top or bottomSKU: n/a -
SOLAR POWERED
Solar Panel SG80W MONO
High Quality Monocrystalline solar panel
• Perfect for 12-volt battery charging or multiple panels can be wired in series for 24/48-volt battery charging or for grid-tied or off-grid solar applications.
• Diodes are pre-installed in junction box and a pair of 28 inches cables with MC4 connectors comes with the panel automatically.SKU: n/a -
CHANGEOVER SWITCHES, GEAR SWITCHES & CHANGEOVER
ABB CHANGEOVER SWITCH 400A with Enclosure
Including a black plastic IP65 I-0-II pistol type handle (see the table below), shaft and bolt set for the cable connection. Handle padlockable in the 0-position, door interlock in the I- and Iipositions and when padlocked.
Dimensions
-
- Product Net Width:
- 265 mm
-
- Product Net Height:
- 185 mm
-
- Product Net Depth / Length:
- 203 mm
-
- Product Net Weight:
- 7.415 kg
16.35 lb
Technical
-
- Rated Operational Current AC-21A (Ie):
- (380 … 415 V) 400 A
(500 V) 400 A
(690 V) 400 A
-
- Rated Operational Current AC-22A (Ie):
- (380 … 415 V) 400 A
(500 V) 400 A
(690 V) 400 A
-
- Rated Operational Current AC-23A (Ie):
- (380 … 415 V) 400 A
(500 V) 400 A
(690 V) 400 A
-
- Rated Operational Current AC-31B (Ie):
- (380 … 415 V) 400 A
-
- Rated Operational Current AC-33B (Ie):
- (380 … 415 V) 400 A
-
- Rated Operational Power AC-23A (Pe):
- (380 … 415 V) 220 kW
(500 V) 280 kW
(690 V) 400 kW
-
- Conventional Free-air Thermal Current (Ith):
- q = 40 °C 400 A
-
- Conventional Thermal Current (Ithe):
- Fully Enclosed 400 A
-
- Rated Impulse Withstand Voltage (Uimp):
- 12 kV
-
- Rated Insulation Voltage (Ui):
- 1000 V
-
- Rated Operational Voltage:
- 1000 V
-
- Rated Short-time Withstand Current (Icw):
- for 1 s 15 kiloampere rms
-
- Power Loss:
- 10 W
SKU: n/a -
-
TRANSFORMER
BETA 1000KVA/33/0.415V COPPER/COPPER WINDING TRANSFORMER
Produced within a power range between 10 – 100.000 kVA , up to 170 kV high voltage level, three phase or single phase, oil immersed, ONAN, ONAF, OFWF, with Off-Load or On-Load Tap Changer, used both external and internal.
Dimensions of transformer conservator are determined and designed after several heat calculations of the oil stored in expansion tank and oil level changes by heat.
Being open to atmosphere, oil pressure changes continuously in Conservator Type Transformers due to thermal effects and exchange of air is dehumidified via air breather silicagel.SKU: n/a -
CIRCUIT BREAKERS
IC60N – miniature circuit breaker – 3P – 63A – C curve
Main device application Distributionrange Acti 9product name Acti 9 iC60product or component type Miniature circuit-breakerdevice short name IC60Npoles description 3Pnumber of protected poles 3[In] rated current 63 Anetwork type DC
ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
36 kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2
10 kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2
20 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2
36 kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2
10 kA Icu at <= 180 V DC conforming to EN/IEC 60947-2utilisation category Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2suitability for isolation Yes conforming to EN 60898-1
Yes conforming to EN 60947-2
Yes conforming to IEC 60898-1
Yes conforming to IEC 60947-2standards EN 60898-1
EN 60947-2
IEC 60898-1
IEC 60947-2Complementary network frequency 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 15 kA 75 % conforming to EN 60947-2 – 220…240 V AC 50/60 Hz
7.5 kA 75 % conforming to EN 60947-2 – 380…415 V AC 50/60 Hz
4.5 kA 75 % conforming to EN 60947-2 – 440 V AC 50/60 Hz
15 kA 75 % conforming to IEC 60947-2 – 220…240 V AC 50/60 Hz
7.5 kA 75 % conforming to IEC 60947-2 – 380…415 V AC 50/60 Hz
4.5 kA 75 % conforming to IEC 60947-2 – 440 V AC 50/60 Hz
27 kA 75 % conforming to IEC 60947-2 – 12…133 V AC 50/60 Hz
27 kA 75 % conforming to EN 60947-2 – 12…133 V AC 50/60 Hz
6000 A 100 % conforming to EN 60898-1 – 400 V AC 50/60 Hz
6000 A 100 % conforming to IEC 60898-1 – 400 V AC 50/60 Hz
10 kA 100 % conforming to IEC 60947-2 – 125…180 V DC
10 kA 100 % conforming to EN 60947-2 – 125…180 V DC[Ui] rated insulation voltage 500 V AC 50/60 Hz conforming to EN 60947-2
500 V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6 kV conforming to EN 60947-2
6 kV conforming to IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Fixedmounting support DIN railcomb busbar and distribution block compatibility Top or bottom: YES9 mm pitches 6height 85 mmwidth 54 mmdepth 78.5 mmnet weight 0.375 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesconnections – terminals Single terminal (top or bottom) 1…35 mm² rigid
Single terminal (top or bottom) 1…25 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 3.5 N.m top or bottomearth-leakage protection Separate blockSKU: n/a