Low Voltage Products and Systems, SCHNEIDER SECTIONS
EZC100N4050 Circuit breaker Easypact EZC100N – TMD – 50 A – 4 poles 3d
range of product |
EasyPact
|
|
---|---|---|
product or component type |
Circuit breaker
|
|
device short name |
Easypact EZC100N
|
|
circuit breaker name |
Easypact EZC100N
|
|
device application |
Distribution
|
|
poles description |
4P
|
|
protected poles description |
3t
|
|
network type |
DC
AC |
|
network frequency |
50/60 Hz
|
|
[In] rated current |
100 A at 40 °C
|
|
[Ui] rated insulation voltage |
690 V AC 50/60 Hz conforming to IEC 60947-2
|
|
[Uimp] rated impulse withstand voltage |
6 kV conforming to IEC 60947-2
|
|
[Ue] rated operational voltage |
550 V AC 50/60 Hz conforming to IEC 60947-2
250 V DC conforming to IEC 60947-2 |
|
breaking capacity code |
N
|
|
breaking capacity |
10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
25 kA Icu at 110…130 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2 5 kA Icu at 125 V DC 1P conforming to IEC 60947-2 5 kA Icu at 250 V DC 2P conforming to IEC 60947-2 5 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 415 V AC 50/60 Hz conforming to IEC 60947-2 18 kA Icu at 380…400 V AC 50/60 Hz conforming to IEC 60947-2 |
|
[Ics] rated service breaking capacity |
5 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
2.5 kA at 125 V DC conforming to IEC 60947-2 2.5 kA at 250 V DC conforming to IEC 60947-2 2.5 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2 12.5 kA at 220…240 V AC 50/60 Hz conforming to IEC 60947-2 12.5 kA at 110…130 V AC 50/60 Hz conforming to IEC 60947-2 9 kA at 380…400 V AC 50/60 Hz conforming to IEC 60947-2 7.5 kA at 415 V AC 50/60 Hz conforming to IEC 60947-2 |
|
suitability for isolation |
Yes conforming to IEC 60947-2
|
|
utilisation category |
Category A
|
|
trip unit name |
TM-D
|
|
trip unit technology |
Thermal-magnetic
|
|
trip unit rating |
50 A at 50 °C
|
|
protection type |
Overload protection
Short-circuit protection |
|
pollution degree |
3 conforming to IEC 60947
|
control type |
Toggle
|
|
---|---|---|
mounting mode |
Fixed
|
|
mounting support |
Backplate
|
|
upside connection |
Front
|
|
downside connection |
Front
|
|
mechanical durability |
8500 cycles
|
|
electrical durability |
Category A: 1500 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2
|
|
connection pitch |
25 mm
|
|
local signalling |
Positive contact indication
|
|
neutral protection setting |
Without protection
|
|
earth-leakage protection |
Without
|
|
height |
130 mm
|
|
width |
100 mm
|
|
depth |
60 mm
|
₦39,999.00
Compare-
TRANSFORMER
BETA 500KVA/33/0.415V COPPER/COPPER WINDING TRANSFORMER
Produced within a power range between 10 – 100.000 kVA , up to 170 kV high voltage level, three phase or single phase, oil immersed, ONAN, ONAF, OFWF, with Off-Load or On-Load Tap Changer, used both external and internal.
Dimensions of transformer conservator are determined and designed after several heat calculations of the oil stored in expansion tank and oil level changes by heat.
Being open to atmosphere, oil pressure changes continuously in Conservator Type Transformers due to thermal effects and exchange of air is dehumidified via air breather silicagel.SKU: n/a -
Electro, LIGHT SWITCHES & ELECTRICAL SOCKETS
Lisse – Switched Socket – 1 gang – 13A SP 2USB Satin Brass with Black Interior GGBL30102USBABSBS
Electro, LIGHT SWITCHES & ELECTRICAL SOCKETSLisse – Switched Socket – 1 gang – 13A SP 2USB Satin Brass with Black Interior GGBL30102USBABSBS
Main range Lisseaesthetic name Screwless decoproduct or component type Switched socketdevice presentation Complete productoutlet standard Britishtype of packing BagComplementary switch function 1-poleactuator Rockernumber of gangs 1 gangfixing mode Concealed screwsconnections – terminals Screw terminalsmaterial Stainless steeltype of installation Indoordepth 32 mmwidth 87 mmheight 87 mmnet weight 0.149 kgSKU: n/a -
LIGHT SWITCHES & ELECTRICAL SOCKETS
32A 1 Gang Full-Flat Double Rocker Switch with Neon, Sliver Bronze E8431D32_SZ
LIGHT SWITCHES & ELECTRICAL SOCKETS32A 1 Gang Full-Flat Double Rocker Switch with Neon, Sliver Bronze E8431D32_SZ
Main range ZENceloproduct or component type Switchload type Resistivecolour tint Silver bronzecover frame colour tint Silver bronzeComplementary device mounting Surface
Flushrated current 32 A at 250 V AC 50/60 Hzlocal signalling Indicator light, neon (amber)number of gangs 1 gangmaterial Polycarbonate + GF 20 %: grid plate
Polycarbonate: base
Polycarbonate: cover
Polycarbonate: surroundconnections – terminals Brass rod terminalsembedding depth 22 mmwidth 87 mmheight 87 mmdepth 30.2 mmSKU: n/a -
Schneider Circuit Breakers, SCHNEIDER SECTIONS
Switch disconnector iSW – 2P – 100 A – 415 V A9S65291 ISOLATOR SWITCH
Schneider Circuit Breakers, SCHNEIDER SECTIONSSwitch disconnector iSW – 2P – 100 A – 415 V A9S65291 ISOLATOR SWITCH
Main range Acti 9product name Acti 9 iSWproduct or component type Switch disconnectordevice short name ISWdevice application Isolation
Controlpoles description 2Putilisation category AC-22Asuitability for isolation YesComplementary [Ie] rated operational current 100 A at 415 V AC 50/60 Hz[Ue] rated operational voltage 415 V AC 50/60 Hz[Icm] rated short-circuit making capacity 5 kA switch-disconnector alone[Icw] rated short-time withstand current 1500 A[Ui] rated insulation voltage 500 V AC 50/60 Hz[Uimp] rated impulse withstand voltage 6 kVcontrol type Togglelocal signalling ON/OFF indicationcontact position indicator Yesmounting mode Fixedmounting support DIN railcomb busbar and distribution block compatibility Top or bottom: YES9 mm pitches 4height 85 mmwidth 36 mmdepth 73 mmcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesconnections – terminals Tunnel type terminals (top or bottom) – <= 1 x 50 mm² – rigid
Tunnel type terminals (top or bottom) – <= 1 x 35 mm² – flexible
Tunnel type terminals (top or bottom) – <= 1 x 35 mm² – flexible with ferrulewire stripping length 9 mmtightening torque 3.5 N.mSKU: n/a