EZC250N3125 Circuit breaker Easypact EZC250N – TMD – 125 A – 3 poles 3d
range of product |
EasyPact
|
|
---|---|---|
product or component type |
Circuit breaker
|
|
device short name |
Easypact EZC250N
|
|
circuit breaker name |
Easypact EZC250N
|
|
device application |
Distribution
|
|
poles description |
3P
|
|
protected poles description |
3t
|
|
network type |
AC
DC |
|
network frequency |
50/60 Hz
|
|
[In] rated current |
250 A at 40 °C
|
|
[Ui] rated insulation voltage |
690 V AC 50/60 Hz conforming to IEC 60947-2
|
|
[Uimp] rated impulse withstand voltage |
6 kV conforming to IEC 60947-2
|
|
[Ue] rated operational voltage |
550 V AC 50/60 Hz conforming to IEC 60947-2
250 V DC conforming to IEC 60947-2 |
|
breaking capacity code |
N
|
|
breaking capacity |
20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 110…130 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 125 V DC 1P conforming to IEC 60947-2 20 kA Icu at 250 V DC 2P conforming to IEC 60947-2 25 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 400…415 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 |
|
[Ics] rated service breaking capacity |
10 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
25 kA at 110/130 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 125 V DC conforming to IEC 60947-2 10 kA at 250 V DC conforming to IEC 60947-2 25 kA at 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2 4 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2 12.5 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2 12.5 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 |
|
suitability for isolation |
Yes conforming to IEC 60947-2
|
|
utilisation category |
Category A
|
|
trip unit name |
TM-D
|
|
trip unit technology |
Thermal-magnetic
|
|
trip unit rating |
125 A at 50 °C
|
|
protection type |
Short-circuit protection
Overload protection |
|
pollution degree |
3 conforming to IEC 60664-1
3 conforming to IEC 947-1 |
control type |
Toggle
|
|
---|---|---|
mounting mode |
Fixed
|
|
mounting support |
Backplate
|
|
upside connection |
Front
|
|
downside connection |
Front
|
|
mechanical durability |
10000 cycles
|
|
electrical durability |
Category A: 5000 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2
|
|
connection pitch |
35 mm
|
|
local signalling |
Positive contact indication
|
|
neutral protection setting |
Without protection
|
|
earth-leakage protection |
Without
|
|
height |
165 mm
|
|
width |
105 mm
|
|
depth |
60 mm
|
₦56,000.00
Compare-
ELECTRICAL INDUSTRIAL, Electro, RECLINE CABLES
Cometstar Nigeria Cable NAY 4 X 70.0MM Per Meter
The construction and material are determined by three main factors:
• Working voltage, determining the thickness of the insulation;
• Current-carrying capacity, determining the cross-sectional size of the conductor(s);
• Environmental conditions such as temperature, water, chemical or sunlight exposure, and mechanical impact, determining the form and composition of the outer cable jacketSKU: Cometstar Nigeria Cable NAY 4 X 70.0MM-1 -
Electro, Schneider Industrial Sockets, SCHNEIDER SECTIONS
Thorsman – Cable reel 25m HO5VVF3G1.5 IP20 BS RCD IMT33146
Electro, Schneider Industrial Sockets, SCHNEIDER SECTIONSThorsman – Cable reel 25m HO5VVF3G1.5 IP20 BS RCD IMT33146
Main range PROchantierproduct or component type Cable reeldevice application Power supply[In] rated current 13 AComplementary cable length 25 mcable cross section 1.5 mm²type of cable H05VV-F3G1.5quantity per set Set of 1height 260 mmwidth 352 mmdepth 192 mmnet weight 4.53 kgSKU: n/a -
ELECTRICAL INDUSTRIAL, TRANSFORMER
MEKSAN Transformer 750kVA 11/415kV
Meksan Transformer manufacture distribution and power transformer from 50 kVA up to 50 MVA. Our products are produced in accordance with the TS 267 and the IEC60076 standards. Our production is documented with the TSE (Türkish Standard Institue) standards confortmity, ISO 9001:2000 quality system and ISO 14001 environmental management system certificates.
SKU: n/a -
-
LIGHT SWITCHES & ELECTRICAL SOCKETS, SCHNEIDER SECTIONS
Ultimate Screwless flat plate – rocker plate switch – 1 gang – black nickel GU1412BBN
LIGHT SWITCHES & ELECTRICAL SOCKETS, SCHNEIDER SECTIONSUltimate Screwless flat plate – rocker plate switch – 1 gang – black nickel GU1412BBN
Main range of product Ultimaterange Ultimateaesthetic name Screwless flat plateproduct or component type Plate switchcontrol type Rockerswitch function 1-pole 2-wayrated current 16 AX at 230 V ACComplementary connections – terminals Screw terminalsmaterial Steelquantity per set Set of 1number of gangs 1 gangdevice mounting Wall mountedheight 88 mmwidth 88 mmdepth 24 mmSKU: n/a -
CIRCUIT BREAKERS, DISTRIBUTION BOARDS
Easy9 miniature circuit breaker- 2P – 25 A – C curve – 6000 A – 230 V
CIRCUIT BREAKERS, DISTRIBUTION BOARDSEasy9 miniature circuit breaker- 2P – 25 A – C curve – 6000 A – 230 V
Schneider Electric Easy9 Miniature Circuit Breaker- 2P – 6 A – C Curve – 6000 A – 230 V
Main range Easy9device application Distributionproduct or component type Miniature circuit-breakerdevice short name Easy9 MCBPoles 2Pnumber of protected poles 2[In] rated current 25 Anetwork type ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 10000 A Icn at 220 V AC 50/60 Hz conforming to IEC 60898-1
6000 A Icn at 400 V AC 50/60 Hz conforming to IEC 60898-1suitability for isolation Yes conforming to IEC 60898-1Complementary network frequency 50/60 Hz[Ue] rated operational voltage 220 V AC 50/60 Hz
400 V AC 50/60 Hzmagnetic tripping limit 5…10 x In[Ics] rated service breaking capacity 6 kA 100 % x Icn at 230 V AC 50/60 Hz conforming to IEC 60898-1[Ui] rated insulation voltage 500 V AC 50/60 Hz conforming to IEC 60898-1[Uimp] rated impulse withstand voltage 4 kV conforming to IEC 60898-1contact position indicator Yescontrol type Togglelocal signalling Withoutmounting mode Clip-onmounting support DIN rail9 mm pitches 4height 81 mmwidth 36 mmdepth 66.5 mmcolour Grey (RAL 7035)mechanical durability 10000 cycleselectrical durability 4000 cyclesconnections – terminals Tunnel type terminal (top or bottom) 1…25 mm² rigid
Tunnel type terminal (top or bottom) 1…16 mm² flexibletightening torque 2 N.m top or bottomearth-leakage protection WithoutEnvironment standards IEC 60898-1product certifications CEIP degree of protection IP20 conforming to IEC 60529pollution degree 2tropicalisation 2relative humidity 95 % at -5…60 °Cambient air temperature for operation -5…60 °Cambient air temperature for storage -40…85 °CSKU: n/a