EZC250N3125 Circuit breaker Easypact EZC250N – TMD – 125 A – 3 poles 3d
range of product |
EasyPact
|
|
---|---|---|
product or component type |
Circuit breaker
|
|
device short name |
Easypact EZC250N
|
|
circuit breaker name |
Easypact EZC250N
|
|
device application |
Distribution
|
|
poles description |
3P
|
|
protected poles description |
3t
|
|
network type |
AC
DC |
|
network frequency |
50/60 Hz
|
|
[In] rated current |
250 A at 40 °C
|
|
[Ui] rated insulation voltage |
690 V AC 50/60 Hz conforming to IEC 60947-2
|
|
[Uimp] rated impulse withstand voltage |
6 kV conforming to IEC 60947-2
|
|
[Ue] rated operational voltage |
550 V AC 50/60 Hz conforming to IEC 60947-2
250 V DC conforming to IEC 60947-2 |
|
breaking capacity code |
N
|
|
breaking capacity |
20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 110…130 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 125 V DC 1P conforming to IEC 60947-2 20 kA Icu at 250 V DC 2P conforming to IEC 60947-2 25 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 400…415 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 |
|
[Ics] rated service breaking capacity |
10 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
25 kA at 110/130 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 125 V DC conforming to IEC 60947-2 10 kA at 250 V DC conforming to IEC 60947-2 25 kA at 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2 4 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2 12.5 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2 12.5 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 |
|
suitability for isolation |
Yes conforming to IEC 60947-2
|
|
utilisation category |
Category A
|
|
trip unit name |
TM-D
|
|
trip unit technology |
Thermal-magnetic
|
|
trip unit rating |
125 A at 50 °C
|
|
protection type |
Short-circuit protection
Overload protection |
|
pollution degree |
3 conforming to IEC 60664-1
3 conforming to IEC 947-1 |
control type |
Toggle
|
|
---|---|---|
mounting mode |
Fixed
|
|
mounting support |
Backplate
|
|
upside connection |
Front
|
|
downside connection |
Front
|
|
mechanical durability |
10000 cycles
|
|
electrical durability |
Category A: 5000 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2
|
|
connection pitch |
35 mm
|
|
local signalling |
Positive contact indication
|
|
neutral protection setting |
Without protection
|
|
earth-leakage protection |
Without
|
|
height |
165 mm
|
|
width |
105 mm
|
|
depth |
60 mm
|
₦206,000.00
Compare-
ELECTRICAL FITTINGS, Electro, INDOOR LIGHTS, LED LIGHTS, LIGHTING
LEDVANCE LED DOWNLIGHT 20WATT RECESSED LDECO 865K
ELECTRICAL FITTINGS, Electro, INDOOR LIGHTS, LED LIGHTS, LIGHTINGLEDVANCE LED DOWNLIGHT 20WATT RECESSED LDECO 865K
Product benefits
- Advanced functionality due to already included DALI driver
- DALI driver with individual luminaire current set-up already installed
- High luminous efficacy
- Energy savings up to 60 % (compared to luminaires that use CFL lamps)
- Very homogenous light
- Functional design
- Easy installation with fast connection
SKU: n/a -
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONS
Acti9 iC60N 4P 63A C Miniature Circuit breaker A9F44463
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONSActi9 iC60N 4P 63A C Miniature Circuit breaker A9F44463
Main range Acti 9product name Disbo iC60product or component type Miniature circuit-breakerdevice short name IC60Npoles description 4Pnumber of protected poles 4[In] rated current 63 Anetwork type AC/DCtrip unit technology Thermal-magneticcurve code Cbreaking capacity 6 kA Icu at 100…133 V DC conforming to EN/IEC 60947-2
6000 A Icn at 415 V AC 50/60 Hz conforming to EN/IEC 60898-1
36 kA Icu at 12…133 V AC 50/60 Hz conforming to EN/IEC 60947-2
20 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
10 kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2
6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2utilisation category Category A conforming to EN/IEC 60947-2Complementary network frequency 50/60 Hz[Ue] rated operational voltage 440 V AC 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 27 kA 75 % conforming to EN/IEC 60947-2 – 12…133 V AC 50/60 Hz
15 kA 75 % conforming to EN/IEC 60947-2 – 220…240 V AC 50/60 Hz
7.5 kA 75 % conforming to EN/IEC 60947-2 – 380…415 V AC 50/60 Hz
4.5 kA 75 % conforming to EN/IEC 60947-2 – 440 V AC 50/60 Hz
6000 A 100 % conforming to EN/IEC 60898-1 – 415 V AC 50/60 Hz
6 kA 100 % conforming to EN/IEC 60947-2 – 100…133 V DClimitation class 3 conforming to EN/IEC 60947-2[Ui] rated insulation voltage 500 V AC 50/60 Hz[Uimp] rated impulse withstand voltage 6 kV conforming to EN/IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Clip-onmounting support Rail9 mm pitches 8height 85 mmwidth 72 mmdepth 78.5 mmnet weight 0.5 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesprovision for padlocking Padlockableconnections – terminals Single terminal (top or bottom) 1…35 mm² rigid
Single terminal (top or bottom) 1…25 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 3.5 N.m top or bottomearth-leakage protection Separate blockSKU: n/a -
LED LIGHTS, OUTDOOR LIGHTS
Wall lights White Good condition + 18 W LED in or Exterior Utility Waterproof
LED LIGHTS, OUTDOOR LIGHTSWall lights White Good condition + 18 W LED in or Exterior Utility Waterproof
Available In White
Our LED bulkheads are great for offering additional light to the outside of your property.
Each one of these fittings are constructed with a thick strong poly carbonate body which is corrosive resistant and built to last in all weather conditions. These also have integrated LEDs which is a high powered 18 watts giving a nice bright output, therefore no lamp is required and will never have the need to change the lamp.Compact Utility Bulkhead Specification
Outstanding Value
Weatherproof Strong Poly Carbonate Construction
Finish White
Thick Frosted Diffuser
Bulb Type : Integrated SMD LED
Wattage :18 Watts
Equivalent Light Output To 120w Standard Bulb
30,000 Hour Bulb Life
1150 Lumens
Ultra Energy Saving – Uses 90% Less Electricity Than Standard Bulbs A++ rated
Voltage : 85-240 Volts
SKU: n/a -
ELECTRICAL INDUSTRIAL, TRANSFORMER
BETA 500KVA/33/0.415V COPPER/COPPER WINDING TRANSFORMER
Produced within a power range between 10 – 100.000 kVA , up to 170 kV high voltage level, three phase or single phase, oil immersed, ONAN, ONAF, OFWF, with Off-Load or On-Load Tap Changer, used both external and internal.
Dimensions of transformer conservator are determined and designed after several heat calculations of the oil stored in expansion tank and oil level changes by heat.
Being open to atmosphere, oil pressure changes continuously in Conservator Type Transformers due to thermal effects and exchange of air is dehumidified via air breather silicagel.SKU: n/a -
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONS
Easy9 miniature circuit breaker- 2P – 10 A – C curve – 6000 A – 230 V EZ9F56210
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONSEasy9 miniature circuit breaker- 2P – 10 A – C curve – 6000 A – 230 V EZ9F56210
Main range Easy9device application Distributionproduct or component type Miniature circuit-breakerdevice short name Easy9 MCBPoles 2Pnumber of protected poles 2[In] rated current 10 Anetwork type ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 10000 A Icn at 220 V AC 50/60 Hz conforming to IEC 60898-1
6000 A Icn at 400 V AC 50/60 Hz conforming to IEC 60898-1suitability for isolation Yes conforming to IEC 60898-1Complementary network frequency 50/60 Hz[Ue] rated operational voltage 220 V AC 50/60 Hz
400 V AC 50/60 Hzmagnetic tripping limit 5…10 x In[Ics] rated service breaking capacity 6 kA 100 % x Icn at 230 V AC 50/60 Hz conforming to IEC 60898-1[Ui] rated insulation voltage 500 V AC 50/60 Hz conforming to IEC 60898-1[Uimp] rated impulse withstand voltage 4 kV conforming to IEC 60898-1contact position indicator Yescontrol type Togglelocal signalling Withoutmounting mode Clip-onmounting support DIN rail9 mm pitches 4height 81 mmwidth 36 mmdepth 66.5 mmcolour Grey (RAL 7035)mechanical durability 10000 cycleselectrical durability 4000 cyclesconnections – terminals Tunnel type terminal (top or bottom) 1…25 mm² rigid
Tunnel type terminal (top or bottom) 1…16 mm² flexibletightening torque 2 N.m top or bottomearth-leakage protection WithoutSKU: n/a -
CHINT
N266 series digital clamp meter
N266 and N266F are kind of trinity half digital pincer-like meter with stable performance, safety and reliability. Adopting A/D converter with large-scaled collected circuit and equipped with overload protecting circuit for overall instrument, it is characterized with all range overload protection, low voltage indication, data hold, inductive indication and fast measurement, becoming the first choice for the electrical measurement.
SKU: n/a
There are no reviews yet.