Schneider Circuit Breakers, SCHNEIDER SECTIONS
Miniature circuit-breaker, Acti9 iC60H, 2P, 2 A, C curve, 10000 A (IEC 60898-1), 70 kA (IEC 60947-2) A9F84202
Schneider Circuit Breakers, SCHNEIDER SECTIONSMiniature circuit-breaker, Acti9 iC60H, 2P, 2 A, C curve, 10000 A (IEC 60898-1), 70 kA (IEC 60947-2) A9F84202
Main device application Distributionrange Acti 9product name Acti 9 iC60product or component type Miniature circuit-breakerdevice short name IC60Hpoles description 2Pnumber of protected poles 2[In] rated current 2 Anetwork type AC
DCtrip unit technology Thermal-magneticcurve code Cbreaking capacity 10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
15 kA Icu at <= 125 V DC conforming to EN/IEC 60947-2
70 kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2
70 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
70 kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2
70 kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2
70 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2utilisation category Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2suitability for isolation Yes conforming to EN 60898-1
Yes conforming to EN 60947-2
Yes conforming to IEC 60898-1
Yes conforming to IEC 60947-2standards IEC 60947-2
IEC 60898-1
EN 60947-2
EN 60898-1quality labels NFComplementary network frequency 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 70 kA 100 % conforming to EN 60947-2 – 220…240 V AC 50/60 Hz
70 kA 100 % conforming to IEC 60947-2 – 220…240 V AC 50/60 Hz
70 kA 100 % conforming to EN 60947-2 – 380…415 V AC 50/60 Hz
70 kA 100 % conforming to IEC 60947-2 – 380…415 V AC 50/60 Hz
7500 A 75 % conforming to EN 60898-1 – 400 V AC 50/60 Hz
7500 A 75 % conforming to IEC 60898-1 – 400 V AC 50/60 Hz
70 kA 100 % conforming to IEC 60947-2 – 12…133 V AC 50/60 Hz
70 kA 100 % conforming to EN 60947-2 – 12…133 V AC 50/60 Hz
50 kA 100 % conforming to EN 60947-2 – 440 V AC 50/60 Hz
50 kA 100 % conforming to IEC 60947-2 – 440 V AC 50/60 Hz
15 kA 100 % conforming to IEC 60947-2 – 72…125 V DC
15 kA 100 % conforming to EN 60947-2 – 72…125 V DClimitation class 3 conforming to EN 60898-1
3 conforming to IEC 60898-1[Ui] rated insulation voltage 500 V AC 50/60 Hz conforming to EN 60947-2
500 V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6 kV conforming to EN 60947-2
6 kV conforming to IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Fixedmounting support DIN railcomb busbar and distribution block compatibility Top or bottom: YES9 mm pitches 4height 85 mmwidth 36 mmdepth 78.5 mmnet weight 0.25 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesconnections – terminals Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 2 N.m top or bottomearth-leakage protection Separate blockSKU: n/a -
CHINT
CHINT Kwh Meter Single
DDSU666 series three phase three wire electronic energy meter (DIN Rail) Summary :
DDSU666 series electronic energy meter is designed for power monitoring and energy measurement such as power system, communication industry, construction industry, etc. to be a new generation of programmable.
DDSU666 series three phase three wire electronic energy meter (DIN Rail)
Summary:
DDSU666 series electronic energy meter is designed for power monitoring and energy measurement such as power system, communication industry, construction industry, etc. to be a new generation of programmable intelligent instrument, integrated with measurement and communication function, mainly used for real-time measurement and display for the electrical parameters such as voltage, current, active power, reactive power, frequency, power factor, energy in the electrical circuit, etc.
1、Main functions and characteristics
◆DIN35mm Standard DIN-Rail, seven modulus with segment LCD display
◆Measurement function: Characterized with measurement for three phase three wire voltage, current, frequency, active power, power factor, active energy and reactive energy
◆communication function: RS485 communication interface, supporting DL/T645-2007 protocol, customizable for MODBUS-RTU protocol
◆Multi-rate function: it supports four rates including top, peak, flat, valley rate.
SKU: n/a -
Schneider Circuit Breakers, SCHNEIDER SECTIONS
Acti9 iC60N 4P 40A C Miniature Circuit breaker A9F44440
Schneider Circuit Breakers, SCHNEIDER SECTIONSActi9 iC60N 4P 40A C Miniature Circuit breaker A9F44440
Main range Acti 9product name Disbo iC60product or component type Miniature circuit-breakerdevice short name IC60Npoles description 4Pnumber of protected poles 4[In] rated current 40 Anetwork type AC/DCtrip unit technology Thermal-magneticcurve code Cbreaking capacity 6 kA Icu at 100…133 V DC conforming to EN/IEC 60947-2
6000 A Icn at 415 V AC 50/60 Hz conforming to EN/IEC 60898-1
36 kA Icu at 12…133 V AC 50/60 Hz conforming to EN/IEC 60947-2
20 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
10 kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2
6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2utilisation category Category A conforming to EN/IEC 60947-2Complementary network frequency 50/60 Hz[Ue] rated operational voltage 440 V AC 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 27 kA 75 % conforming to EN/IEC 60947-2 – 12…133 V AC 50/60 Hz
15 kA 75 % conforming to EN/IEC 60947-2 – 220…240 V AC 50/60 Hz
7.5 kA 75 % conforming to EN/IEC 60947-2 – 380…415 V AC 50/60 Hz
4.5 kA 75 % conforming to EN/IEC 60947-2 – 440 V AC 50/60 Hz
6000 A 100 % conforming to EN/IEC 60898-1 – 415 V AC 50/60 Hz
6 kA 100 % conforming to EN/IEC 60947-2 – 100…133 V DClimitation class 3 conforming to EN/IEC 60947-2[Ui] rated insulation voltage 500 V AC 50/60 Hz[Uimp] rated impulse withstand voltage 6 kV conforming to EN/IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Clip-onmounting support Rail9 mm pitches 8height 85 mmwidth 72 mmdepth 78.5 mmnet weight 0.5 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesprovision for padlocking Padlockableconnections – terminals Single terminal (top or bottom) 1…35 mm² rigid
Single terminal (top or bottom) 1…25 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 3.5 N.m top or bottomearth-leakage protection Separate blockSKU: n/a -
-
SCHNEIDER SECTIONS, Schneider Thorsman Testmeters
Thorsman 4 in 1 Digital detector IMT23104
Main range Thorsmanproduct or component type Digital detectorsupply battery 9 V 6F22Complementary display type LCD and sound signaltype of setting Manualdevice composition detector
pencil slider
pencil hole
2 m measure tapelocal signalling edge of object detection by icon indicator
object detection by spotlightcontrol type Button mark dots on the wall surface
Button selection modemaximum detection depth AC mode: <50 mm for 90…250 V at 50…60 Hz
Stud mode: wood stud detection of 30 x 30 mm <14 mm
Metal mode: iron pipe detection of 20 mm <25 mmlanguage Finnish
Norwegian
Danish
English
Swedishheight 180 mmwidth 73 mmdepth 32 mmnet weight 213 g with batterySKU: n/a
There are no reviews yet.