IC60H – miniature circuit breaker – 2P – 25A – C curve A9F84225
device application |
Distribution
|
|
---|---|---|
range |
Acti 9
|
|
product name |
Acti 9 iC60
|
|
product or component type |
Miniature circuit-breaker
|
|
device short name |
IC60H
|
|
poles description |
2P
|
|
number of protected poles |
2
|
|
[In] rated current |
25 A
|
|
network type |
AC
DC |
|
trip unit technology |
Thermal-magnetic
|
|
curve code |
C
|
|
breaking capacity |
10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
42 kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2 30 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at <= 125 V DC conforming to EN/IEC 60947-2 42 kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
|
utilisation category |
Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2 |
|
suitability for isolation |
Yes conforming to EN 60898-1
Yes conforming to EN 60947-2 Yes conforming to IEC 60898-1 Yes conforming to IEC 60947-2 |
|
standards |
EN 60898-1
EN 60947-2 IEC 60898-1 IEC 60947-2 |
network frequency |
50/60 Hz
|
|
---|---|---|
magnetic tripping limit |
8 x In +/- 20 %
|
|
[Ics] rated service breaking capacity |
15 kA 50 % conforming to EN 60947-2 – 220…240 V AC 50/60 Hz
7.5 kA 50 % conforming to EN 60947-2 – 380…415 V AC 50/60 Hz 5 kA 50 % conforming to EN 60947-2 – 440 V AC 50/60 Hz 15 kA 50 % conforming to IEC 60947-2 – 220…240 V AC 50/60 Hz 7.5 kA 50 % conforming to IEC 60947-2 – 380…415 V AC 50/60 Hz 5 kA 50 % conforming to IEC 60947-2 – 440 V AC 50/60 Hz 7500 A 75 % conforming to EN 60898-1 – 400 V AC 50/60 Hz 7500 A 75 % conforming to IEC 60898-1 – 400 V AC 50/60 Hz 21 kA 50 % conforming to IEC 60947-2 – 12…133 V AC 50/60 Hz 21 kA 50 % conforming to EN 60947-2 – 12…133 V AC 50/60 Hz 15 kA 100 % conforming to IEC 60947-2 – 72…125 V DC 15 kA 100 % conforming to EN 60947-2 – 72…125 V DC |
|
limitation class |
3 conforming to EN 60898-1
3 conforming to IEC 60898-1 |
|
[Ui] rated insulation voltage |
500 V AC 50/60 Hz conforming to EN 60947-2
500 V AC 50/60 Hz conforming to IEC 60947-2 |
|
[Uimp] rated impulse withstand voltage |
6 kV conforming to EN 60947-2
6 kV conforming to IEC 60947-2 |
|
contact position indicator |
Yes
|
|
control type |
Toggle
|
|
local signalling |
Trip indicator
|
|
mounting mode |
Fixed
|
|
mounting support |
DIN rail
|
|
comb busbar and distribution block compatibility |
Top or bottom: YES
|
|
9 mm pitches |
4
|
|
height |
85 mm
|
|
width |
36 mm
|
|
depth |
78.5 mm
|
|
net weight |
0.25 kg
|
|
colour |
White
|
|
mechanical durability |
20000 cycles
|
|
electrical durability |
10000 cycles
|
|
connections – terminals |
Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexible |
|
wire stripping length |
14 mm for top or bottom connection
|
|
tightening torque |
2 N.m top or bottom
|
|
earth-leakage protection |
Separate block
|
₦7,999.00
Compare-
CHANGEOVER SWITCHES, Electro, GEAR SWITCHES & CHANGEOVER
STANLEY 63A Changeover
Stanley Products always provides new technology for all industrial requirements, with excellent value for their investments. You can depend upon for matchless quality on all Stanley Products. Our new range products in sheet metal Side Handle Operating Switchgear are made as per industrial requirements with powder coating. This certificate of “Stanley” original products, issued with the assurance as the same has been manufactured in accordance with requirement of IEC-60947-3 (2005-06). Quality system, standards and mechanism has been tested satisfactory to the specific test as follows: 1. Dielectric Test 2. Mechanical Operation Test 3. High Voltage Test 4. Insulation Resistance Test 5. Temperature Rise Test 6. Mini Volt Drop Test STANLEY 63A Changeover
SKU: 62A -
-
ELECTRICAL INDUSTRIAL, Electro, Schneider, SCHNEIDER ELECTRIC BRANDS, SCHNEIDER SECTIONS, TRANSFORMER
Schneider 300kVA 11/400 CuCu Transformer
ELECTRICAL INDUSTRIAL, Electro, Schneider, SCHNEIDER ELECTRIC BRANDS, SCHNEIDER SECTIONS, TRANSFORMERSchneider 300kVA 11/400 CuCu Transformer
Features
Distribution transformers from Schneider Electric are available in ratings from 100kVA upto 4000kVA at voltages upto 36kV. They can be supplied in many types and styles, with standard industry fittings or bespoke design to the customers specific requirements. Choices available include:
- Type – Free Breathing (with or without conservator) or Hermetically sealed
- Style – Ground Mounted Cable Connected, Unit Substation or Bespoke to customer requirements
- Insulating Fluids – Mineral Oil or Midel 7131 Transformer Fluid
- Eco losses
- In addition, transformers can be supplied with directly mounted MV or LV switchgear to form an assembled package substation
Benefits
- Large choice of ratings, types and styles
- Bespoke or Standard Design
- Manufactured to specific customer requirements
- Available with MV & LV Switchgear
- Direct to Site Deliveries
- Ease of Installation
Applications
- Energy
- Infrastructure
- Commercial
SKU: n/a -
COMPUTING, PRINTERS
HP LASERJET ENTERPRISE FLOW M632Z MULTIFUNCTION PRINTER
- Print, copy, scan, fax; AIO multitasking supported
- Print speed letter: Up to 65 ppm (black)
- 1×550 and 2,000-sheet HCI feeder and stand; 3-bin stapler/stacker; 150-sheet ADF; Pull out keyboard
- FCC Class A emissions – for use in commercial environments, not residential
SKU: n/a -
CIRCUIT BREAKERS
Circuit breaker Easypact EZC100H – TMD – 63 A – 4 poles 3d
Main range of product EasyPactproduct or component type Circuit breakerdevice short name Easypact EZC100Hcircuit breaker name Easypact EZC100Hdevice application Distributionpoles description 4Pprotected poles description 3tnetwork type AC
DCnetwork frequency 50/60 Hz[In] rated current 100 A at 40 °C[Ui] rated insulation voltage 690 V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947-2[Ue] rated operational voltage 550 V AC 50/60 Hz conforming to IEC 60947-2
250 V DC conforming to IEC 60947-2breaking capacity code Hbreaking capacity 10 kA Icu at 125 V DC 1P conforming to IEC 60947-2
10 kA Icu at 250 V DC 2P conforming to IEC 60947-2
10 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2
100 kA Icu at 110…130 V AC 50/60 Hz conforming to IEC 60947-2
20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
30 kA Icu at 380…400 V AC 50/60 Hz conforming to IEC 60947-2
30 kA Icu at 415 V AC 50/60 Hz conforming to IEC 60947-2[Ics] rated service breaking capacity 5 kA at 125 V DC conforming to IEC 60947-2
5 kA at 250 V DC conforming to IEC 60947-2
5 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
2.5 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2
15 kA at 380…400 V AC 50/60 Hz conforming to IEC 60947-2
25 kA at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
50 kA at 110…130 V AC 50/60 Hz conforming to IEC 60947-2
7.5 kA at 415 V AC 50/60 Hz conforming to IEC 60947-2suitability for isolation Yes conforming to IEC 60947-2utilisation category Category Atrip unit name TM-Dtrip unit technology Thermal-magnetictrip unit rating 63 A at 50 °Cprotection type Overload protection
Short-circuit protectionpollution degree 3 conforming to IEC 60947Complementary control type Togglemounting mode Fixedmounting support Backplateupside connection Frontdownside connection Frontmechanical durability 8500 cycleselectrical durability Category A: 1500 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2connection pitch 25 mmlocal signalling Positive contact indicationneutral protection setting Without protectionearth-leakage protection Withoutheight 130 mmwidth 100 mmdepth 60 mmSKU: n/a
There are no reviews yet.