Schneider Circuit Breakers, SCHNEIDER SECTIONS
IC60H – miniature circuit breaker – 2P – 32A – C curve A9F84232
device application |
Distribution
|
|
---|---|---|
range |
Acti 9
|
|
product name |
Acti 9 iC60
|
|
product or component type |
Miniature circuit-breaker
|
|
device short name |
IC60H
|
|
poles description |
2P
|
|
number of protected poles |
2
|
|
[In] rated current |
32 A
|
|
network type |
DC
AC |
|
trip unit technology |
Thermal-magnetic
|
|
curve code |
C
|
|
breaking capacity |
10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
42 kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2 30 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at <= 125 V DC conforming to EN/IEC 60947-2 42 kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
|
utilisation category |
Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2 |
|
suitability for isolation |
Yes conforming to EN 60898-1
Yes conforming to EN 60947-2 Yes conforming to IEC 60898-1 Yes conforming to IEC 60947-2 |
|
standards |
EN 60898-1
IEC 60898-1 EN 60947-2 IEC 60947-2 |
network frequency |
50/60 Hz
|
|
---|---|---|
magnetic tripping limit |
8 x In +/- 20 %
|
|
[Ics] rated service breaking capacity |
15 kA 50 % conforming to EN 60947-2 – 220…240 V AC 50/60 Hz
7.5 kA 50 % conforming to EN 60947-2 – 380…415 V AC 50/60 Hz 5 kA 50 % conforming to EN 60947-2 – 440 V AC 50/60 Hz 15 kA 50 % conforming to IEC 60947-2 – 220…240 V AC 50/60 Hz 7.5 kA 50 % conforming to IEC 60947-2 – 380…415 V AC 50/60 Hz 5 kA 50 % conforming to IEC 60947-2 – 440 V AC 50/60 Hz 7500 A 75 % conforming to EN 60898-1 – 400 V AC 50/60 Hz 7500 A 75 % conforming to IEC 60898-1 – 400 V AC 50/60 Hz 21 kA 50 % conforming to IEC 60947-2 – 12…133 V AC 50/60 Hz 21 kA 50 % conforming to EN 60947-2 – 12…133 V AC 50/60 Hz 15 kA 100 % conforming to IEC 60947-2 – 72…125 V DC 15 kA 100 % conforming to EN 60947-2 – 72…125 V DC |
|
limitation class |
3 conforming to EN 60898-1
3 conforming to IEC 60898-1 |
|
[Ui] rated insulation voltage |
500 V AC 50/60 Hz conforming to EN 60947-2
500 V AC 50/60 Hz conforming to IEC 60947-2 |
|
[Uimp] rated impulse withstand voltage |
6 kV conforming to EN 60947-2
6 kV conforming to IEC 60947-2 |
|
contact position indicator |
Yes
|
|
control type |
Toggle
|
|
local signalling |
Trip indicator
|
|
mounting mode |
Fixed
|
|
mounting support |
DIN rail
|
|
comb busbar and distribution block compatibility |
Top or bottom: YES
|
|
9 mm pitches |
4
|
|
height |
85 mm
|
|
width |
36 mm
|
|
depth |
78.5 mm
|
|
net weight |
0.25 kg
|
|
colour |
White
|
|
mechanical durability |
20000 cycles
|
|
electrical durability |
10000 cycles
|
|
connections – terminals |
Single terminal (top or bottom) 1…35 mm² rigid
Single terminal (top or bottom) 1…25 mm² flexible |
|
wire stripping length |
14 mm for top or bottom connection
|
|
tightening torque |
3.5 N.m top or bottom
|
|
earth-leakage protection |
Separate block
|
₦7,999.00
Compare-
SOLAR POWERED
Mobiya Portable Grid Lighting + USB Charging Port – Schneider Electric
Portable lighting with integrated mobile charger for people living with limited access to grid.
- Powered by universal AC adapter with voltage range : 110VAC – 270VAC, 50/60Hz
- Uniform lighting with maximum brightness more than 120 Lumens
- 3 Step dimming – “Low / Medium / High” with lighting hours – “48 / 12 / 6” hours
- User Friendly – 7 simple ways to use the Lamp
- Water resistant up to 0.5m for 1 hour
- Drop impact resistant from a height of 1.5m
- Superior Lithium Ferro Phosphate battery with 1500 Cycles
- Integrated USB Mobile phone charger and USB Cable with 5 adapters
SKU: n/a -
LIGHT SWITCHES & ELECTRICAL SOCKETS, SCHNEIDER SECTIONS
Universal Shaver Unit, Horizontal, White E84T727H_WE
LIGHT SWITCHES & ELECTRICAL SOCKETS, SCHNEIDER SECTIONSUniversal Shaver Unit, Horizontal, White E84T727H_WE
Main range ZENceloproduct or component type Shaver socketinstallation direction Horizontalinput voltage 240 V AC 50 Hzoutput voltage 115 V AC 50 Hz
240 V AC 50 Hzmaterial Polycarbonate: base
Polycarbonate: grid plate
Polycarbonate: surroundcolour tint WhiteComplementary device mounting Surface
Flushcable cross section 1…2.5 mm²rated operational power in VA 20 VAconnections – terminals Pillar terminal without pressure plateelectrical insulation class Class Bwidth 147 mmheight 87 mmdepth 49.3 mmSKU: n/a -
ACCESSORIES
APC ESSENTIAL SURGE ARREST 5 OUTLETS 230V – PM5-UK
The Essential SurgeArrest series offers a great value for home equipment and business applications such as small office/home computers
The APC will protect your equipment from the threat of bad power
Device Type Surge suppressor – external
Input Voltage AC 230 V/Frequency Required 50/60 HzSKU: APC 5outlet -
LIGHT SWITCHES & ELECTRICAL SOCKETS, SCHNEIDER SECTIONS
Ultimate Screwless flat plate – data/telephone socket – RJ11 – stainless steel GU7451BSS
LIGHT SWITCHES & ELECTRICAL SOCKETS, SCHNEIDER SECTIONSUltimate Screwless flat plate – data/telephone socket – RJ11 – stainless steel GU7451BSS
Main range of product Ultimateaesthetic name Screwless flat plateproduct or component type Data/telephone sockettelephone socket type RJ11colour tint Stainless steel matt
BlackComplementary number of gangs 1 gangfixing mode By screwsconnections – terminals Screw terminalsmaterial Steelquantity per set Set of 1depth 88 mmwidth 88 mmheight 35 mmSKU: n/a -
Schneider Circuit Breakers, SCHNEIDER SECTIONS
Easy9 miniature circuit breaker- 2P – 10 A – C curve – 6000 A – 230 V EZ9F56210
Schneider Circuit Breakers, SCHNEIDER SECTIONSEasy9 miniature circuit breaker- 2P – 10 A – C curve – 6000 A – 230 V EZ9F56210
Main range Easy9device application Distributionproduct or component type Miniature circuit-breakerdevice short name Easy9 MCBPoles 2Pnumber of protected poles 2[In] rated current 10 Anetwork type ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 10000 A Icn at 220 V AC 50/60 Hz conforming to IEC 60898-1
6000 A Icn at 400 V AC 50/60 Hz conforming to IEC 60898-1suitability for isolation Yes conforming to IEC 60898-1Complementary network frequency 50/60 Hz[Ue] rated operational voltage 220 V AC 50/60 Hz
400 V AC 50/60 Hzmagnetic tripping limit 5…10 x In[Ics] rated service breaking capacity 6 kA 100 % x Icn at 230 V AC 50/60 Hz conforming to IEC 60898-1[Ui] rated insulation voltage 500 V AC 50/60 Hz conforming to IEC 60898-1[Uimp] rated impulse withstand voltage 4 kV conforming to IEC 60898-1contact position indicator Yescontrol type Togglelocal signalling Withoutmounting mode Clip-onmounting support DIN rail9 mm pitches 4height 81 mmwidth 36 mmdepth 66.5 mmcolour Grey (RAL 7035)mechanical durability 10000 cycleselectrical durability 4000 cyclesconnections – terminals Tunnel type terminal (top or bottom) 1…25 mm² rigid
Tunnel type terminal (top or bottom) 1…16 mm² flexibletightening torque 2 N.m top or bottomearth-leakage protection WithoutSKU: n/a -
LIGHT SWITCHES & ELECTRICAL SOCKETS
16 A X/20 A 2 gang 2wfull – flat switch White E8432_2_WE
Main range ZENceloproduct or component type Switchdevice application Controlload type Inductive
Incandescent lamp
Fluorescent lamp
ResistiveComplementary device mounting Surface
Flushswitch function 2-wayrated current 20 A/16 AX at 250 V AC 50 Hznumber of gangs 2 gangsmaterial Polycarbonate + GF 20 %: grid plate
Polycarbonate: base
Polycarbonate: cover
Polycarbonate: surroundSKU: n/a
There are no reviews yet.