IC60N – miniature circuit breaker – 3P – 63A – C curve
device application |
Distribution
|
|
---|---|---|
range |
Acti 9
|
|
product name |
Acti 9 iC60
|
|
product or component type |
Miniature circuit-breaker
|
|
device short name |
IC60N
|
|
poles description |
3P
|
|
number of protected poles |
3
|
|
[In] rated current |
63Â A
|
|
network type |
DC
AC |
|
trip unit technology |
Thermal-magnetic
|
|
curve code |
C
|
|
breaking capacity |
6000Â A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
36Â kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2 10Â kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2 20Â kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2 6Â kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 36Â kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2 10Â kA Icu at <= 180 V DC conforming to EN/IEC 60947-2 |
|
utilisation category |
Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2 |
|
suitability for isolation |
Yes conforming to EN 60898-1
Yes conforming to EN 60947-2 Yes conforming to IEC 60898-1 Yes conforming to IEC 60947-2 |
|
standards |
EN 60898-1
EN 60947-2 IEC 60898-1 IEC 60947-2 |
network frequency |
50/60 Hz
|
|
---|---|---|
magnetic tripping limit |
8 x In +/- 20 %
|
|
[Ics] rated service breaking capacity |
15Â kA 75Â % conforming to EN 60947-2 – 220…240 V AC 50/60 Hz
7.5Â kA 75Â % conforming to EN 60947-2 – 380…415 V AC 50/60 Hz 4.5Â kA 75Â % conforming to EN 60947-2 – 440 V AC 50/60 Hz 15Â kA 75Â % conforming to IEC 60947-2 – 220…240 V AC 50/60 Hz 7.5Â kA 75Â % conforming to IEC 60947-2 – 380…415 V AC 50/60 Hz 4.5Â kA 75Â % conforming to IEC 60947-2 – 440 V AC 50/60 Hz 27Â kA 75Â % conforming to IEC 60947-2 – 12…133 V AC 50/60 Hz 27Â kA 75Â % conforming to EN 60947-2 – 12…133 V AC 50/60 Hz 6000Â A 100Â % conforming to EN 60898-1 – 400 V AC 50/60 Hz 6000Â A 100Â % conforming to IEC 60898-1 – 400 V AC 50/60 Hz 10Â kA 100Â % conforming to IEC 60947-2 – 125…180 V DC 10Â kA 100Â % conforming to EN 60947-2 – 125…180 V DC |
|
[Ui] rated insulation voltage |
500Â V AC 50/60 Hz conforming to EN 60947-2
500Â V AC 50/60 Hz conforming to IEC 60947-2 |
|
[Uimp] rated impulse withstand voltage |
6Â kV conforming to EN 60947-2
6Â kV conforming to IEC 60947-2 |
|
contact position indicator |
Yes
|
|
control type |
Toggle
|
|
local signalling |
Trip indicator
|
|
mounting mode |
Fixed
|
|
mounting support |
DIN rail
|
|
comb busbar and distribution block compatibility |
Top or bottom: YES
|
|
9 mm pitches |
6
|
|
height |
85Â mm
|
|
width |
54Â mm
|
|
depth |
78.5Â mm
|
|
net weight |
0.375Â kg
|
|
colour |
White
|
|
mechanical durability |
20000Â cycles
|
|
electrical durability |
10000Â cycles
|
|
connections – terminals |
Single terminal (top or bottom) 1…35 mm² rigid
Single terminal (top or bottom) 1…25 mm² flexible |
|
wire stripping length |
14Â mm for top or bottom connection
|
|
tightening torque |
3.5Â N.m top or bottom
|
|
earth-leakage protection |
Separate block
|
₦16,000.00
Compare-
ELECTRICAL INDUSTRIAL, Schneider, TRANSFORMER
Schneider 500kVA 33/400 CuCu Transformer
Features
Distribution transformers from Schneider Electric are available in ratings from 100kVA upto 4000kVA at voltages upto 36kV. They can be supplied in many types and styles, with standard industry fittings or bespoke design to the customers specific requirements. Choices available include:
- Type – Free Breathing (with or without conservator) or Hermetically sealed
- Style – Ground Mounted Cable Connected, Unit Substation or Bespoke to customer requirements
- Insulating Fluids – Mineral Oil or Midel 7131 Transformer Fluid
- Eco losses
- In addition, transformers can be supplied with directly mounted MV or LV switchgear to form an assembled package substation
Benefits
- Large choice of ratings, types and styles
- Bespoke or Standard Design
- Manufactured to specific customer requirements
- Available with MV & LV Switchgear
- Direct to Site Deliveries
- Ease of Installation
Applications
- Energy
- Infrastructure
- Commercial
SKU: n/a -
Electro, LIGHT SWITCHES & ELECTRICAL SOCKETS
Lisse – Switched Socket – 1 gang – 13A SP 2USB Polished Chrome with Black Inter GGBL30102USBABSSS
Electro, LIGHT SWITCHES & ELECTRICAL SOCKETSLisse – Switched Socket – 1 gang – 13A SP 2USB Polished Chrome with Black Inter GGBL30102USBABSSS
Main range Lisseaesthetic name Screwless decoproduct or component type Switched socketdevice presentation Complete productoutlet standard Britishtype of packing BagComplementary switch function 1-poleactuator Rockernumber of gangs 1 gangfixing mode Concealed screwsconnections – terminals Screw terminalsmaterial Stainless steeltype of installation Indoordepth 32Â mmwidth 87Â mmheight 87Â mmnet weight 0.149Â kgSKU: n/a -
CABLE AND CABLE MANAGEMENT, Electro, SINGLE CORE WIRE
Doncaster Cables 2.5mm Single Core – Red
Product Description
Manufactured to BS 6004:2012 Table 3
Annealed Stranded Copper Conductor / PVC Insulated / PVC Sheathed. 300/500V
Designed for use in light industrial and domestic wiring. These cables are particularly suited for installation as meter tails and are intended for fixed installation in dry or damp premises.
These cables can be installed in conduit, in cable trunking and in cable ducting. Or where there is deemed little risk of mechanical damage these cables can be clipped direct, on cable tray, embedded or in free air. These cables are not intended to be laid underground.
Product Details
 Harmonisation Code Nominal Cross Sectional Area of Conductor (mm2) Nominal Stranding of Conductor (mm) Nominal Radial Thickness of insulation (mm) Nominal Radial Thickness of sheath (mm) Overall Diameter Lower Limit (mm) Overall Diameter Upper Limit (mm) Approximate Weight(kg/km) National Type 1.0 1 / 1.13 0.6 0.8 3.8 4.5 26 National Type 1.5 1 / 1.38 0.7 0.8 4.2 4.9 35 National Type 2.5 1 / 1.78 0.8 0.8 4.8 5.8 55 National Type 4.0 7 / 0.85 0.8 0.9 5.4 6.8 75 National Type 6.0 7 / 1.04 0.8 0.9 6.0 7.4 95 National Type 10.0 7 / 1.35 1.0 0.9 7.2 8.8 155 National Type 16.0 7 / 1.70 1.0 1.0 8.4 10.5 225 National Type 25.0 7 / 2.14 1.2 1.1 10.0 12.5 340 National Type 35.0 7 / 2.52 1.2 1.1 11.0 13.5 445 SKU: n/a -
LIGHT SWITCHES & ELECTRICAL SOCKETS
15A 250V 1 Gang Switched Socket KB15_15
Main range Vivaceproduct or component type Socket-outlet with switchdevice short name KB15device presentation Complete mechanismComplementary outlet poles configuration 2P + Enumber of gangs 1 gangColour tint Whitematerial Polycarbonate: grid plate
Polycarbonate: surround
Polycarbonate: baseprojecting depth 8Â mmdevice mounting Flushmounting support Wall mountedfixing mode By screw M3.5fixing center 60.3 mmembedding depth 35Â mmrated current 15 A at 250 V AC, resistivenetwork frequency 50 Hzcontacts material Brass and phosphor bronzeconnections – terminals Pillar terminalterminal identifier N
Earth
Ltightening torque 0.4 N.mclamping connection capacity 2.5 mm²width 87 mmheight 87 mmSKU: n/a -
Low Voltage Products and Systems, SCHNEIDER SECTIONS
EZC100F3080 – Circuit breaker Easypact EZC100F – TMD – 80 A – 3 poles 3d
Low Voltage Products and Systems, SCHNEIDER SECTIONSEZC100F3080 – Circuit breaker Easypact EZC100F – TMD – 80 A – 3 poles 3d
Main range of product EasyPactproduct or component type Circuit breakerdevice short name Easypact EZC100Fcircuit breaker name Easypact EZC100Fdevice application Distributionpoles description 3Pprotected poles description 3tnetwork type AC
DCnetwork frequency 50/60 Hz[In] rated current 100 A at 40 °C[Ui] rated insulation voltage 690 V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947-2[Ue] rated operational voltage 550 V AC 50/60 Hz conforming to IEC 60947-2
250 V DC conforming to IEC 60947-2breaking capacity code Fbreaking capacity 25Â kA Icu at 110…130 V AC 50/60 Hz conforming to IEC 60947-2
25Â kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
5Â kA Icu at 125 V DC 1P conforming to IEC 60947-2
5Â kA Icu at 250 V DC 2P conforming to IEC 60947-2
5Â kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2
10Â kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2
10Â kA Icu at 400…415 V AC 50/60 Hz conforming to IEC 60947-2
7.5Â kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2[Ics] rated service breaking capacity 12.5Â kA at 110/130 V AC 50/60 Hz conforming to IEC 60947-2
12.5Â kA at 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2
2.5Â kA at 125 V DC conforming to IEC 60947-2
2.5Â kA at 250 V DC conforming to IEC 60947-2
2.5Â kA at 550 V AC 50/60 Hz conforming to IEC 60947-2
5Â kA at 380 V AC 50/60 Hz conforming to IEC 60947-2
5Â kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
3.75 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2suitability for isolation Yes conforming to IEC 60947-2utilisation category Category Atrip unit name TM-Dtrip unit technology Thermal-magnetictrip unit rating 80 A at 50 °Cprotection type Short-circuit protection
Overload protectionpollution degree 3 conforming to IEC 60664-1
3 conforming to IEC 947-1Complementary control type Togglemounting mode Fixedmounting support Backplateupside connection Frontdownside connection Frontmechanical durability 8500Â cycleselectrical durability Category A: 1500Â cycles 415 V AC 50/60 Hz conforming to IEC 60947-2connection pitch 25Â mmlocal signalling Positive contact indicationneutral protection setting Without protectionearth-leakage protection Withoutheight 130Â mmwidth 75Â mmdepth 60Â mmSKU: n/a -
There are no reviews yet.