Schneider Circuit Breakers, SCHNEIDER SECTIONS
Miniature circuit-breaker, Acti9 iC60H, 2P, 10 A, C curve, 10000 A (IEC 60898-1), 15 kA (IEC 60947-2) A9F84210
device application |
Distribution
|
|
---|---|---|
range |
Acti 9
|
|
product name |
Acti 9 iC60
|
|
product or component type |
Miniature circuit-breaker
|
|
device short name |
IC60H
|
|
poles description |
2P
|
|
number of protected poles |
2
|
|
[In] rated current |
10 A
|
|
network type |
AC
DC |
|
trip unit technology |
Thermal-magnetic
|
|
curve code |
C
|
|
breaking capacity |
10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
42 kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2 30 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at <= 125 V DC conforming to EN/IEC 60947-2 42 kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
|
utilisation category |
Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2 |
|
suitability for isolation |
Yes conforming to EN 60898-1
Yes conforming to EN 60947-2 Yes conforming to IEC 60898-1 Yes conforming to IEC 60947-2 |
|
standards |
EN 60898-1
IEC 60947-2 IEC 60898-1 EN 60947-2 |
network frequency |
50/60 Hz
|
|
---|---|---|
magnetic tripping limit |
8 x In +/- 20 %
|
|
[Ics] rated service breaking capacity |
15 kA 50 % conforming to EN 60947-2 – 220…240 V AC 50/60 Hz
7.5 kA 50 % conforming to EN 60947-2 – 380…415 V AC 50/60 Hz 5 kA 50 % conforming to EN 60947-2 – 440 V AC 50/60 Hz 15 kA 50 % conforming to IEC 60947-2 – 220…240 V AC 50/60 Hz 7.5 kA 50 % conforming to IEC 60947-2 – 380…415 V AC 50/60 Hz 5 kA 50 % conforming to IEC 60947-2 – 440 V AC 50/60 Hz 7500 A 75 % conforming to EN 60898-1 – 400 V AC 50/60 Hz 7500 A 75 % conforming to IEC 60898-1 – 400 V AC 50/60 Hz 21 kA 50 % conforming to IEC 60947-2 – 12…133 V AC 50/60 Hz 21 kA 50 % conforming to EN 60947-2 – 12…133 V AC 50/60 Hz 15 kA 100 % conforming to IEC 60947-2 – 72…125 V DC 15 kA 100 % conforming to EN 60947-2 – 72…125 V DC |
|
limitation class |
3 conforming to EN 60898-1
3 conforming to IEC 60898-1 |
|
[Ui] rated insulation voltage |
500 V AC 50/60 Hz conforming to EN 60947-2
500 V AC 50/60 Hz conforming to IEC 60947-2 |
|
[Uimp] rated impulse withstand voltage |
6 kV conforming to EN 60947-2
6 kV conforming to IEC 60947-2 |
|
contact position indicator |
Yes
|
|
control type |
Toggle
|
|
local signalling |
Trip indicator
|
|
mounting mode |
Fixed
|
|
mounting support |
DIN rail
|
|
comb busbar and distribution block compatibility |
Top or bottom: YES
|
|
9 mm pitches |
4
|
|
height |
85 mm
|
|
width |
36 mm
|
|
depth |
78.5 mm
|
|
net weight |
0.25 kg
|
|
colour |
White
|
|
mechanical durability |
20000 cycles
|
|
electrical durability |
10000 cycles
|
|
connections – terminals |
Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexible |
|
wire stripping length |
14 mm for top or bottom connection
|
|
tightening torque |
2 N.m top or bottom
|
|
earth-leakage protection |
Separate block
|
₦7,999.00
Compare-
Schneider Mureva Floodlight, SCHNEIDER SECTIONS
Mureva lights, Floodlight 200W, IP65 230V IMT47223
Main range Murevarange of product Mureva lightsproduct name Floodlightproduct or component type Lampdevice application Ware-houses and parking garages
Residential
Media device support
Public areas
Secure lighting
Stadiums and arenasComplementary type of installation OutdoorTotal system power 200 Wlight source LED[Ue] rated operational voltage 230 V ACpower factor 0.9colour rendering index Ra=80luminous flux 20000 lmbulb lifespan 50000 hcolour temperature 6500 Kcolour Blackprovided equipment Sensorbeam angle 110 °shape Rectangularheight 342.0 mmwidth 278.0 mmdepth 61.0 mmnet weight 4.9 kgSKU: n/a -
Electro, SOCKETS & SWITCHES, SWITCHES
BG BRASS GEORGIAN LIGHT SWITCH PLATE – SINGLE 1 GANG 2 WAY
BG NBG12 Brass Georgian Light Switch Plate – Single 1 Gang 2 WayAT A GLANCE…- Top quality Brass finish – lightly lacquered to prevent finger marks
- Matching Brass rocker switch
- No visible plastic around switches
- Specification: 1 gang, 2 way, 10 amp (10AX)
- Requires a 16mm metal wall box
- Supplied with colour coded fixing screws
SKU: g7 -
-
LIGHT SWITCHES & ELECTRICAL SOCKETS
1 Gang Category 6 Data Outlet with Shutter KB31RJ6
Main range Vivacedevice short name KB31product or component type Data socket with shutterdevice presentation Complete mechanismcover frame colour tint WhiteComplementary communication network category 6number of gangs 1 gangtightening torque 0.4 N.mmaterial Polycarbonate: grid plate
Polycarbonate: surround
Polycarbonate: basedevice mounting Flushmounting support Wall mountedfixing mode By screw M3.5fixing center 60.3 mmwidth 86 mmheight 86 mmprojecting depth 8 mmembedding depth 35 mmSKU: n/a -
TRANSFORMER
BETA 1000KVA/11/0.415V COPPER/COPPER WINDING TRANSFORMER
Produced within a power range between 10 – 100.000 kVA , up to 170 kV high voltage level, three phase or single phase, oil immersed, ONAN, ONAF, OFWF, with Off-Load or On-Load Tap Changer, used both external and internal.
Dimensions of transformer conservator are determined and designed after several heat calculations of the oil stored in expansion tank and oil level changes by heat.
Being open to atmosphere, oil pressure changes continuously in Conservator Type Transformers due to thermal effects and exchange of air is dehumidified via air breather silicagel.SKU: n/a
There are no reviews yet.