Schneider Circuit Breakers, SCHNEIDER SECTIONS
Miniature circuit breaker, Easy9, 2P, 16 A, C curve, 6000 A EZ9F56216
range |
Easy9
|
|
---|---|---|
device application |
Distribution
|
|
product or component type |
Miniature circuit-breaker
|
|
device short name |
Easy9 MCB
|
|
Poles |
2P
|
|
number of protected poles |
2
|
|
[In] rated current |
16 A
|
|
network type |
AC
|
|
trip unit technology |
Thermal-magnetic
|
|
curve code |
C
|
|
breaking capacity |
10000 A Icn at 220 V AC 50/60 Hz conforming to IEC 60898-1
6000 A Icn at 400 V AC 50/60 Hz conforming to IEC 60898-1 |
|
suitability for isolation |
Yes conforming to IEC 60898-1
|
network frequency |
50/60 Hz
|
|
---|---|---|
[Ue] rated operational voltage |
220 V AC 50/60 Hz
400 V AC 50/60 Hz |
|
magnetic tripping limit |
5…10 x In
|
|
[Ics] rated service breaking capacity |
6 kA 100 % x Icn at 230 V AC 50/60 Hz conforming to IEC 60898-1
|
|
[Ui] rated insulation voltage |
500 V AC 50/60 Hz conforming to IEC 60898-1
|
|
[Uimp] rated impulse withstand voltage |
4 kV conforming to IEC 60898-1
|
|
contact position indicator |
Yes
|
|
control type |
Toggle
|
|
local signalling |
Without
|
|
mounting mode |
Clip-on
|
|
mounting support |
DIN rail
|
|
9 mm pitches |
4
|
|
height |
81 mm
|
|
width |
36 mm
|
|
depth |
66.5 mm
|
|
colour |
Grey (RAL 7035)
|
|
mechanical durability |
10000 cycles
|
|
electrical durability |
4000 cycles
|
|
connections – terminals |
Tunnel type terminal (top or bottom) 1…25 mm² rigid
Tunnel type terminal (top or bottom) 1…16 mm² flexible |
|
tightening torque |
2 N.m top or bottom
|
|
earth-leakage protection |
Without
|
₦3,350.00
Compare-
ELECTRICAL INDUSTRIAL, TRANSFORMER
MEKSAN Transformer 500kVA 11/415kV
Meksan Transformer manufacture distribution and power transformer from 50 kVA up to 50 MVA. Our products are produced in accordance with the TS 267 and the IEC60076 standards. Our production is documented with the TSE (Türkish Standard Institue) standards confortmity, ISO 9001:2000 quality system and ISO 14001 environmental management system certificates.
SKU: n/a -
CIRCUIT BREAKERS
C120H – circuit breaker – 3P – 100A – C curve
Main range of product C120range Acti 9product name C120product or component type Miniature circuit-breakerdevice short name C120Hdevice application Distributionpoles description 3Pnumber of protected poles 3[In] rated current 100 Anetwork type ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 15 kA Icu at <= 375 V DC conforming to EN/IEC 60947-2
15 kA Icu at 230…400 V AC 50/60 Hz conforming to EN/IEC 60947-2Complementary network frequency 50/60 Hz[Ue] rated operational voltage <= 375 V DC
230…400 V AC 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 15 kA 100 % conforming to EN/IEC 60947-2 – <= 375 V DC
7.5 kA 50 % conforming to EN/IEC 60947-2 – 230…400 V AC 50/60 Hzlimitation class 3 conforming to EN/IEC 60947-2[Ui] rated insulation voltage 500 V AC 50/60 Hz conforming to EN/IEC 60947-2[Uimp] rated impulse withstand voltage 6 kV conforming to EN/IEC 60947-2control type Togglelocal signalling ON/OFF indicationmounting mode Clip-onmounting support 35 mm symmetrical DIN rail9 mm pitches 9height 81 mmwidth 81 mmdepth 73 mmnet weight 0.615 kgcolour Whitemechanical durability 20000 cycleselectrical durability 5000 cyclesconnections – terminals Tunnel type terminals1…50 mm² rigid
Tunnel type terminals1.5…35 mm² flexiblewire stripping length 15 mmtightening torque 3.5 N.mearth-leakage protection Separate blockEnvironment standards EN/IEC 60947-2IP degree of protection IP20 conforming to IEC 60529pollution degree 3 conforming to IEC 60947-2overvoltage category IIItropicalisation 2 conforming to IEC 60068-1relative humidity 95 % at 55 °Cambient air temperature for operation -30…70 °Cambient air temperature for storage -40…80 °CSKU: n/a -
Schneider Circuit Breakers, SCHNEIDER SECTIONS
Miniature circuit-breaker, Acti9 iC60H, 2P, 1 A, C curve, 10000 A (IEC 60898-1), 70 kA (IEC 60947-2) A9F84201
Schneider Circuit Breakers, SCHNEIDER SECTIONSMiniature circuit-breaker, Acti9 iC60H, 2P, 1 A, C curve, 10000 A (IEC 60898-1), 70 kA (IEC 60947-2) A9F84201
Main device application Distributionrange Acti 9product name Acti 9 iC60product or component type Miniature circuit-breakerdevice short name IC60Hpoles description 2Pnumber of protected poles 2[In] rated current 1 Anetwork type DC
ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
15 kA Icu at <= 125 V DC conforming to EN/IEC 60947-2
70 kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2
70 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
70 kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2
70 kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2
70 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2utilisation category Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2suitability for isolation Yes conforming to EN 60898-1
Yes conforming to EN 60947-2
Yes conforming to IEC 60898-1
Yes conforming to IEC 60947-2standards EN 60898-1
IEC 60898-1
EN 60947-2
IEC 60947-2quality labels NFComplementary network frequency 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 70 kA 100 % conforming to EN 60947-2 – 220…240 V AC 50/60 Hz
70 kA 100 % conforming to IEC 60947-2 – 220…240 V AC 50/60 Hz
70 kA 100 % conforming to EN 60947-2 – 380…415 V AC 50/60 Hz
70 kA 100 % conforming to IEC 60947-2 – 380…415 V AC 50/60 Hz
7500 A 75 % conforming to EN 60898-1 – 400 V AC 50/60 Hz
7500 A 75 % conforming to IEC 60898-1 – 400 V AC 50/60 Hz
70 kA 100 % conforming to IEC 60947-2 – 12…133 V AC 50/60 Hz
70 kA 100 % conforming to EN 60947-2 – 12…133 V AC 50/60 Hz
50 kA 100 % conforming to EN 60947-2 – 440 V AC 50/60 Hz
50 kA 100 % conforming to IEC 60947-2 – 440 V AC 50/60 Hz
15 kA 100 % conforming to IEC 60947-2 – 72…125 V DC
15 kA 100 % conforming to EN 60947-2 – 72…125 V DClimitation class 3 conforming to EN 60898-1
3 conforming to IEC 60898-1[Ui] rated insulation voltage 500 V AC 50/60 Hz conforming to EN 60947-2
500 V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6 kV conforming to EN 60947-2
6 kV conforming to IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Fixedmounting support DIN railcomb busbar and distribution block compatibility Top or bottom: YES9 mm pitches 4height 85 mmwidth 36 mmdepth 78.5 mmnet weight 0.25 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesconnections – terminals Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 2 N.m top or bottomearth-leakage protection Separate blockSKU: n/a -
LIGHT SWITCHES & ELECTRICAL SOCKETS
Lisse – Switched Socket – 2 gang – 13A Mocha Bronze with Black Interior GGBL3020BMB
LIGHT SWITCHES & ELECTRICAL SOCKETSLisse – Switched Socket – 2 gang – 13A Mocha Bronze with Black Interior GGBL3020BMB
Main range Lisseaesthetic name Screwless decoproduct or component type Switched socketdevice presentation Complete productoutlet standard Britishcolour tint Cover plate: mocha bronze
Interior: blackquantity per set Set of 5type of packing BoxComplementary switch function 1-polerated current 13 A at 250 V AC 50/60 Hzactuator Rockernumber of gangs 2 gangspilot light without LEDfixing mode Concealed screwsconnections – terminals Screw terminalsmaterial Stainless steeltype of installation Indoordepth 36 mmwidth 148 mmheight 87 mmnet weight 0.198 kgSKU: n/a -
CHANGEOVER SWITCHES, Electro, GEAR SWITCHES & CHANGEOVER
ABB CHANGEOVER SWITCH 800A with Enclosure
-
-
-
- Long Description:
- Including a black plastic IP65 I-0-II pistol type handle (see the table below), shaft and bolt set for the cable connection. Handle not padlockable and no door interlocking. Operating angle 90° to achieve fast switching. Minimum OFF-time between transfer from I-II or II-I is 20 ms.
Categories
- Products » Low Voltage Products and Systems » Switches » Change-over and Transfer Switches » Manual Change-over Switches
-
-
Technical
-
- Rated Operational Current AC-21A (Ie):
- (380 … 415 V) 800 A
(500 V) 800 A
(690 V) 800 A
-
- Rated Operational Current AC-22A (Ie):
- (380 … 415 V) 800 A
(500 V) 800 A
(690 V) 800 A
-
- Rated Operational Current AC-23A (Ie):
- (380 … 415 V) 800 A
(500 V) 800 A
(690 V) 800 A
-
- Rated Operational Current AC-31B (Ie):
- (380 … 415 V) 800 A
-
- Rated Operational Current AC-33B (Ie):
- (380 … 415 V) 800 A
-
- Rated Operational Power AC-23A (Pe):
- (380 … 415 V) 450 kW
(500 V) 560 kW
(690 V) 800 kW
-
- Conventional Free-air Thermal Current (Ith):
- q = 40 °C 800 A
-
- Conventional Thermal Current (Ithe):
- Fully Enclosed 800 A
-
- Rated Impulse Withstand Voltage (Uimp):
- 12 kV
-
- Rated Insulation Voltage (Ui):
- 1000 V
-
- Rated Operational Voltage:
- 1000 V
-
- Rated Short-time Withstand Current (Icw):
- for 1 s 20 kiloampere rms
-
- Power Loss:
- 40 W
SKU: n/a -
-
CHINT
CHINT NU6-ⅡG/F Low-voltage Surge Arrester 15 – 40kA
NU6-ⅡG/F Low-voltage Surge Arrester
- Certificates: international certificates are under proceeding;
- Number of poles: 1, 2,3, 4;
- Electric ratings: 230/400V, AC50Hz;
- Application: Protect electric system and on-loading electrical apparatus from thunder and instantaneous over-voltage;
- Standard: IEC 61643-1, EN 61643-11
SKU: n/a