NX8 – MCB CHINT . ELECTRIC BOX 5way
Material: ABS/PC Plastic
Type: Wall-mounted electrical cabinet
Degree of protection: IP30
Meets standard: IEC/EN 60439-3 (IEC/EN 60670-24)
The MCB CHINT NX8 plastic electrical cabinet box is compact, sturdy, and has a high finish.
Can be used as a wall cabinet or used as a floating cabinet due to its versatile design. There are error lights, power failure.
ABS plastic helps to withstand factors such as heat, sunlight, increasing the life of the cabinet. The lid of the cabinet is made of transparent PC plastic, making it easy to see the equipment inside. Available with 4-sided wiring hole.
Standard DIN Rail, convenient to connect and install equipment
Parameters of MCB CHINT NX8 . plastic electrical cabinet box
- Material: ABS/PC . plastic
- Type: Wall mounted plastic electrical cabinet
- Protection level: IP30
- Meets standards: IEC/EN 60439-3 (IEC/EN 60670-24)
- Application: in civil electricity, industrial electricity, solar power
₦15,000.00
Vendor Information
- 5.00 rating from 1 review
-
SINGLE CORE WIRE
Doncaster Cables 10mm Single Core – Red
Product Description
Manufactured to BS 6004:2012 Table 3
Annealed Stranded Copper Conductor / PVC Insulated / PVC Sheathed. 300/500V
Designed for use in light industrial and domestic wiring. These cables are particularly suited for installation as meter tails and are intended for fixed installation in dry or damp premises.
These cables can be installed in conduit, in cable trunking and in cable ducting. Or where there is deemed little risk of mechanical damage these cables can be clipped direct, on cable tray, embedded or in free air. These cables are not intended to be laid underground.
Product Details
Harmonisation Code Nominal Cross Sectional Area of Conductor (mm2) Nominal Stranding of Conductor (mm) Nominal Radial Thickness of insulation (mm) Nominal Radial Thickness of sheath (mm) Overall Diameter Lower Limit (mm) Overall Diameter Upper Limit (mm) Approximate Weight(kg/km) National Type 1.0 1 / 1.13 0.6 0.8 3.8 4.5 26 National Type 1.5 1 / 1.38 0.7 0.8 4.2 4.9 35 National Type 2.5 1 / 1.78 0.8 0.8 4.8 5.8 55 National Type 4.0 7 / 0.85 0.8 0.9 5.4 6.8 75 National Type 6.0 7 / 1.04 0.8 0.9 6.0 7.4 95 National Type 10.0 7 / 1.35 1.0 0.9 7.2 8.8 155 National Type 16.0 7 / 1.70 1.0 1.0 8.4 10.5 225 National Type 25.0 7 / 2.14 1.2 1.1 10.0 12.5 340 National Type 35.0 7 / 2.52 1.2 1.1 11.0 13.5 445 SKU: n/a -
Schneider Circuit Breakers, SCHNEIDER SECTIONS
Acti9 iC60N 2P 63A C Miniature Circuit breaker A9F44263
Schneider Circuit Breakers, SCHNEIDER SECTIONSActi9 iC60N 2P 63A C Miniature Circuit breaker A9F44263
Main range Acti 9product name Disbo iC60product or component type Miniature circuit-breakerdevice short name IC60Npoles description 2Pnumber of protected poles 2[In] rated current 63 Anetwork type AC/DCtrip unit technology Thermal-magneticcurve code Cbreaking capacity 6 kA Icu at 100…133 V DC conforming to EN/IEC 60947-2
6000 A Icn at 415 V AC 50/60 Hz conforming to EN/IEC 60898-1
36 kA Icu at 12…133 V AC 50/60 Hz conforming to EN/IEC 60947-2
20 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
10 kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2
6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2utilisation category Category A conforming to EN/IEC 60947-2Complementary network frequency 50/60 Hz[Ue] rated operational voltage 440 V AC 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 27 kA 75 % conforming to EN/IEC 60947-2 – 12…133 V AC 50/60 Hz
15 kA 75 % conforming to EN/IEC 60947-2 – 220…240 V AC 50/60 Hz
7.5 kA 75 % conforming to EN/IEC 60947-2 – 380…415 V AC 50/60 Hz
4.5 kA 75 % conforming to EN/IEC 60947-2 – 440 V AC 50/60 Hz
6000 A 100 % conforming to EN/IEC 60898-1 – 415 V AC 50/60 Hz
6 kA 100 % conforming to EN/IEC 60947-2 – 100…133 V DClimitation class 3 conforming to EN/IEC 60947-2[Ui] rated insulation voltage 500 V AC 50/60 Hz[Uimp] rated impulse withstand voltage 6 kV conforming to EN/IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Clip-onmounting support Rail9 mm pitches 4height 85 mmwidth 36 mmdepth 78.5 mmnet weight 0.25 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesprovision for padlocking Padlockableconnections – terminals Single terminal (top or bottom) 1…35 mm² rigid
Single terminal (top or bottom) 1…25 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 3.5 N.m top or bottomearth-leakage protection Separate blockEnvironment standards EN/IEC 60947-2
EN/IEC 60898-1IP degree of protection IP20 conforming to IEC 60529pollution degree 3 conforming to EN/IEC 60947-2tropicalisation 2 conforming to IEC 60068-1relative humidity 95 % at 55 °Cambient air temperature for operation -35…70 °Cambient air temperature for storage -40…85 °CSKU: n/a -
SINGLE CORE WIRE
Doncaster Cables 16mm Single Core – Black
Product Description
Manufactured to BS 6004:2012 Table 3
Annealed Stranded Copper Conductor / PVC Insulated / PVC Sheathed. 300/500V
Designed for use in light industrial and domestic wiring. These cables are particularly suited for installation as meter tails and are intended for fixed installation in dry or damp premises.
These cables can be installed in conduit, in cable trunking and in cable ducting. Or where there is deemed little risk of mechanical damage these cables can be clipped direct, on cable tray, embedded or in free air. These cables are not intended to be laid underground.
Product Details
Harmonisation Code Nominal Cross Sectional Area of Conductor (mm2) Nominal Stranding of Conductor (mm) Nominal Radial Thickness of insulation (mm) Nominal Radial Thickness of sheath (mm) Overall Diameter Lower Limit (mm) Overall Diameter Upper Limit (mm) Approximate Weight(kg/km) National Type 1.0 1 / 1.13 0.6 0.8 3.8 4.5 26 National Type 1.5 1 / 1.38 0.7 0.8 4.2 4.9 35 National Type 2.5 1 / 1.78 0.8 0.8 4.8 5.8 55 National Type 4.0 7 / 0.85 0.8 0.9 5.4 6.8 75 National Type 6.0 7 / 1.04 0.8 0.9 6.0 7.4 95 National Type 10.0 7 / 1.35 1.0 0.9 7.2 8.8 155 National Type 16.0 7 / 1.70 1.0 1.0 8.4 10.5 225 National Type 25.0 7 / 2.14 1.2 1.1 10.0 12.5 340 National Type 35.0 7 / 2.52 1.2 1.1 11.0 13.5 445 SKU: n/a -
SOCKETS
BG 870 mfp Nexus Moulded White 45 Amp Double Pole Cooker Control Unit With 13 Amp Socket And LED 6 x 6
SOCKETSBG 870 mfp Nexus Moulded White 45 Amp Double Pole Cooker Control Unit With 13 Amp Socket And LED 6 x 6
BG 870 Nexus Moulded White 45 Amp Double Pole Cooker Control Unit with 13 Amp Socket and LED is a modern design that will blend with any décor. Suitable for use in domestic or commercial installations.
Features
- Stylish modern profile finished in White
- Covers to conceal fixing screws for a clean finish
- Colour Coded Terminals for easy installation
- Supplied with Space Adaptor Plate
- 2 Earth Terminals
SKU: goodman9 -
ARMOURED CABLE
Barliac 185mm x 1core PVC/PVC Unarmoured Cable
Armoured Cables are manufactured to BS-6346/IEC 60502 Standards. Typically, the construction of an aluminium or steel wire armoured cable comprises five components:
- Conductor: This is usually a plain stranded Copper Conductor.
- Insulation: Materials such as Poly-Vynyl Chloride (PVC) or Cross-linked Polyethylene (XLPE) provide good temperature resistance and excellent dielectric strength providing enhanced electrical properties.
- Bedding: This is a layer to create a protective barrier between armour and insulation.
- Sheath: the constituent parts of the cable are held together by a sheath offering a further level of protection. Black Poly-Vinyl Chloride sheaths can be carbon-loaded for UV stability.
- Voltage: Voltage ratings of 600/1000V, 6.35/11kV and 19/33kV
SKU: n/a