Smart Bright
LED Slim Panel
Edge-Lit Panel
Energy efficient
Easy to Install
₦48,500.00
CompareSmart Bright
LED Slim Panel
Edge-Lit Panel
Energy efficient
Easy to Install
Protect against
Ideal for
Max Current: 15 amps
Wait time: User adjustable from 2 minutes to 5 minutes
range |
Acti 9
|
|
---|---|---|
product name |
Disbo iC60
|
|
product or component type |
Miniature circuit-breaker
|
|
device short name |
IC60N
|
|
poles description |
2P
|
|
number of protected poles |
2
|
|
[In] rated current |
40 A
|
|
network type |
AC/DC
|
|
trip unit technology |
Thermal-magnetic
|
|
curve code |
C
|
|
breaking capacity |
6 kA Icu at 100…133 V DC conforming to EN/IEC 60947-2
6000 A Icn at 415 V AC 50/60 Hz conforming to EN/IEC 60898-1 36 kA Icu at 12…133 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
|
utilisation category |
Category A conforming to EN/IEC 60947-2
|
network frequency |
50/60 Hz
|
|
---|---|---|
[Ue] rated operational voltage |
440 V AC 50/60 Hz
|
|
magnetic tripping limit |
8 x In +/- 20 %
|
|
[Ics] rated service breaking capacity |
27 kA 75 % conforming to EN/IEC 60947-2 – 12…133 V AC 50/60 Hz
15 kA 75 % conforming to EN/IEC 60947-2 – 220…240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 – 380…415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 – 440 V AC 50/60 Hz 6000 A 100 % conforming to EN/IEC 60898-1 – 415 V AC 50/60 Hz 6 kA 100 % conforming to EN/IEC 60947-2 – 100…133 V DC |
|
limitation class |
3 conforming to EN/IEC 60947-2
|
|
[Ui] rated insulation voltage |
500 V AC 50/60 Hz
|
|
[Uimp] rated impulse withstand voltage |
6 kV conforming to EN/IEC 60947-2
|
|
contact position indicator |
Yes
|
|
control type |
Toggle
|
|
local signalling |
Trip indicator
|
|
mounting mode |
Clip-on
|
|
mounting support |
Rail
|
|
9 mm pitches |
4
|
|
height |
85 mm
|
|
width |
36 mm
|
|
depth |
78.5 mm
|
|
net weight |
0.25 kg
|
|
colour |
White
|
|
mechanical durability |
20000 cycles
|
|
electrical durability |
10000 cycles
|
|
provision for padlocking |
Padlockable
|
|
connections – terminals |
Single terminal (top or bottom) 1…35 mm² rigid
Single terminal (top or bottom) 1…25 mm² flexible |
|
wire stripping length |
14 mm for top or bottom connection
|
|
tightening torque |
3.5 N.m top or bottom
|
|
earth-leakage protection |
Separate block
|
standards |
EN/IEC 60898-1
EN/IEC 60947-2 |
|
---|---|---|
IP degree of protection |
IP20 conforming to IEC 60529
|
|
pollution degree |
3 conforming to EN/IEC 60947-2
|
|
tropicalisation |
2 conforming to IEC 60068-1
|
|
relative humidity |
95 % at 55 °C
|
|
ambient air temperature for operation |
-35…70 °C
|
|
ambient air temperature for storage |
-40…85 °C
|
Distribution transformers from Schneider Electric are available in ratings from 100kVA upto 4000kVA at voltages upto 36kV. They can be supplied in many types and styles, with standard industry fittings or bespoke design to the customers specific requirements. Choices available include:
aesthetic name |
Screwless flat plate
|
|
---|---|---|
product or component type |
Switched socket
|
|
rated current |
13 A at 230 V AC 50 Hz
|
|
fixing mode |
By screws M3.5 x 30 mm
|
|
colour tint |
Black nickel
|
device presentation |
Complete product
|
|
---|---|---|
outlet poles configuration |
1P
|
|
outlet standard description |
3 pins
|
|
outlet standard |
British
|
|
actuator |
Rocker
|
|
number of gangs |
2 gangs
|
|
earth circuit |
Standard earth
|
|
pilot light |
Without neon indicator
|
|
device mounting |
Wall mounted
|
|
connections – terminals |
Screw terminal
|
|
material |
Steel
|
|
quantity per set |
Set of 1
|
|
height |
88 mm
|
|
width |
148 mm
|
|
depth |
30 mm
|
Product Description
Manufactured to BS 6004:2012 Table 3
Annealed Stranded Copper Conductor / PVC Insulated / PVC Sheathed. 300/500V
Designed for use in light industrial and domestic wiring. These cables are particularly suited for installation as meter tails and are intended for fixed installation in dry or damp premises.
These cables can be installed in conduit, in cable trunking and in cable ducting. Or where there is deemed little risk of mechanical damage these cables can be clipped direct, on cable tray, embedded or in free air. These cables are not intended to be laid underground.
Product Details
Harmonisation Code | Nominal Cross Sectional Area of Conductor (mm2) | Nominal Stranding of Conductor (mm) | Nominal Radial Thickness of insulation (mm) | Nominal Radial Thickness of sheath (mm) | Overall Diameter Lower Limit (mm) | Overall Diameter Upper Limit (mm) | Approximate Weight(kg/km) | |
National Type | 1.0 | 1 / 1.13 | 0.6 | 0.8 | 3.8 | 4.5 | 26 | |
National Type | 1.5 | 1 / 1.38 | 0.7 | 0.8 | 4.2 | 4.9 | 35 | |
National Type | 2.5 | 1 / 1.78 | 0.8 | 0.8 | 4.8 | 5.8 | 55 | |
National Type | 4.0 | 7 / 0.85 | 0.8 | 0.9 | 5.4 | 6.8 | 75 | |
National Type | 6.0 | 7 / 1.04 | 0.8 | 0.9 | 6.0 | 7.4 | 95 | |
National Type | 10.0 | 7 / 1.35 | 1.0 | 0.9 | 7.2 | 8.8 | 155 | |
National Type | 16.0 | 7 / 1.70 | 1.0 | 1.0 | 8.4 | 10.5 | 225 | |
National Type | 25.0 | 7 / 2.14 | 1.2 | 1.1 | 10.0 | 12.5 | 340 | |
National Type | 35.0 | 7 / 2.52 | 1.2 | 1.1 | 11.0 | 13.5 | 445 |
There are no reviews yet.