LIGHT SWITCHES & ELECTRICAL SOCKETS
15A 250V 1 Gang Switched Socket with Neon KB15_15N
range |
Vivace
|
|
---|---|---|
product or component type |
Socket-outlet with switch
|
|
device short name |
KB15
|
|
device presentation |
Complete mechanism
|
pilot light |
Red neon indicator
|
|
---|---|---|
outlet poles configuration |
2P + E
|
|
number of gangs |
1 gang
|
|
Colour tint |
White
|
|
material |
Polycarbonate: grid plate
Polycarbonate: surround Polycarbonate: base |
|
projecting depth |
8 mm
|
|
device mounting |
Flush
|
|
mounting support |
Wall mounted
|
|
fixing mode |
By screw M3.5
|
|
fixing center |
60.3 mm
|
|
embedding depth |
35 mm
|
|
rated current |
15 A at 250 V AC, resistive
|
|
network frequency |
50 Hz
|
|
contacts material |
Brass and phosphor bronze
|
|
connections – terminals |
Pillar terminal
|
|
terminal identifier |
Earth
L N |
|
tightening torque |
0.4 N.m
|
|
clamping connection capacity |
2.5 mm²
|
|
width |
87 mm
|
|
height |
87 mm
|
₦3,500.00
Compare-
LIGHT SWITCHES & ELECTRICAL SOCKETS, SCHNEIDER SECTIONS
Ultimate Screwless flat plate – TV/FM socket – coaxial – 1 gang – stainles steel GU7410WSS
LIGHT SWITCHES & ELECTRICAL SOCKETS, SCHNEIDER SECTIONSUltimate Screwless flat plate – TV/FM socket – coaxial – 1 gang – stainles steel GU7410WSS
Main range of product Ultimateaesthetic name Screwless flat plateproduct or component type TV/FM socketTV socket type TV/FMquantity per set Set of 1Complementary radio connector Malenumber of gangs 1 gangfixing mode By screwsmaterial Steelheight 88 mmwidth 88 mmdepth 24 mmSKU: n/a -
Schneider Circuit Breakers, SCHNEIDER SECTIONS
IC60H – miniature circuit breaker – 2P – 32A – C curve A9F84232
Schneider Circuit Breakers, SCHNEIDER SECTIONSIC60H – miniature circuit breaker – 2P – 32A – C curve A9F84232
Main device application Distributionrange Acti 9product name Acti 9 iC60product or component type Miniature circuit-breakerdevice short name IC60Hpoles description 2Pnumber of protected poles 2[In] rated current 32 Anetwork type DC
ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
42 kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2
10 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2
15 kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2
30 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
15 kA Icu at <= 125 V DC conforming to EN/IEC 60947-2
42 kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2utilisation category Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2suitability for isolation Yes conforming to EN 60898-1
Yes conforming to EN 60947-2
Yes conforming to IEC 60898-1
Yes conforming to IEC 60947-2standards EN 60898-1
IEC 60898-1
EN 60947-2
IEC 60947-2Complementary network frequency 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 15 kA 50 % conforming to EN 60947-2 – 220…240 V AC 50/60 Hz
7.5 kA 50 % conforming to EN 60947-2 – 380…415 V AC 50/60 Hz
5 kA 50 % conforming to EN 60947-2 – 440 V AC 50/60 Hz
15 kA 50 % conforming to IEC 60947-2 – 220…240 V AC 50/60 Hz
7.5 kA 50 % conforming to IEC 60947-2 – 380…415 V AC 50/60 Hz
5 kA 50 % conforming to IEC 60947-2 – 440 V AC 50/60 Hz
7500 A 75 % conforming to EN 60898-1 – 400 V AC 50/60 Hz
7500 A 75 % conforming to IEC 60898-1 – 400 V AC 50/60 Hz
21 kA 50 % conforming to IEC 60947-2 – 12…133 V AC 50/60 Hz
21 kA 50 % conforming to EN 60947-2 – 12…133 V AC 50/60 Hz
15 kA 100 % conforming to IEC 60947-2 – 72…125 V DC
15 kA 100 % conforming to EN 60947-2 – 72…125 V DClimitation class 3 conforming to EN 60898-1
3 conforming to IEC 60898-1[Ui] rated insulation voltage 500 V AC 50/60 Hz conforming to EN 60947-2
500 V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6 kV conforming to EN 60947-2
6 kV conforming to IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Fixedmounting support DIN railcomb busbar and distribution block compatibility Top or bottom: YES9 mm pitches 4height 85 mmwidth 36 mmdepth 78.5 mmnet weight 0.25 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesconnections – terminals Single terminal (top or bottom) 1…35 mm² rigid
Single terminal (top or bottom) 1…25 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 3.5 N.m top or bottomearth-leakage protection Separate blockSKU: n/a -
Schneider Circuit Breakers, SCHNEIDER SECTIONS
Easy9 Residual Current Circuit Breaker – 4P – 63 A – 30 mA – AC type – 400 V EZ9R34463
Schneider Circuit Breakers, SCHNEIDER SECTIONSEasy9 Residual Current Circuit Breaker – 4P – 63 A – 30 mA – AC type – 400 V EZ9R34463
Main range of product Easy9product or component type Residual current circuit breaker (RCCB)device short name Easy9 RCCBPoles 4Pneutral position Left[In] rated current 63 Anetwork type ACearth-leakage sensitivity 30 mAearth-leakage protection time delay Instantaneousearth-leakage protection class Type ACrated breaking and making capacity 630 Arated conditional short-circuit current Easy9 MCB: 4500 A 63 AComplementary device location in system Outgoernetwork frequency 50 Hz[Ue] rated operational voltage 400 V AC 50 Hzresidual current tripping technology Voltage independent[Ui] rated insulation voltage 440 V AC[Uimp] rated impulse withstand voltage 4 kVsurge current 250 Acontact position indicator Yescontrol type Togglemounting mode Clip-onmounting support DIN railcomb busbar and distribution block compatibility Top: YES9 mm pitches 8height 82 mmwidth 72 mmdepth 72 mmcolour Grey (RAL 7035)mechanical durability 5000 cycleselectrical durability AC: 2000 cycles 400 V AC 50 Hzconnections – terminals Tunnel type terminal (top or bottom) 1…35 mm² rigid
Tunnel type terminal (top or bottom) 1…25 mm² flexibletightening torque 3.5 N.m top or bottommarket segment Residential
Small commercialSKU: n/a -
Electro, SOCKETS & SWITCHES, SURGE PROTECTOR
Himel Single Phase Voltage Stabilizers 10kVA HTNDS10HB230 British type plug, 230 V output
Electro, SOCKETS & SWITCHES, SURGE PROTECTORHimel Single Phase Voltage Stabilizers 10kVA HTNDS10HB230 British type plug, 230 V output
Voltage stabilizer, HTND2, 10 kVA, British type plug, 230 V output
Main
Range of product -HTND2Product or component type -Voltage stabilizerTechnology type -Servo motorRated power in VA -10 kVAOutlet standard -BritishProvided equipment -User manualOutput voltage -230 VComplementary
Response time -1 sEfficiency -92 %Input voltage limits -140…250 VProtection type -Overvoltage
Short-circuit -UndervoltageNetwork frequency -50/60 HzMounting mode -Desktop installationEnvironment
Ambient air temperature for operation -5…40 °CRelative humidity -0…90 %Humidity storage -0…90 %Operating altitude -0…2000 mStorage altitude -0…2000 mStandards -EN 61000-6-2
EN 61000-6-4 -EN 61558-1Product certifications – CEPacking Units
Unit Type of Package 1 -PCENumber of Units in Package 1 -1SKU: n/a