LIGHT SWITCHES & ELECTRICAL SOCKETS
16AX 250V 1 Gang 1 Way Switch KB31_1
range |
Vivace
|
|
---|---|---|
product or component type |
Switch
|
|
device short name |
KB31
|
|
device presentation |
Complete mechanism
|
switch function |
1-way
|
|
---|---|---|
actuator |
Rocker
|
|
number of gangs |
1 gang
|
|
colour tint |
White
|
|
material |
Polycarbonate: grid plate
Polycarbonate: surround Polycarbonate: base |
|
projecting depth |
8 mm
|
|
device mounting |
Flush
|
|
mounting support |
Wall mounted
|
|
fixing mode |
By screw M3.5
|
|
fixing center |
60.3 mm
|
|
embedding depth |
35 mm
|
|
rated current |
16 AX at 250 V AC, inductive
16 AX at 250 V AC, fluorescent |
|
[Ue] rated operational voltage |
250 V AC
|
|
network frequency |
50 Hz
|
|
contacts material |
Brass and phosphor bronze
|
|
connections – terminals |
pillar terminal
|
|
terminal identifier |
L1
COM L2 |
|
tightening torque |
0.4 N.m
|
|
clamping connection capacity |
2.5 mm²
|
|
width |
87 mm
|
|
height |
87 mm
|
₦1,000.00
Compare-
Low Voltage Products and Systems, SCHNEIDER SECTIONS
EZC100N4040 – Circuit breaker Easypact EZC100N – TMD – 40 A – 4 poles 3d
Low Voltage Products and Systems, SCHNEIDER SECTIONSEZC100N4040 – Circuit breaker Easypact EZC100N – TMD – 40 A – 4 poles 3d
Main range of product EasyPactproduct or component type Circuit breakerdevice short name Easypact EZC100Ncircuit breaker name Easypact EZC100Ndevice application Distributionpoles description 4Pprotected poles description 3tnetwork type AC
DCnetwork frequency 50/60 Hz[In] rated current 100 A at 40 °C[Ui] rated insulation voltage 690 V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947-2[Ue] rated operational voltage 550 V AC 50/60 Hz conforming to IEC 60947-2
250 V DC conforming to IEC 60947-2breaking capacity code Nbreaking capacity 10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
25 kA Icu at 110…130 V AC 50/60 Hz conforming to IEC 60947-2
25 kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
5 kA Icu at 125 V DC 1P conforming to IEC 60947-2
5 kA Icu at 250 V DC 2P conforming to IEC 60947-2
5 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2
15 kA Icu at 415 V AC 50/60 Hz conforming to IEC 60947-2
18 kA Icu at 380…400 V AC 50/60 Hz conforming to IEC 60947-2[Ics] rated service breaking capacity 5 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
2.5 kA at 125 V DC conforming to IEC 60947-2
2.5 kA at 250 V DC conforming to IEC 60947-2
2.5 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2
12.5 kA at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
12.5 kA at 110…130 V AC 50/60 Hz conforming to IEC 60947-2
9 kA at 380…400 V AC 50/60 Hz conforming to IEC 60947-2
7.5 kA at 415 V AC 50/60 Hz conforming to IEC 60947-2suitability for isolation Yes conforming to IEC 60947-2utilisation category Category Atrip unit name TM-Dtrip unit technology Thermal-magnetictrip unit rating 40 A at 50 °Cprotection type Overload protection
Short-circuit protectionpollution degree 3 conforming to IEC 60947Complementary control type Togglemounting mode Fixedmounting support Backplateupside connection Frontdownside connection Frontmechanical durability 8500 cycleselectrical durability Category A: 1500 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2connection pitch 25 mmlocal signalling Positive contact indicationneutral protection setting Without protectionearth-leakage protection Withoutheight 130 mmwidth 100 mmdepth 60 mmSKU: n/a -
LIGHT SWITCHES & ELECTRICAL SOCKETS
Lisse – unswitched socket – 2 gangs – 13 A 230 V – white GGBL3060
LIGHT SWITCHES & ELECTRICAL SOCKETSLisse – unswitched socket – 2 gangs – 13 A 230 V – white GGBL3060
Main range Lisseaesthetic name White mouldedproduct or component type Unswitched socketdevice presentation Complete productoutlet standard Britishcolour tint Matt whitequantity per set Set of 5type of packing CartonComplementary switch function 1-polerated current 13 A at 250 V AC 50 Hzactuator Rockernumber of gangs 2 gangsfixing mode By screwsconnections – terminals Screw terminalsmaterial Urea (carbamide)type of installation Indoordepth 22 mmwidth 148 mmheight 87 mmnet weight 0.123 kgSKU: n/a -
LIGHT SWITCHES & ELECTRICAL SOCKETS
2 Gang TV Coaxial Outlet KB32TV
Main range of product Vivacerange Vivacedevice short name KB32product or component type TV socketdevice presentation Complete mechanismComplementary number of gangs 1 gangnumber of outputs 2Colour tint Whitematerial Polycarbonate: surround
Polycarbonate: grid plate
Polycarbonate: baseprojecting depth 8 mmdevice mounting Flushmounting support Wall mountedfixing mode By screw M3.5fixing center 60.3 mmembedding depth 35 mmtightening torque 0.4 N.mwidth 86 mmheight 86 mmSKU: n/a -
LIGHT SWITCHES & ELECTRICAL SOCKETS
Lisse – Plate Switch – 2 gang 2 way – 10AX Satin Brass with Black interior GGBL1022BSB
LIGHT SWITCHES & ELECTRICAL SOCKETSLisse – Plate Switch – 2 gang 2 way – 10AX Satin Brass with Black interior GGBL1022BSB
Main range Lisseaesthetic name Screwless decoproduct or component type Plate switchdevice presentation Complete productcolour tint Interior: black
Cover plate: satin brassquantity per set Set of 10Complementary switch function 2-waycontrol type Rockernumber of gangs 2 gangsdevice mounting Wall mountedrated current 10 AX at 230 V ACfixing mode Concealed screwsconnections – terminals Screw terminalsmaterial Stainless steelsurface finish Brushed finishtype of packing Boxheight 87 mmwidth 87 mmdepth 25 mmnet weight 0.122 kgSKU: n/a -
Schneider Circuit Breakers, SCHNEIDER SECTIONS
Acti9 iC60N 2P 1A C Miniature Circuit breaker A9F44201
Schneider Circuit Breakers, SCHNEIDER SECTIONSActi9 iC60N 2P 1A C Miniature Circuit breaker A9F44201
Main range Acti 9product name Disbo iC60product or component type Miniature circuit-breakerdevice short name IC60Npoles description 2Pnumber of protected poles 2[In] rated current 1 Anetwork type ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 50 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
50 kA Icu at 12…133 V AC 50/60 Hz conforming to EN/IEC 60947-2
50 kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2
25 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2
6 kA Icu at 100…133 V DC conforming to EN/IEC 60947-2
6000 A Icn at 415 V AC 50/60 Hz conforming to EN/IEC 60898-1utilisation category Category A conforming to EN/IEC 60947-2Complementary network frequency 50/60 Hz[Ue] rated operational voltage 440 V AC 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 50 kA 100 % conforming to EN/IEC 60947-2 – 220…240 V AC 50/60 Hz
50 kA 100 % conforming to EN/IEC 60947-2 – 12…133 V AC 50/60 Hz
50 kA 100 % conforming to EN/IEC 60947-2 – 380…415 V AC 50/60 Hz
25 kA 100 % conforming to EN/IEC 60947-2 – 440 V AC 50/60 Hz
6000 A 100 % conforming to EN/IEC 60898-1 – 415 V AC 50/60 Hz
6 kA 100 % conforming to EN/IEC 60947-2 – 100…133 V DClimitation class 3 conforming to EN/IEC 60947-2[Ui] rated insulation voltage 500 V AC 50/60 Hz[Uimp] rated impulse withstand voltage 6 kV conforming to EN/IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Clip-onmounting support Rail9 mm pitches 4height 85 mmwidth 36 mmdepth 78.5 mmnet weight 0.25 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesprovision for padlocking Padlockableconnections – terminals Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 2 N.m top or bottomearth-leakage protection Separate blockEnvironment standards EN/IEC 60947-2
EN/IEC 60898-1IP degree of protection IP20 conforming to IEC 60529pollution degree 3 conforming to EN/IEC 60947-2tropicalisation 2 conforming to IEC 60068-1relative humidity 95 % at 55 °Cambient air temperature for operation -35…70 °Cambient air temperature for storage -40…85 °CSKU: n/a