Acti9 iC60N 2P 25A C Miniature Circuit breaker A9F44225
range |
Acti 9
|
|
---|---|---|
product name |
Disbo iC60
|
|
product or component type |
Miniature circuit-breaker
|
|
device short name |
IC60N
|
|
poles description |
2P
|
|
number of protected poles |
2
|
|
[In] rated current |
25 A
|
|
network type |
AC/DC
|
|
trip unit technology |
Thermal-magnetic
|
|
curve code |
C
|
|
breaking capacity |
6 kA Icu at 100…133 V DC conforming to EN/IEC 60947-2
6000 A Icn at 415 V AC 50/60 Hz conforming to EN/IEC 60898-1 36 kA Icu at 12…133 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
|
utilisation category |
Category A conforming to EN/IEC 60947-2
|
network frequency |
50/60 Hz
|
|
---|---|---|
[Ue] rated operational voltage |
440 V AC 50/60 Hz
|
|
magnetic tripping limit |
8 x In +/- 20 %
|
|
[Ics] rated service breaking capacity |
27 kA 75 % conforming to EN/IEC 60947-2 – 12…133 V AC 50/60 Hz
15 kA 75 % conforming to EN/IEC 60947-2 – 220…240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 – 380…415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 – 440 V AC 50/60 Hz 6000 A 100 % conforming to EN/IEC 60898-1 – 415 V AC 50/60 Hz 6 kA 100 % conforming to EN/IEC 60947-2 – 100…133 V DC |
|
limitation class |
3 conforming to EN/IEC 60947-2
|
|
[Ui] rated insulation voltage |
500 V AC 50/60 Hz
|
|
[Uimp] rated impulse withstand voltage |
6 kV conforming to EN/IEC 60947-2
|
|
contact position indicator |
Yes
|
|
control type |
Toggle
|
|
local signalling |
Trip indicator
|
|
mounting mode |
Clip-on
|
|
mounting support |
Rail
|
|
9 mm pitches |
4
|
|
height |
85 mm
|
|
width |
36 mm
|
|
depth |
78.5 mm
|
|
net weight |
0.25 kg
|
|
colour |
White
|
|
mechanical durability |
20000 cycles
|
|
electrical durability |
10000 cycles
|
|
provision for padlocking |
Padlockable
|
|
connections – terminals |
Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexible |
|
wire stripping length |
14 mm for top or bottom connection
|
|
tightening torque |
2 N.m top or bottom
|
|
earth-leakage protection |
Separate block
|
₦5,999.00
Compare-
CABLE AND CABLE MANAGEMENT, Electro, SINGLE CORE WIRE
Doncaster Cables 16mm Single Core – Red
Product Description
Manufactured to BS 6004:2012 Table 3
Annealed Stranded Copper Conductor / PVC Insulated / PVC Sheathed. 300/500V
Designed for use in light industrial and domestic wiring. These cables are particularly suited for installation as meter tails and are intended for fixed installation in dry or damp premises.
These cables can be installed in conduit, in cable trunking and in cable ducting. Or where there is deemed little risk of mechanical damage these cables can be clipped direct, on cable tray, embedded or in free air. These cables are not intended to be laid underground.
Product Details
Harmonisation Code Nominal Cross Sectional Area of Conductor (mm2) Nominal Stranding of Conductor (mm) Nominal Radial Thickness of insulation (mm) Nominal Radial Thickness of sheath (mm) Overall Diameter Lower Limit (mm) Overall Diameter Upper Limit (mm) Approximate Weight(kg/km) National Type 1.0 1 / 1.13 0.6 0.8 3.8 4.5 26 National Type 1.5 1 / 1.38 0.7 0.8 4.2 4.9 35 National Type 2.5 1 / 1.78 0.8 0.8 4.8 5.8 55 National Type 4.0 7 / 0.85 0.8 0.9 5.4 6.8 75 National Type 6.0 7 / 1.04 0.8 0.9 6.0 7.4 95 National Type 10.0 7 / 1.35 1.0 0.9 7.2 8.8 155 National Type 16.0 7 / 1.70 1.0 1.0 8.4 10.5 225 National Type 25.0 7 / 2.14 1.2 1.1 10.0 12.5 340 National Type 35.0 7 / 2.52 1.2 1.1 11.0 13.5 445 SKU: n/a -
ELECTRICAL INDUSTRIAL, TRANSFORMER
BETA 500KVA/11/0.415V COPPER/COPPER WINDING TRANSFORMER
Produced within a power range between 10 – 100.000 kVA , up to 170 kV high voltage level, three phase or single phase, oil immersed, ONAN, ONAF, OFWF, with Off-Load or On-Load Tap Changer, used both external and internal.
Dimensions of transformer conservator are determined and designed after several heat calculations of the oil stored in expansion tank and oil level changes by heat.
Being open to atmosphere, oil pressure changes continuously in Conservator Type Transformers due to thermal effects and exchange of air is dehumidified via air breather silicagel.SKU: n/a -
Electro, SOCKETS & SWITCHES, SWITCHES
FBN74 – 45AMP WATER HEATER SWITCH
BG Electrical are confident in the quality of our workmanship and materials, the guarantee stated applies from the date of delivery.
45A Rated
Easy to install supplied with fixing screws and installation instructions
Ideal for cookers and ovens
Double Pole switching for the peace of mind of a safer installation
Twin earth fitted as standard for high integrity circuits
Captive screws prevent screw loss
Flush power indicator
Screwless front plate clips on and off easily and has a sleek flat profile, with no visible plastic around the switch.
Moisture control gasket prevents tarnishing from new plaster
Minimum mounting box depth 47mm
SKU: n/a -
Electro, INDOOR LIGHTS, LED LIGHTS, LIGHTING
Vtac 2ft LED Tube SAMSUNG Chip
Product benefits
- Cost effective, safe retrofit for T8 Tubes
- Perfectly matches with the traditional daylight tube fixture
- Easy Installation
- No Lead or Mercury content hence Environment friendly
- No Ultraviolet or Infrared rays
- No flickering
- Long Lifespan, Low maintenance and energy saving
- Available in 60 cm, 120 cm, 150 cm
- Ballast or Starter NOT REQUIRED – DIRECT AC POWER
Applications
- Domestic and Commercial Lighting
- Offices
- Supermarkets
- Shops, Hotels & similar environment
SKU: n/a -
Schneider Circuit Breakers, SCHNEIDER SECTIONS
Easy9 switch disconnector – 4P – 100 A – 400 V EZ9S16491
Schneider Circuit Breakers, SCHNEIDER SECTIONSEasy9 switch disconnector – 4P – 100 A – 400 V EZ9S16491
Main range Easy9product or component type Switchdevice short name Easy9 switchswitch application DistributionPoles 4Putilisation category AC-22Asuitability for isolation YesComplementary [Ie] rated operational current 100 A at 400 V 50/60 Hz[Ue] rated operational voltage 400 V AC 50/60 Hz[Icm] rated short-circuit making capacity 1.5 kA[Icw] rated short-time withstand current 1.2 kA during 1 s[Ui] rated insulation voltage 500 V AC 50/60 Hz[Uimp] rated impulse withstand voltage 4 kVcontrol type Togglelocal signalling ON/OFF indicationcontact position indicator Yesmounting mode Clip-onmounting support DIN rail9 mm pitches 8height 81 mmwidth 72 mmdepth 66.5 mmcolour Greymechanical durability 8500 cycleselectrical durability 1500 cyclesconnections – terminals Tunnel type terminal (top or bottom) 1…50 mm² rigid
Tunnel type terminal (top or bottom) 1…35 mm² flexibletightening torque 3.5 N.mSKU: n/a
There are no reviews yet.