Schneider Circuit Breakers, SCHNEIDER SECTIONS
Acti9 iC60N 4P 40A C Miniature Circuit breaker A9F44440
range |
Acti 9
|
|
---|---|---|
product name |
Disbo iC60
|
|
product or component type |
Miniature circuit-breaker
|
|
device short name |
IC60N
|
|
poles description |
4P
|
|
number of protected poles |
4
|
|
[In] rated current |
40 A
|
|
network type |
AC/DC
|
|
trip unit technology |
Thermal-magnetic
|
|
curve code |
C
|
|
breaking capacity |
6 kA Icu at 100…133 V DC conforming to EN/IEC 60947-2
6000 A Icn at 415 V AC 50/60 Hz conforming to EN/IEC 60898-1 36 kA Icu at 12…133 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
|
utilisation category |
Category A conforming to EN/IEC 60947-2
|
network frequency |
50/60 Hz
|
|
---|---|---|
[Ue] rated operational voltage |
440 V AC 50/60 Hz
|
|
magnetic tripping limit |
8 x In +/- 20 %
|
|
[Ics] rated service breaking capacity |
27 kA 75 % conforming to EN/IEC 60947-2 – 12…133 V AC 50/60 Hz
15 kA 75 % conforming to EN/IEC 60947-2 – 220…240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 – 380…415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 – 440 V AC 50/60 Hz 6000 A 100 % conforming to EN/IEC 60898-1 – 415 V AC 50/60 Hz 6 kA 100 % conforming to EN/IEC 60947-2 – 100…133 V DC |
|
limitation class |
3 conforming to EN/IEC 60947-2
|
|
[Ui] rated insulation voltage |
500 V AC 50/60 Hz
|
|
[Uimp] rated impulse withstand voltage |
6 kV conforming to EN/IEC 60947-2
|
|
contact position indicator |
Yes
|
|
control type |
Toggle
|
|
local signalling |
Trip indicator
|
|
mounting mode |
Clip-on
|
|
mounting support |
Rail
|
|
9 mm pitches |
8
|
|
height |
85 mm
|
|
width |
72 mm
|
|
depth |
78.5 mm
|
|
net weight |
0.5 kg
|
|
colour |
White
|
|
mechanical durability |
20000 cycles
|
|
electrical durability |
10000 cycles
|
|
provision for padlocking |
Padlockable
|
|
connections – terminals |
Single terminal (top or bottom) 1…35 mm² rigid
Single terminal (top or bottom) 1…25 mm² flexible |
|
wire stripping length |
14 mm for top or bottom connection
|
|
tightening torque |
3.5 N.m top or bottom
|
|
earth-leakage protection |
Separate block
|
₦15,999.00
Compare-
Electro, Schneider, SCHNEIDER SECTIONS
Easy9 distribution board – 3P – 125A – 36 ways- straight with fixlink EZ9ET36L
Electro, Schneider, SCHNEIDER SECTIONSEasy9 distribution board – 3P – 125A – 36 ways- straight with fixlink EZ9ET36L
Main range Easy9product name VTPNproduct or component type Distribution boardprovided equipment 1 x washer
4 x screws
Removable front cover
Copper link
Insulated fishbone
Adjustable pan assembly
Provision for incomer
Blanking plateComplementary enclosure mounting Flush
Surfacenetwork number of phases Three phasenumber of ways 36 waystype of rail DINcable entry 11 knock-outsType of door Plain door[In] rated current 125 Aenclosure material Powder coated steelwidth 466 mm outside:height 675 mm outside:depth 110 mm outside:colour Grey (RAL 7035)Environment standards IEC 61439-1
IEC 61439-3product certifications ASTAIP degree of protection IP40 conforming to IEC 60529 (closed door)IK degree of protection IK08 conforming to IEC 62262ambient air temperature for operation -5…50 °CPacking Units Package 1 Weight 17000.000 kgPackage 1 Height 110.000 mmPackage 1 width 466.000 mmPackage 1 Length 740.000 mmSKU: n/a -
Schneider Industrial Sockets, SCHNEIDER SECTIONS
IMT33157 Thorsman – Cable reel 50m HO5VVF3G1.25 IP20 BS 230V
Schneider Industrial Sockets, SCHNEIDER SECTIONSIMT33157 Thorsman – Cable reel 50m HO5VVF3G1.25 IP20 BS 230V
IMT33157 Thorsman – Cable reel 50m HO5VVF3G1.25 IP20 BS 230V
range PROchantierproduct or component type Cable reeldevice application Power supply[In] rated current 13 AComplementary cable length 50 mcable cross section 1.25 mm²type of cable H05VV-F3G1.25quantity per set Set of 1height 295 mmwidth 376 mmdepth 201 mmnet weight 7.62 kgSKU: n/a -
ELECTRICAL FITTINGS, Electro, FLUORESCENT FITTINGS, HOME&OFFICE LIGHTING, INDOOR LIGHTS, INTERIOR LIGHTING, LIGHTING
2×10W Mosquito Fly Trap Killer,KILL PEST,White
ELECTRICAL FITTINGS, Electro, FLUORESCENT FITTINGS, HOME&OFFICE LIGHTING, INDOOR LIGHTS, INTERIOR LIGHTING, LIGHTING2×10W Mosquito Fly Trap Killer,KILL PEST,White
Product Description:-
Voltage: – 220v~50/60Hz
Power: – 2*20w
Size: – 49*8*28cm
High efficiency
Destroys insects
Eco friendly
Energy saver
Caution: customer must read the instruction exactly before using
SKU: n/a -
Electro, Schneider "Consort Dado" Trunking, SCHNEIDER SECTIONS
Mita – Cableline 50 – end cap – 180W x 52 mm DPE3W
Electro, Schneider "Consort Dado" Trunking, SCHNEIDER SECTIONSMita – Cableline 50 – end cap – 180W x 52 mm DPE3W
Main product name Cableline 50product or component type End capcolour tint Whitequantity per set Set of 2Complementary trunking dimension 180W x 52 mmmaterial with surface finish UPVC (unplasticized polyvinyl chloride)Environment ambient air temperature for operation -5…60 °CPacking Units Unit Type of Package 1 PCENumber of Units in Package 1 1Package 1 Weight 60 gPackage 1 Height 2.5 cmPackage 1 width 5.5 cmPackage 1 Length 18.5 cmSKU: n/a -
Schneider Circuit Breakers, SCHNEIDER SECTIONS
Acti9 iC60N 3P 20A C Miniature Circuit breaker A9F44320
Schneider Circuit Breakers, SCHNEIDER SECTIONSActi9 iC60N 3P 20A C Miniature Circuit breaker A9F44320
Main range Acti 9product name Disbo iC60product or component type Miniature circuit-breakerdevice short name IC60Npoles description 3Pnumber of protected poles 3[In] rated current 20 Anetwork type ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 6000 A Icn at 415 V AC 50/60 Hz conforming to EN/IEC 60898-1
36 kA Icu at 12…133 V AC 50/60 Hz conforming to EN/IEC 60947-2
20 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
10 kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2
6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2
15 kA Icu at 100…133 V DC conforming to EN/IEC 60947-2utilisation category Category A conforming to EN/IEC 60947-2Complementary network frequency 50/60 Hz[Ue] rated operational voltage 440 V AC 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 27 kA 75 % conforming to EN/IEC 60947-2 – 12…133 V AC 50/60 Hz
15 kA 75 % conforming to EN/IEC 60947-2 – 220…240 V AC 50/60 Hz
7.5 kA 75 % conforming to EN/IEC 60947-2 – 380…415 V AC 50/60 Hz
4.5 kA 75 % conforming to EN/IEC 60947-2 – 440 V AC 50/60 Hz
6000 A 100 % conforming to EN/IEC 60898-1 – 415 V AC 50/60 Hz
15 kA 100 % conforming to EN/IEC 60947-2 – 100…133 V DClimitation class 3 conforming to EN/IEC 60947-2[Ui] rated insulation voltage 500 V AC 50/60 Hz[Uimp] rated impulse withstand voltage 6 kV conforming to EN/IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Clip-onmounting support Rail9 mm pitches 6height 85 mmwidth 54 mmdepth 78.5 mmnet weight 0.375 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesprovision for padlocking Padlockableconnections – terminals Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 2 N.m top or bottomearth-leakage protection Separate blockEnvironment standards EN/IEC 60898-1
EN/IEC 60947-2IP degree of protection IP20 conforming to IEC 60529pollution degree 3 conforming to EN/IEC 60947-2tropicalisation 2 conforming to IEC 60068-1relative humidity 95 % at 55 °Cambient air temperature for operation -35…70 °Cambient air temperature for storage -40…85 °CSKU: n/a -
Schneider Circuit Breakers, SCHNEIDER SECTIONS
Acti9 iC60N 1P 40A C Miniature Circuit breaker A9F44140
Schneider Circuit Breakers, SCHNEIDER SECTIONSActi9 iC60N 1P 40A C Miniature Circuit breaker A9F44140
Main range Acti 9product name Disbo iC60product or component type Miniature circuit-breakerdevice short name IC60Npoles description 1Pnumber of protected poles 1[In] rated current 40 Anetwork type ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 15 kA Icu at 12…48 V DC conforming to EN/IEC 60947-2
6 kA Icu at 72 V DC conforming to EN/IEC 60947-2
6000 A Icn at 240 V AC 50/60 Hz conforming to EN/IEC 60898-1
36 kA Icu at 10…60 V AC 50/60 Hz conforming to EN/IEC 60947-2
20 kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2
10 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2utilisation category Category A conforming to EN/IEC 60947-2Complementary network frequency 50/60 Hz[Ue] rated operational voltage 240 V AC 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 27 kA 75 % conforming to EN/IEC 60947-2 – 10…60 V AC 50/60 Hz
15 kA 75 % conforming to EN/IEC 60947-2 – 100…133 V AC 50/60 Hz
7.5 kA 75 % conforming to EN/IEC 60947-2 – 220…240 V AC 50/60 Hz
6000 A 100 % conforming to EN/IEC 60898-1 – 240 V AC 50/60 Hz
15 kA 100 % conforming to EN/IEC 60947-2 – 12…48 V DC
6 kA 100 % conforming to EN/IEC 60947-2 – 72 V DClimitation class 3 conforming to EN/IEC 60947-2[Ui] rated insulation voltage 500 V AC 50/60 Hz[Uimp] rated impulse withstand voltage 6 kV conforming to EN/IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Clip-onmounting support Rail9 mm pitches 2height 85 mmwidth 18 mmdepth 78.5 mmnet weight 0.125 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesprovision for padlocking Padlockableconnections – terminals Single terminal (top or bottom) 1…35 mm² rigid
Single terminal (top or bottom) 1…25 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 3.5 N.m top or bottomearth-leakage protection Separate blockSKU: n/a
There are no reviews yet.