Doncaster Cables 16mm Single Core – Black
Product Description
Manufactured to BS 6004:2012 Table 3
Annealed Stranded Copper Conductor / PVC Insulated / PVC Sheathed. 300/500V
Designed for use in light industrial and domestic wiring. These cables are particularly suited for installation as meter tails and are intended for fixed installation in dry or damp premises.
These cables can be installed in conduit, in cable trunking and in cable ducting. Or where there is deemed little risk of mechanical damage these cables can be clipped direct, on cable tray, embedded or in free air. These cables are not intended to be laid underground.
Product Details
 | Harmonisation Code | Nominal Cross Sectional Area of Conductor (mm2) | Nominal Stranding of Conductor (mm) | Nominal Radial Thickness of insulation (mm) | Nominal Radial Thickness of sheath (mm) | Overall Diameter Lower Limit (mm) | Overall Diameter Upper Limit (mm) | Approximate Weight(kg/km) |
National Type | 1.0 | 1 / 1.13 | 0.6 | 0.8 | 3.8 | 4.5 | 26 | |
National Type | 1.5 | 1 / 1.38 | 0.7 | 0.8 | 4.2 | 4.9 | 35 | |
National Type | 2.5 | 1 / 1.78 | 0.8 | 0.8 | 4.8 | 5.8 | 55 | |
National Type | 4.0 | 7 / 0.85 | 0.8 | 0.9 | 5.4 | 6.8 | 75 | |
National Type | 6.0 | 7 / 1.04 | 0.8 | 0.9 | 6.0 | 7.4 | 95 | |
National Type | 10.0 | 7 / 1.35 | 1.0 | 0.9 | 7.2 | 8.8 | 155 | |
National Type | 16.0 | 7 / 1.70 | 1.0 | 1.0 | 8.4 | 10.5 | 225 | |
National Type | 25.0 | 7 / 2.14 | 1.2 | 1.1 | 10.0 | 12.5 | 340 | |
National Type | 35.0 | 7 / 2.52 | 1.2 | 1.1 | 11.0 | 13.5 | 445 |
₦455,000.00
Compare-
CHINT
CHINT NU6-â…¡ Low-voltage Surge Arrester 40 – 100KA
NU6-â…¡ Low-voltage Surge Arrester
- Certificates: international certificates are under proceeding;
- Number of poles: 1, 2,3, 4;
- Electric ratings: 230/400V, AC50Hz;
- Application: Protect electric system and on-loading electrical apparatus from thunder and instantaneous over-voltage;
- Standard: IEC 61643-1, EN 61643-11
SKU: n/a -
COMPUTING, LAPTOPS
HP 250 G7 NOTEBOOK PC (6BP28EA)
Description
SPECIFICATION
OPERATING SYSTEM FreeDOS 2.0 MEMORY SLOTS 2 SODIMM MEMORY 4 GB DDR4-2133 SDRAM (1 x 4 GB) STANDARD MEMORY NOTE Transfer rates up to 2133 MT/s. MEMORY AND STORAGE 4 GB memory
500 GB HDD storageSTORAGE TYPE HDD INTERNAL STORAGE 500 GB 5400 rpm SATA PROCESSOR SPEED 2.3 GHz PROCESSOR FAMILY 7th Generation Intel® Core™ i3 processor (i3-7020U) PROCESSOR Intel® Core™ i3-7020U with Intel® HD Graphics 620 (2.5 GHz base frequency, up to 3.1 GHz with Intel® Turbo Boost Technology, 3 MB cache, 2 cores) GRAPHIC CARD FOOTNOTE NUMBER  5 GRAPHICS (INTEGRATED) Intel® HD Graphics 620 DISPLAY 39.6 cm (15.6″) diagonal HD SVA eDP anti-glare LED-backlit, 220 cd/m², 67% sRGB (1366 x 768) DISPLAY SIZE (DIAGONAL) 39.6 cm (15.6″) BATTERY LIFE NOTE Battery is internal and not replaceable by customer. Serviceable by warranty. Fast charging 90% in 90 minutes. BATTERY TYPE HP Long Life 3-cell, 41 Wh Li-ion BATTERY WEIGHT 0.18 kg POWER HP Smart 45 W External AC power adapter WEIGHT Starting at 1.78 kg
6AUDIO FEATURES Dual stereo speakers CAMERA HP VGA Camera KEYBOARD Full-size island-style keyboard with numeric keypad EXPANSION SLOTS 1 multi-format digital media reader7 EXPANSION SLOTS NOTE Supports SD, SDHC, SDXC. PORTS 2 USB 3.1 Gen 1
1 USB 2.0
1 HDMI 1.4b
1 RJ-45
1 headphone/microphone combo
1 AC power8NETWORK INTERFACE Integrated 10/100/1000 GbE NIC WIRELESS Realtek 802.11ac (1×1) Wi-Fi® and Bluetooth® 4.2 Combo9 SECURITY MANAGEMENT TPM 2.0
Security lock slot10Â 11WARRANTY 1 year standard parts and labor limited warranty (1-1-0), depending on country (upgrades available). 1 year limited warranty on primary battery. SKU: n/a -
Schneider Circuit Breakers, SCHNEIDER SECTIONS
Miniature circuit-breaker, Acti9 iC60H, 1P, 6 A, C curve, 10000 A (IEC 60898-1), 15 kA (IEC 60947-2) A9F84106
Schneider Circuit Breakers, SCHNEIDER SECTIONSMiniature circuit-breaker, Acti9 iC60H, 1P, 6 A, C curve, 10000 A (IEC 60898-1), 15 kA (IEC 60947-2) A9F84106
Main device application Distributionrange Acti 9product name Acti 9 iC60product or component type Miniature circuit-breakerdevice short name IC60Hpoles description 1Pnumber of protected poles 1[In] rated current 6Â Anetwork type AC
DCtrip unit technology Thermal-magneticcurve code Cbreaking capacity 10000Â A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
15Â kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
42Â kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2
30Â kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2
15Â kA Icu at 60…72 V DC conforming to EN/IEC 60947-2
20Â kA Icu at 12…60 V DC conforming to EN/IEC 60947-2utilisation category Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2suitability for isolation Yes conforming to EN 60898-1
Yes conforming to EN 60947-2
Yes conforming to IEC 60898-1
Yes conforming to IEC 60947-2standards EN 60898-1
IEC 60947-2
IEC 60898-1
EN 60947-2Complementary network frequency 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 21Â kA 50Â % conforming to EN 60947-2 – 12…60 V AC 50/60 Hz
7.5Â kA 50Â % conforming to EN 60947-2 – 220…240 V AC 50/60 Hz
21Â kA 50Â % conforming to IEC 60947-2 – 12…60 V AC 50/60 Hz
7.5Â kA 50Â % conforming to IEC 60947-2 – 220…240 V AC 50/60 Hz
7500Â A 75Â % conforming to EN 60898-1 – 230 V AC 50/60 Hz
7500Â A 75Â % conforming to IEC 60898-1 – 230 V AC 50/60 Hz
15Â kA 50Â % conforming to IEC 60947-2 – 100…133 V AC 50/60 Hz
15Â kA 50Â % conforming to EN 60947-2 – 100…133 V AC 50/60 Hz
15Â kA 100Â % conforming to EN 60947-2 – 72 V DC
15Â kA 100Â % conforming to IEC 60947-2 – 72 V DC
20Â kA 100Â % conforming to EN 60947-2 – 12…60 V DC
20Â kA 100Â % conforming to IEC 60947-2 – 12…60 V DClimitation class 3 conforming to EN 60898-1
3 conforming to IEC 60898-1[Ui] rated insulation voltage 500Â V AC 50/60 Hz conforming to EN 60947-2
500Â V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6Â kV conforming to EN 60947-2
6 kV conforming to IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Fixedmounting support DIN railcomb busbar and distribution block compatibility Top or bottom: YES9 mm pitches 2height 85 mmwidth 18 mmdepth 78.5 mmnet weight 0.215 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesconnections – terminals Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 2 N.m top or bottomearth-leakage protection WithoutSKU: n/a -
CABLE AND CABLE MANAGEMENT, Electro, SINGLE CORE WIRE
Doncaster Cables 6mm Single Core – Black
Product Description
Manufactured to BS 6004:2012 Table 3
Annealed Stranded Copper Conductor / PVC Insulated / PVC Sheathed. 300/500V
Designed for use in light industrial and domestic wiring. These cables are particularly suited for installation as meter tails and are intended for fixed installation in dry or damp premises.
These cables can be installed in conduit, in cable trunking and in cable ducting. Or where there is deemed little risk of mechanical damage these cables can be clipped direct, on cable tray, embedded or in free air. These cables are not intended to be laid underground.
Product Details
 Harmonisation Code Nominal Cross Sectional Area of Conductor (mm2) Nominal Stranding of Conductor (mm) Nominal Radial Thickness of insulation (mm) Nominal Radial Thickness of sheath (mm) Overall Diameter Lower Limit (mm) Overall Diameter Upper Limit (mm) Approximate Weight(kg/km) National Type 1.0 1 / 1.13 0.6 0.8 3.8 4.5 26 National Type 1.5 1 / 1.38 0.7 0.8 4.2 4.9 35 National Type 2.5 1 / 1.78 0.8 0.8 4.8 5.8 55 National Type 4.0 7 / 0.85 0.8 0.9 5.4 6.8 75 National Type 6.0 7 / 1.04 0.8 0.9 6.0 7.4 95 National Type 10.0 7 / 1.35 1.0 0.9 7.2 8.8 155 National Type 16.0 7 / 1.70 1.0 1.0 8.4 10.5 225 National Type 25.0 7 / 2.14 1.2 1.1 10.0 12.5 340 National Type 35.0 7 / 2.52 1.2 1.1 11.0 13.5 445 SKU: n/a -
ACCESSORIES
APC ESSENTIAL SURGE ARREST 5 OUTLETS 230V – PM5-UK
The Essential SurgeArrest series offers a great value for home equipment and business applications such as small office/home computers
The APC will protect your equipment from the threat of bad power
Device Type Surge suppressor – external
Input Voltage AC 230 V/Frequency Required 50/60 HzSKU: APC 5outlet -
Schneider Circuit Breakers, SCHNEIDER SECTIONS
Acti9 iC60N 3P 20A C Miniature Circuit breaker A9F44320
Schneider Circuit Breakers, SCHNEIDER SECTIONSActi9 iC60N 3P 20A C Miniature Circuit breaker A9F44320
Main range Acti 9product name Disbo iC60product or component type Miniature circuit-breakerdevice short name IC60Npoles description 3Pnumber of protected poles 3[In] rated current 20Â Anetwork type ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 6000Â A Icn at 415 V AC 50/60 Hz conforming to EN/IEC 60898-1
36Â kA Icu at 12…133 V AC 50/60 Hz conforming to EN/IEC 60947-2
20Â kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
10Â kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2
6Â kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2
15Â kA Icu at 100…133 V DC conforming to EN/IEC 60947-2utilisation category Category A conforming to EN/IEC 60947-2Complementary network frequency 50/60 Hz[Ue] rated operational voltage 440 V AC 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 27Â kA 75Â % conforming to EN/IEC 60947-2 – 12…133 V AC 50/60 Hz
15Â kA 75Â % conforming to EN/IEC 60947-2 – 220…240 V AC 50/60 Hz
7.5Â kA 75Â % conforming to EN/IEC 60947-2 – 380…415 V AC 50/60 Hz
4.5Â kA 75Â % conforming to EN/IEC 60947-2 – 440 V AC 50/60 Hz
6000Â A 100Â % conforming to EN/IEC 60898-1 – 415 V AC 50/60 Hz
15 kA 100 % conforming to EN/IEC 60947-2 – 100…133 V DClimitation class 3 conforming to EN/IEC 60947-2[Ui] rated insulation voltage 500 V AC 50/60 Hz[Uimp] rated impulse withstand voltage 6 kV conforming to EN/IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Clip-onmounting support Rail9 mm pitches 6height 85 mmwidth 54 mmdepth 78.5 mmnet weight 0.375 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesprovision for padlocking Padlockableconnections – terminals Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 2 N.m top or bottomearth-leakage protection Separate blockEnvironment standards EN/IEC 60898-1
EN/IEC 60947-2IP degree of protection IP20 conforming to IEC 60529pollution degree 3 conforming to EN/IEC 60947-2tropicalisation 2 conforming to IEC 60068-1relative humidity 95 % at 55 °Cambient air temperature for operation -35…70 °Cambient air temperature for storage -40…85 °CSKU: n/a