Electro, Schneider, SCHNEIDER SECTIONS
Easy9 distribution board – 3P – 125A – 36 ways- straight with fixlink EZ9ET36L
range |
Easy9
|
|
---|---|---|
product name |
VTPN
|
|
product or component type |
Distribution board
|
|
provided equipment |
1 x washer
4 x screws Removable front cover Copper link Insulated fishbone Adjustable pan assembly Provision for incomer Blanking plate |
enclosure mounting |
Flush
Surface |
|
---|---|---|
network number of phases |
Three phase
|
|
number of ways |
36 ways
|
|
type of rail |
DIN
|
|
cable entry |
11 knock-outs
|
|
Type of door |
Plain door
|
|
[In] rated current |
125 A
|
|
enclosure material |
Powder coated steel
|
|
width |
466 mm outside:
|
|
height |
675 mm outside:
|
|
depth |
110 mm outside:
|
|
colour |
Grey (RAL 7035)
|
standards |
IEC 61439-1
IEC 61439-3 |
|
---|---|---|
product certifications |
ASTA
|
|
IP degree of protection |
IP40 conforming to IEC 60529 (closed door)
|
|
IK degree of protection |
IK08 conforming to IEC 62262
|
|
ambient air temperature for operation |
-5…50 °C
|
Package 1 Weight |
17000.000 kg
|
|
---|---|---|
Package 1 Height |
110.000 mm
|
|
Package 1 width |
466.000 mm
|
|
Package 1 Length |
740.000 mm
|
₦0.00
Compare-
INDOOR LIGHTS, LED LIGHTS, LIGHTING
2 x 36W LED with Emergency PHILIPS WT008C LED54/CW Philip
Product Type:Voltage:220-240 V
Wattage:60W
Lamp Life (hrs): 30000
Dimmable:NO
Total Luminous Flux (lm): 6000
Colour Rendering Index(Ra):RA80Driver included: Yes
Color Temperature: 6500K
Luminous Flux (LUMEN): 6000K
Luminous efficacy: 100lm/watt
TrustSight
LED Emergency driverThis design-in guide describes the TrustSight LED Emergency kit developed for indoor lighting applications.
We advise you to consult our websites for the latest up-to-date information.
Applications
Typical applications are linear or point source type of luminaires applied in: offices, public buildings, industrial
and retail environments.SKU: n/a -
Schneider Circuit Breakers, SCHNEIDER SECTIONS
IC60H – miniature circuit breaker – 2P – 32A – C curve A9F84232
Schneider Circuit Breakers, SCHNEIDER SECTIONSIC60H – miniature circuit breaker – 2P – 32A – C curve A9F84232
Main device application Distributionrange Acti 9product name Acti 9 iC60product or component type Miniature circuit-breakerdevice short name IC60Hpoles description 2Pnumber of protected poles 2[In] rated current 32 Anetwork type DC
ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
42 kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2
10 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2
15 kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2
30 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
15 kA Icu at <= 125 V DC conforming to EN/IEC 60947-2
42 kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2utilisation category Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2suitability for isolation Yes conforming to EN 60898-1
Yes conforming to EN 60947-2
Yes conforming to IEC 60898-1
Yes conforming to IEC 60947-2standards EN 60898-1
IEC 60898-1
EN 60947-2
IEC 60947-2Complementary network frequency 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 15 kA 50 % conforming to EN 60947-2 – 220…240 V AC 50/60 Hz
7.5 kA 50 % conforming to EN 60947-2 – 380…415 V AC 50/60 Hz
5 kA 50 % conforming to EN 60947-2 – 440 V AC 50/60 Hz
15 kA 50 % conforming to IEC 60947-2 – 220…240 V AC 50/60 Hz
7.5 kA 50 % conforming to IEC 60947-2 – 380…415 V AC 50/60 Hz
5 kA 50 % conforming to IEC 60947-2 – 440 V AC 50/60 Hz
7500 A 75 % conforming to EN 60898-1 – 400 V AC 50/60 Hz
7500 A 75 % conforming to IEC 60898-1 – 400 V AC 50/60 Hz
21 kA 50 % conforming to IEC 60947-2 – 12…133 V AC 50/60 Hz
21 kA 50 % conforming to EN 60947-2 – 12…133 V AC 50/60 Hz
15 kA 100 % conforming to IEC 60947-2 – 72…125 V DC
15 kA 100 % conforming to EN 60947-2 – 72…125 V DClimitation class 3 conforming to EN 60898-1
3 conforming to IEC 60898-1[Ui] rated insulation voltage 500 V AC 50/60 Hz conforming to EN 60947-2
500 V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6 kV conforming to EN 60947-2
6 kV conforming to IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Fixedmounting support DIN railcomb busbar and distribution block compatibility Top or bottom: YES9 mm pitches 4height 85 mmwidth 36 mmdepth 78.5 mmnet weight 0.25 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesconnections – terminals Single terminal (top or bottom) 1…35 mm² rigid
Single terminal (top or bottom) 1…25 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 3.5 N.m top or bottomearth-leakage protection Separate blockSKU: n/a -
Low Voltage Products and Systems, SCHNEIDER SECTIONS
EZC100F3080 – Circuit breaker Easypact EZC100F – TMD – 80 A – 3 poles 3d
Low Voltage Products and Systems, SCHNEIDER SECTIONSEZC100F3080 – Circuit breaker Easypact EZC100F – TMD – 80 A – 3 poles 3d
Main range of product EasyPactproduct or component type Circuit breakerdevice short name Easypact EZC100Fcircuit breaker name Easypact EZC100Fdevice application Distributionpoles description 3Pprotected poles description 3tnetwork type AC
DCnetwork frequency 50/60 Hz[In] rated current 100 A at 40 °C[Ui] rated insulation voltage 690 V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947-2[Ue] rated operational voltage 550 V AC 50/60 Hz conforming to IEC 60947-2
250 V DC conforming to IEC 60947-2breaking capacity code Fbreaking capacity 25 kA Icu at 110…130 V AC 50/60 Hz conforming to IEC 60947-2
25 kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
5 kA Icu at 125 V DC 1P conforming to IEC 60947-2
5 kA Icu at 250 V DC 2P conforming to IEC 60947-2
5 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2
10 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2
10 kA Icu at 400…415 V AC 50/60 Hz conforming to IEC 60947-2
7.5 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2[Ics] rated service breaking capacity 12.5 kA at 110/130 V AC 50/60 Hz conforming to IEC 60947-2
12.5 kA at 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2
2.5 kA at 125 V DC conforming to IEC 60947-2
2.5 kA at 250 V DC conforming to IEC 60947-2
2.5 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2
5 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2
5 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
3.75 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2suitability for isolation Yes conforming to IEC 60947-2utilisation category Category Atrip unit name TM-Dtrip unit technology Thermal-magnetictrip unit rating 80 A at 50 °Cprotection type Short-circuit protection
Overload protectionpollution degree 3 conforming to IEC 60664-1
3 conforming to IEC 947-1Complementary control type Togglemounting mode Fixedmounting support Backplateupside connection Frontdownside connection Frontmechanical durability 8500 cycleselectrical durability Category A: 1500 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2connection pitch 25 mmlocal signalling Positive contact indicationneutral protection setting Without protectionearth-leakage protection Withoutheight 130 mmwidth 75 mmdepth 60 mmSKU: n/a -
Schneider Circuit Breakers, SCHNEIDER SECTIONS
Acti9 iC60N 1P 50A C Miniature Circuit breaker A9F44150
Schneider Circuit Breakers, SCHNEIDER SECTIONSActi9 iC60N 1P 50A C Miniature Circuit breaker A9F44150
Main range Acti 9product name Disbo iC60product or component type Miniature circuit-breakerdevice short name IC60Npoles description 1Pnumber of protected poles 1[In] rated current 50 Anetwork type ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 15 kA Icu at 12…48 V DC conforming to EN/IEC 60947-2
6 kA Icu at 72 V DC conforming to EN/IEC 60947-2
6000 A Icn at 240 V AC 50/60 Hz conforming to EN/IEC 60898-1
36 kA Icu at 10…60 V AC 50/60 Hz conforming to EN/IEC 60947-2
20 kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2
10 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2utilisation category Category A conforming to EN/IEC 60947-2Complementary network frequency 50/60 Hz[Ue] rated operational voltage 240 V AC 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 27 kA 75 % conforming to EN/IEC 60947-2 – 10…60 V AC 50/60 Hz
15 kA 75 % conforming to EN/IEC 60947-2 – 100…133 V AC 50/60 Hz
7.5 kA 75 % conforming to EN/IEC 60947-2 – 220…240 V AC 50/60 Hz
6000 A 100 % conforming to EN/IEC 60898-1 – 240 V AC 50/60 Hz
15 kA 100 % conforming to EN/IEC 60947-2 – 12…48 V DC
6 kA 100 % conforming to EN/IEC 60947-2 – 72 V DClimitation class 3 conforming to EN/IEC 60947-2[Ui] rated insulation voltage 500 V AC 50/60 Hz[Uimp] rated impulse withstand voltage 6 kV conforming to EN/IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Clip-onmounting support Rail9 mm pitches 2height 85 mmwidth 18 mmdepth 78.5 mmnet weight 0.125 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesprovision for padlocking Padlockableconnections – terminals Single terminal (top or bottom) 1…35 mm² rigid
Single terminal (top or bottom) 1…25 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 3.5 N.m top or bottomearth-leakage protection Separate blockSKU: n/a -
-
Electro, SOCKETS, SOCKETS & SWITCHES
BG 13AMP SINGLE SOCKET WITH USB – FBS21U
This 13A single power socket from British General comes with two USB charging ports, allowing you to plug in an electrical device and charge mobile devices simultaneously without having to sacrifice a power socket. The Screwed Flat plate brushed steel finish screwed flat plate sits flush against the wall, making it ideal for modern interiors.SKU: n/a