Easy9 distribution board – 3P – 125A – 36 ways- straight with fixlink EZ9ET36L
range |
Easy9
|
|
---|---|---|
product name |
VTPN
|
|
product or component type |
Distribution board
|
|
provided equipment |
1 x washer
4 x screws Removable front cover Copper link Insulated fishbone Adjustable pan assembly Provision for incomer Blanking plate |
enclosure mounting |
Flush
Surface |
|
---|---|---|
network number of phases |
Three phase
|
|
number of ways |
36 ways
|
|
type of rail |
DIN
|
|
cable entry |
11 knock-outs
|
|
Type of door |
Plain door
|
|
[In] rated current |
125Â A
|
|
enclosure material |
Powder coated steel
|
|
width |
466Â mm outside:
|
|
height |
675Â mm outside:
|
|
depth |
110Â mm outside:
|
|
colour |
Grey (RAL 7035)
|
standards |
IEC 61439-1
IEC 61439-3 |
|
---|---|---|
product certifications |
ASTA
|
|
IP degree of protection |
IP40 conforming to IEC 60529 (closed door)
|
|
IK degree of protection |
IK08 conforming to IEC 62262
|
|
ambient air temperature for operation |
-5…50 °C
|
Package 1 Weight |
17000.000Â kg
|
|
---|---|---|
Package 1 Height |
110.000Â mm
|
|
Package 1 width |
466.000Â mm
|
|
Package 1 Length |
740.000Â mm
|
₦0.00
Compare-
Electro, Low Voltage Products and Systems, SCHNEIDER SECTIONS
EZC250N4250 Circuit breaker Easypact EZC250N – TMD – 250 A – 4 poles 3d
Electro, Low Voltage Products and Systems, SCHNEIDER SECTIONSEZC250N4250 Circuit breaker Easypact EZC250N – TMD – 250 A – 4 poles 3d
Main
Range of product EasyPact
Product or component type Circuit breaker
Device short name Easypact EZC250N
Circuit breaker name Easypact EZC250N
Device application Distribution
Poles description 4P
Protected poles description 3t
Network type AC
DC
Network frequency 50/60 Hz
[In] rated current 250 A at 40 °C
[Ui] rated insulation voltage 690 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947-2
[Ue] rated operational voltage 550 V AC 50/60 Hz conforming to IEC 60947-2
250 V DC conforming to IEC 60947-2
Breaking capacity code N
Breaking capacity 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
20 kA Icu at 125 V DC 1P conforming to IEC 60947-2
20 kA Icu at 250 V DC 2P conforming to IEC 60947-2
8 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2
25 kA Icu at 380…415 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service breaking capacity 10 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
25 kA at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
10 kA at 125 V DC conforming to IEC 60947-2
10 kA at 250 V DC conforming to IEC 60947-2
4 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2
12.5 kA at 380…415 V AC 50/60 Hz conforming to IEC 60947-2
Suitability for isolation Yes conforming to IEC 60947-2
Utilisation category Category ASKU: n/a -
Low Voltage Products and Systems, SCHNEIDER SECTIONS
EZC100N4050 Circuit breaker Easypact EZC100N – TMD – 50 A – 4 poles 3d
Low Voltage Products and Systems, SCHNEIDER SECTIONSEZC100N4050 Circuit breaker Easypact EZC100N – TMD – 50 A – 4 poles 3d
Main range of product EasyPactproduct or component type Circuit breakerdevice short name Easypact EZC100Ncircuit breaker name Easypact EZC100Ndevice application Distributionpoles description 4Pprotected poles description 3tnetwork type DC
ACnetwork frequency 50/60 Hz[In] rated current 100 A at 40 °C[Ui] rated insulation voltage 690 V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947-2[Ue] rated operational voltage 550 V AC 50/60 Hz conforming to IEC 60947-2
250 V DC conforming to IEC 60947-2breaking capacity code Nbreaking capacity 10Â kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
25Â kA Icu at 110…130 V AC 50/60 Hz conforming to IEC 60947-2
25Â kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
5Â kA Icu at 125 V DC 1P conforming to IEC 60947-2
5Â kA Icu at 250 V DC 2P conforming to IEC 60947-2
5Â kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2
15Â kA Icu at 415 V AC 50/60 Hz conforming to IEC 60947-2
18Â kA Icu at 380…400 V AC 50/60 Hz conforming to IEC 60947-2[Ics] rated service breaking capacity 5Â kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
2.5Â kA at 125 V DC conforming to IEC 60947-2
2.5Â kA at 250 V DC conforming to IEC 60947-2
2.5Â kA at 550 V AC 50/60 Hz conforming to IEC 60947-2
12.5Â kA at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
12.5Â kA at 110…130 V AC 50/60 Hz conforming to IEC 60947-2
9Â kA at 380…400 V AC 50/60 Hz conforming to IEC 60947-2
7.5 kA at 415 V AC 50/60 Hz conforming to IEC 60947-2suitability for isolation Yes conforming to IEC 60947-2utilisation category Category Atrip unit name TM-Dtrip unit technology Thermal-magnetictrip unit rating 50 A at 50 °Cprotection type Overload protection
Short-circuit protectionpollution degree 3 conforming to IEC 60947Complementary control type Togglemounting mode Fixedmounting support Backplateupside connection Frontdownside connection Frontmechanical durability 8500Â cycleselectrical durability Category A: 1500Â cycles 415 V AC 50/60 Hz conforming to IEC 60947-2connection pitch 25Â mmlocal signalling Positive contact indicationneutral protection setting Without protectionearth-leakage protection Withoutheight 130Â mmwidth 100Â mmdepth 60Â mmSKU: n/a -
Electro, SOCKETS, SOCKETS & SWITCHES
13AMP DOUBLE SOCKET WITH LIGHT – BG826
13A Rated
Easy to install, supplied with fixing screws and installation instructions
Angled in-line terminals with captive screws provide easy access for quick installation
Screw covers for sleek appearance
Twin earth fitted as standard to allow a double earth facility for installations requiring high integrity protective connection Ref. BS 7671:2008
LED power Indicator, reliable and low power
Minimum mounting box depth 25mm
Manufactured using high grade thermoset Urea which effectively inhibits the growth of infectious diseases, including MRSA, E-Coli, Salmonella and Klebsiella Pneumonia bacteria
SKU: n/a -
Schneider Circuit Breakers, SCHNEIDER SECTIONS
Acti9 iC60N 3P 4A C Miniature Circuit breaker A9F44304
Schneider Circuit Breakers, SCHNEIDER SECTIONSActi9 iC60N 3P 4A C Miniature Circuit breaker A9F44304
Main range Acti 9product name Disbo iC60product or component type Miniature circuit-breakerdevice short name IC60Npoles description 3Pnumber of protected poles 3[In] rated current 4Â Anetwork type ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 50Â kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
50Â kA Icu at 12…133 V AC 50/60 Hz conforming to EN/IEC 60947-2
50Â kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2
25Â kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2
6000Â A Icn at 415 V AC 50/60 Hz conforming to EN/IEC 60898-1
15Â kA Icu at 100…133 V DC conforming to EN/IEC 60947-2utilisation category Category A conforming to EN/IEC 60947-2Complementary network frequency 50/60 Hz[Ue] rated operational voltage 440 V AC 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 50Â kA 100Â % conforming to EN/IEC 60947-2 – 220…240 V AC 50/60 Hz
50Â kA 100Â % conforming to EN/IEC 60947-2 – 12…133 V AC 50/60 Hz
50Â kA 100Â % conforming to EN/IEC 60947-2 – 380…415 V AC 50/60 Hz
25Â kA 100Â % conforming to EN/IEC 60947-2 – 440 V AC 50/60 Hz
6000Â A 100Â % conforming to EN/IEC 60898-1 – 415 V AC 50/60 Hz
15 kA 100 % conforming to EN/IEC 60947-2 – 100…133 V DClimitation class 3 conforming to EN/IEC 60947-2[Ui] rated insulation voltage 500 V AC 50/60 Hz[Uimp] rated impulse withstand voltage 6 kV conforming to EN/IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Clip-onmounting support Rail9 mm pitches 6height 85 mmwidth 54 mmdepth 78.5 mmnet weight 0.375 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesprovision for padlocking Padlockableconnections – terminals Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 2 N.m top or bottomearth-leakage protection Separate blockSKU: n/a -
Schneider Circuit Breakers, SCHNEIDER SECTIONS
Acti9 iC60N 2P 50A C Miniature Circuit breaker A9F44250
Schneider Circuit Breakers, SCHNEIDER SECTIONSActi9 iC60N 2P 50A C Miniature Circuit breaker A9F44250
Main range Acti 9product name Disbo iC60product or component type Miniature circuit-breakerdevice short name IC60Npoles description 2Pnumber of protected poles 2[In] rated current 50Â Anetwork type ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 6Â kA Icu at 100…133 V DC conforming to EN/IEC 60947-2
6000Â A Icn at 415 V AC 50/60 Hz conforming to EN/IEC 60898-1
36Â kA Icu at 12…133 V AC 50/60 Hz conforming to EN/IEC 60947-2
20Â kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
10Â kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2
6Â kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2utilisation category Category A conforming to EN/IEC 60947-2Complementary network frequency 50/60 Hz[Ue] rated operational voltage 440 V AC 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 27Â kA 75Â % conforming to EN/IEC 60947-2 – 12…133 V AC 50/60 Hz
15Â kA 75Â % conforming to EN/IEC 60947-2 – 220…240 V AC 50/60 Hz
7.5Â kA 75Â % conforming to EN/IEC 60947-2 – 380…415 V AC 50/60 Hz
4.5Â kA 75Â % conforming to EN/IEC 60947-2 – 440 V AC 50/60 Hz
6000Â A 100Â % conforming to EN/IEC 60898-1 – 415 V AC 50/60 Hz
6 kA 100 % conforming to EN/IEC 60947-2 – 100…133 V DClimitation class 3 conforming to EN/IEC 60947-2[Ui] rated insulation voltage 500 V AC 50/60 Hz[Uimp] rated impulse withstand voltage 6 kV conforming to EN/IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Clip-onmounting support Rail9 mm pitches 4height 85 mmwidth 36 mmdepth 78.5 mmnet weight 0.25 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesprovision for padlocking Padlockableconnections – terminals Single terminal (top or bottom) 1…35 mm² rigid
Single terminal (top or bottom) 1…25 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 3.5 N.m top or bottomearth-leakage protection Separate blockSKU: n/a
There are no reviews yet.