Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONS
Easy9 miniature circuit breaker- 2P – 40 A – C curve – 6000 A – 230 V EZ9F56240
range |
Easy9
|
|
---|---|---|
device application |
Distribution
|
|
product or component type |
Miniature circuit-breaker
|
|
device short name |
Easy9 MCB
|
|
Poles |
2P
|
|
number of protected poles |
2
|
|
[In] rated current |
40Â A
|
|
network type |
AC
|
|
trip unit technology |
Thermal-magnetic
|
|
curve code |
C
|
|
breaking capacity |
10000Â A Icn at 220 V AC 50/60 Hz conforming to IEC 60898-1
6000Â A Icn at 400 V AC 50/60 Hz conforming to IEC 60898-1 |
|
suitability for isolation |
Yes conforming to IEC 60898-1
|
network frequency |
50/60 Hz
|
|
---|---|---|
[Ue] rated operational voltage |
220 V AC 50/60 Hz
400 V AC 50/60 Hz |
|
magnetic tripping limit |
5…10 x In
|
|
[Ics] rated service breaking capacity |
6Â kA 100Â % x Icn at 230 V AC 50/60 Hz conforming to IEC 60898-1
|
|
[Ui] rated insulation voltage |
500Â V AC 50/60 Hz conforming to IEC 60898-1
|
|
[Uimp] rated impulse withstand voltage |
4Â kV conforming to IEC 60898-1
|
|
contact position indicator |
Yes
|
|
control type |
Toggle
|
|
local signalling |
Without
|
|
mounting mode |
Clip-on
|
|
mounting support |
DIN rail
|
|
9 mm pitches |
4
|
|
height |
81Â mm
|
|
width |
36Â mm
|
|
depth |
66.5Â mm
|
|
colour |
Grey (RAL 7035)
|
|
mechanical durability |
10000Â cycles
|
|
electrical durability |
4000Â cycles
|
|
connections – terminals |
Tunnel type terminal (top or bottom) 1…25 mm² flexible
Tunnel type terminal (top or bottom) 1…35 mm² rigid |
|
tightening torque |
3.5Â N.m top or bottom
|
|
earth-leakage protection |
Without
|
₦10,928.00
Compare-
Schneider Mureva Floodlight, SCHNEIDER SECTIONS
Mureva lights, Floodlight 150W, IP65 230V IMT47222
Main range Murevarange of product Mureva lightsproduct name Floodlightproduct or component type Lampdevice application Ware-houses and parking garages
Residential
Media device support
Public areas
Secure lighting
Stadiums and arenasComplementary type of installation OutdoorTotal system power 150 Wlight source LED[Ue] rated operational voltage 230 V ACpower factor 0.9colour rendering index Ra=80luminous flux 15000 lmbulb lifespan 50000 hcolour temperature 6500 Kcolour Blackprovided equipment Sensorbeam angle 110 °shape Rectangularheight 342.0 mmwidth 278.0 mmdepth 61.0 mmnet weight 4.05 kgSKU: n/a -
Schneider Circuit Breakers, SCHNEIDER SECTIONS
Miniature circuit-breaker, Acti9 iC60H, 2P, 10 A, C curve, 10000 A (IEC 60898-1), 15 kA (IEC 60947-2) A9F84210
Schneider Circuit Breakers, SCHNEIDER SECTIONSMiniature circuit-breaker, Acti9 iC60H, 2P, 10 A, C curve, 10000 A (IEC 60898-1), 15 kA (IEC 60947-2) A9F84210
Main device application Distributionrange Acti 9product name Acti 9 iC60product or component type Miniature circuit-breakerdevice short name IC60Hpoles description 2Pnumber of protected poles 2[In] rated current 10Â Anetwork type AC
DCtrip unit technology Thermal-magneticcurve code Cbreaking capacity 10000Â A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
42Â kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2
10Â kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2
15Â kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2
30Â kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
15Â kA Icu at <= 125 V DC conforming to EN/IEC 60947-2
42Â kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2utilisation category Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2suitability for isolation Yes conforming to EN 60898-1
Yes conforming to EN 60947-2
Yes conforming to IEC 60898-1
Yes conforming to IEC 60947-2standards EN 60898-1
IEC 60947-2
IEC 60898-1
EN 60947-2Complementary network frequency 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 15Â kA 50Â % conforming to EN 60947-2 – 220…240 V AC 50/60 Hz
7.5Â kA 50Â % conforming to EN 60947-2 – 380…415 V AC 50/60 Hz
5Â kA 50Â % conforming to EN 60947-2 – 440 V AC 50/60 Hz
15Â kA 50Â % conforming to IEC 60947-2 – 220…240 V AC 50/60 Hz
7.5Â kA 50Â % conforming to IEC 60947-2 – 380…415 V AC 50/60 Hz
5Â kA 50Â % conforming to IEC 60947-2 – 440 V AC 50/60 Hz
7500Â A 75Â % conforming to EN 60898-1 – 400 V AC 50/60 Hz
7500Â A 75Â % conforming to IEC 60898-1 – 400 V AC 50/60 Hz
21Â kA 50Â % conforming to IEC 60947-2 – 12…133 V AC 50/60 Hz
21Â kA 50Â % conforming to EN 60947-2 – 12…133 V AC 50/60 Hz
15Â kA 100Â % conforming to IEC 60947-2 – 72…125 V DC
15Â kA 100Â % conforming to EN 60947-2 – 72…125 V DClimitation class 3 conforming to EN 60898-1
3 conforming to IEC 60898-1[Ui] rated insulation voltage 500Â V AC 50/60 Hz conforming to EN 60947-2
500Â V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6Â kV conforming to EN 60947-2
6 kV conforming to IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Fixedmounting support DIN railcomb busbar and distribution block compatibility Top or bottom: YES9 mm pitches 4height 85 mmwidth 36 mmdepth 78.5 mmnet weight 0.25 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesconnections – terminals Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 2 N.m top or bottomearth-leakage protection Separate blockSKU: n/a -
-
Schneider Circuit Breakers, SCHNEIDER SECTIONS
Acti9 iC60N 2P 50A C Miniature Circuit breaker A9F44250
Schneider Circuit Breakers, SCHNEIDER SECTIONSActi9 iC60N 2P 50A C Miniature Circuit breaker A9F44250
Main range Acti 9product name Disbo iC60product or component type Miniature circuit-breakerdevice short name IC60Npoles description 2Pnumber of protected poles 2[In] rated current 50Â Anetwork type ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 6Â kA Icu at 100…133 V DC conforming to EN/IEC 60947-2
6000Â A Icn at 415 V AC 50/60 Hz conforming to EN/IEC 60898-1
36Â kA Icu at 12…133 V AC 50/60 Hz conforming to EN/IEC 60947-2
20Â kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
10Â kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2
6Â kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2utilisation category Category A conforming to EN/IEC 60947-2Complementary network frequency 50/60 Hz[Ue] rated operational voltage 440 V AC 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 27Â kA 75Â % conforming to EN/IEC 60947-2 – 12…133 V AC 50/60 Hz
15Â kA 75Â % conforming to EN/IEC 60947-2 – 220…240 V AC 50/60 Hz
7.5Â kA 75Â % conforming to EN/IEC 60947-2 – 380…415 V AC 50/60 Hz
4.5Â kA 75Â % conforming to EN/IEC 60947-2 – 440 V AC 50/60 Hz
6000Â A 100Â % conforming to EN/IEC 60898-1 – 415 V AC 50/60 Hz
6 kA 100 % conforming to EN/IEC 60947-2 – 100…133 V DClimitation class 3 conforming to EN/IEC 60947-2[Ui] rated insulation voltage 500 V AC 50/60 Hz[Uimp] rated impulse withstand voltage 6 kV conforming to EN/IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Clip-onmounting support Rail9 mm pitches 4height 85 mmwidth 36 mmdepth 78.5 mmnet weight 0.25 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesprovision for padlocking Padlockableconnections – terminals Single terminal (top or bottom) 1…35 mm² rigid
Single terminal (top or bottom) 1…25 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 3.5 N.m top or bottomearth-leakage protection Separate blockSKU: n/a -
Schneider Circuit Breakers, SCHNEIDER SECTIONS
Miniature circuit-breaker, Acti9 iC60H, 2P, 20 A, C curve, 10000 A (IEC 60898-1), 15 kA (IEC 60947-2) A9F84220
Schneider Circuit Breakers, SCHNEIDER SECTIONSMiniature circuit-breaker, Acti9 iC60H, 2P, 20 A, C curve, 10000 A (IEC 60898-1), 15 kA (IEC 60947-2) A9F84220
Main device application Distributionrange Acti 9product name Acti 9 iC60product or component type Miniature circuit-breakerdevice short name IC60Hpoles description 2Pnumber of protected poles 2[In] rated current 20Â Anetwork type AC
DCtrip unit technology Thermal-magneticcurve code Cbreaking capacity 10000Â A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
42Â kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2
10Â kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2
15Â kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2
30Â kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
15Â kA Icu at <= 125 V DC conforming to EN/IEC 60947-2
42Â kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2utilisation category Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2suitability for isolation Yes conforming to EN 60898-1
Yes conforming to EN 60947-2
Yes conforming to IEC 60898-1
Yes conforming to IEC 60947-2standards IEC 60898-1
EN 60898-1
IEC 60947-2
EN 60947-2Complementary network frequency 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 15Â kA 50Â % conforming to EN 60947-2 – 220…240 V AC 50/60 Hz
7.5Â kA 50Â % conforming to EN 60947-2 – 380…415 V AC 50/60 Hz
5Â kA 50Â % conforming to EN 60947-2 – 440 V AC 50/60 Hz
15Â kA 50Â % conforming to IEC 60947-2 – 220…240 V AC 50/60 Hz
7.5Â kA 50Â % conforming to IEC 60947-2 – 380…415 V AC 50/60 Hz
5Â kA 50Â % conforming to IEC 60947-2 – 440 V AC 50/60 Hz
7500Â A 75Â % conforming to EN 60898-1 – 400 V AC 50/60 Hz
7500Â A 75Â % conforming to IEC 60898-1 – 400 V AC 50/60 Hz
21Â kA 50Â % conforming to IEC 60947-2 – 12…133 V AC 50/60 Hz
21Â kA 50Â % conforming to EN 60947-2 – 12…133 V AC 50/60 Hz
15Â kA 100Â % conforming to IEC 60947-2 – 72…125 V DC
15Â kA 100Â % conforming to EN 60947-2 – 72…125 V DClimitation class 3 conforming to EN 60898-1
3 conforming to IEC 60898-1[Ui] rated insulation voltage 500Â V AC 50/60 Hz conforming to EN 60947-2
500Â V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6Â kV conforming to EN 60947-2
6 kV conforming to IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Fixedmounting support DIN railcomb busbar and distribution block compatibility Top or bottom: YES9 mm pitches 4height 85 mmwidth 36 mmdepth 78.5 mmnet weight 0.25 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesconnections – terminals Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 2 N.m top or bottomearth-leakage protection Separate blockSKU: n/a
There are no reviews yet.