EZC100F3050 – Circuit breaker Easypact EZC100F – TMD – 50 A – 3 poles 3d
range of product |
EasyPact
|
|
---|---|---|
product or component type |
Circuit breaker
|
|
device short name |
Easypact EZC100F
|
|
circuit breaker name |
Easypact EZC100F
|
|
device application |
Distribution
|
|
poles description |
3P
|
|
protected poles description |
3t
|
|
network type |
DC
AC |
|
network frequency |
50/60 Hz
|
|
[In] rated current |
100 A at 40 °C
|
|
[Ui] rated insulation voltage |
690 V AC 50/60 Hz conforming to IEC 60947-2
|
|
[Uimp] rated impulse withstand voltage |
6 kV conforming to IEC 60947-2
|
|
[Ue] rated operational voltage |
550 V AC 50/60 Hz conforming to IEC 60947-2
250 V DC conforming to IEC 60947-2 |
|
breaking capacity code |
F
|
|
breaking capacity |
25 kA Icu at 110…130 V AC 50/60 Hz conforming to IEC 60947-2
25 kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2 5 kA Icu at 125 V DC 1P conforming to IEC 60947-2 5 kA Icu at 250 V DC 2P conforming to IEC 60947-2 5 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 400…415 V AC 50/60 Hz conforming to IEC 60947-2 7.5 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
|
[Ics] rated service breaking capacity |
12.5 kA at 110/130 V AC 50/60 Hz conforming to IEC 60947-2
12.5 kA at 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA at 125 V DC conforming to IEC 60947-2 2.5 kA at 250 V DC conforming to IEC 60947-2 2.5 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2 5 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2 5 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 3.75 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
|
suitability for isolation |
Yes conforming to IEC 60947-2
|
|
utilisation category |
Category A
|
|
trip unit name |
TM-D
|
|
trip unit technology |
Thermal-magnetic
|
|
trip unit rating |
50 A at 50 °C
|
|
protection type |
Overload protection
Short-circuit protection |
|
pollution degree |
3 conforming to IEC 60664-1
3 conforming to IEC 947-1 |
control type |
Toggle
|
|
---|---|---|
mounting mode |
Fixed
|
|
mounting support |
Backplate
|
|
upside connection |
Front
|
|
downside connection |
Front
|
|
mechanical durability |
8500 cycles
|
|
electrical durability |
Category A: 1500 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2
|
|
connection pitch |
25 mm
|
|
local signalling |
Positive contact indication
|
|
neutral protection setting |
Without protection
|
|
earth-leakage protection |
Without
|
|
height |
130 mm
|
|
width |
75 mm
|
|
depth |
60 mm
|
₦18,999.00
Compare-
CEILING LIGHTS, ELECTRICAL FITTINGS, ELECTRICAL INDUSTRIAL, Electro, HIGH BAY LIGHTS, HOME&OFFICE LIGHTING, INTERIOR LIGHTING, LED LIGHTS, LIGHTING
Philip Highbay Light BY239P LED100/CW PSU 100watt Philips
CEILING LIGHTS, ELECTRICAL FITTINGS, ELECTRICAL INDUSTRIAL, Electro, HIGH BAY LIGHTS, HOME&OFFICE LIGHTING, INTERIOR LIGHTING, LED LIGHTS, LIGHTINGPhilip Highbay Light BY239P LED100/CW PSU 100watt Philips
General Information
Beam angle of light source – °Light source color 865 cool daylightLight source replaceable NoNumber of gear units 1 unitDriver/power unit/transformer Power supply unitDriver included YesOptic type –Optical cover/lens type Polycarbonate bowl/cover foggyLuminaire light beam spread 100°Control interface –Connection –Cable Cable 0.3 m without plugOperating and Electrical
Input Voltage 220 to 240 VInput Frequency 50 to 60 HzInitial CLO power consumption – WAverage CLO power consumption – WSKU: n/a -
CHANGEOVER SWITCHES, Electro, GEAR SWITCHES & CHANGEOVER
ABB CHANGEOVER SWITCH 400A with Enclosure
Including a black plastic IP65 I-0-II pistol type handle (see the table below), shaft and bolt set for the cable connection. Handle padlockable in the 0-position, door interlock in the I- and Iipositions and when padlocked.
Dimensions
-
- Product Net Width:
- 265 mm
-
- Product Net Height:
- 185 mm
-
- Product Net Depth / Length:
- 203 mm
-
- Product Net Weight:
- 7.415 kg
16.35 lb
Technical
-
- Rated Operational Current AC-21A (Ie):
- (380 … 415 V) 400 A
(500 V) 400 A
(690 V) 400 A
-
- Rated Operational Current AC-22A (Ie):
- (380 … 415 V) 400 A
(500 V) 400 A
(690 V) 400 A
-
- Rated Operational Current AC-23A (Ie):
- (380 … 415 V) 400 A
(500 V) 400 A
(690 V) 400 A
-
- Rated Operational Current AC-31B (Ie):
- (380 … 415 V) 400 A
-
- Rated Operational Current AC-33B (Ie):
- (380 … 415 V) 400 A
-
- Rated Operational Power AC-23A (Pe):
- (380 … 415 V) 220 kW
(500 V) 280 kW
(690 V) 400 kW
-
- Conventional Free-air Thermal Current (Ith):
- q = 40 °C 400 A
-
- Conventional Thermal Current (Ithe):
- Fully Enclosed 400 A
-
- Rated Impulse Withstand Voltage (Uimp):
- 12 kV
-
- Rated Insulation Voltage (Ui):
- 1000 V
-
- Rated Operational Voltage:
- 1000 V
-
- Rated Short-time Withstand Current (Icw):
- for 1 s 15 kiloampere rms
-
- Power Loss:
- 10 W
SKU: n/a -
-
LIGHT SWITCHES & ELECTRICAL SOCKETS, SCHNEIDER SECTIONS
Ultimate Screwless flat plate – data/telephone socket – RJ11 – black nickel GU7451BBN
LIGHT SWITCHES & ELECTRICAL SOCKETS, SCHNEIDER SECTIONSUltimate Screwless flat plate – data/telephone socket – RJ11 – black nickel GU7451BBN
Main range of product Ultimateaesthetic name Screwless flat plateproduct or component type Data/telephone sockettelephone socket type RJ11colour tint Black nickel polished
BlackComplementary number of gangs 1 gangfixing mode By screwsconnections – terminals Screw terminalsmaterial Steelquantity per set Set of 1depth 88 mmwidth 88 mmheight 35 mmSKU: n/a -
Electro, INDOOR LIGHTS, LED LIGHTS, LIGHT BULBS, LIGHTING
WINWIN Surface Mounted LED Panel light 12watt
Electro, INDOOR LIGHTS, LED LIGHTS, LIGHT BULBS, LIGHTINGWINWIN Surface Mounted LED Panel light 12watt
Rated Power(W): 6/12/18/24W
Size: φ120*40mm/φ174*40mm/φ225*40mm/φ300*40mm
Input Voltage(V): AC85-265V
LED Type: SMD
Lumen(LM): 60-80LM/W
Frequency Range(Hz): 50-60Hz
Beam angle(Degree): 180°
Color Temperature(K): 2700K-6500K
CRI(Ra): >70
Power factor(PF): >0.55
LED Chip Brand: San’an
Material: Aluminum+Pmma
Working Temperature: -20℃~+45℃SKU: n/a -
ELECTRICAL INDUSTRIAL, Electro, RECLINE CABLES
Cometstar Nigeria Cable NAY 4 x120.0MM
The construction and material are determined by three main factors:
• Working voltage, determining the thickness of the insulation;
• Current-carrying capacity, determining the cross-sectional size of the conductor(s);
• Environmental conditions such as temperature, water, chemical or sunlight exposure, and mechanical impact, determining the form and composition of the outer cable jacketSKU: Cometstar Nigeria Cable NAY 4 x120.0MM
There are no reviews yet.