EZC100F3050 – Circuit breaker Easypact EZC100F – TMD – 50 A – 3 poles 3d
range of product |
EasyPact
|
|
---|---|---|
product or component type |
Circuit breaker
|
|
device short name |
Easypact EZC100F
|
|
circuit breaker name |
Easypact EZC100F
|
|
device application |
Distribution
|
|
poles description |
3P
|
|
protected poles description |
3t
|
|
network type |
DC
AC |
|
network frequency |
50/60 Hz
|
|
[In] rated current |
100 A at 40 °C
|
|
[Ui] rated insulation voltage |
690 V AC 50/60 Hz conforming to IEC 60947-2
|
|
[Uimp] rated impulse withstand voltage |
6 kV conforming to IEC 60947-2
|
|
[Ue] rated operational voltage |
550 V AC 50/60 Hz conforming to IEC 60947-2
250 V DC conforming to IEC 60947-2 |
|
breaking capacity code |
F
|
|
breaking capacity |
25 kA Icu at 110…130 V AC 50/60 Hz conforming to IEC 60947-2
25 kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2 5 kA Icu at 125 V DC 1P conforming to IEC 60947-2 5 kA Icu at 250 V DC 2P conforming to IEC 60947-2 5 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 400…415 V AC 50/60 Hz conforming to IEC 60947-2 7.5 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
|
[Ics] rated service breaking capacity |
12.5 kA at 110/130 V AC 50/60 Hz conforming to IEC 60947-2
12.5 kA at 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA at 125 V DC conforming to IEC 60947-2 2.5 kA at 250 V DC conforming to IEC 60947-2 2.5 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2 5 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2 5 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 3.75 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
|
suitability for isolation |
Yes conforming to IEC 60947-2
|
|
utilisation category |
Category A
|
|
trip unit name |
TM-D
|
|
trip unit technology |
Thermal-magnetic
|
|
trip unit rating |
50 A at 50 °C
|
|
protection type |
Overload protection
Short-circuit protection |
|
pollution degree |
3 conforming to IEC 60664-1
3 conforming to IEC 947-1 |
control type |
Toggle
|
|
---|---|---|
mounting mode |
Fixed
|
|
mounting support |
Backplate
|
|
upside connection |
Front
|
|
downside connection |
Front
|
|
mechanical durability |
8500 cycles
|
|
electrical durability |
Category A: 1500 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2
|
|
connection pitch |
25 mm
|
|
local signalling |
Positive contact indication
|
|
neutral protection setting |
Without protection
|
|
earth-leakage protection |
Without
|
|
height |
130 mm
|
|
width |
75 mm
|
|
depth |
60 mm
|
₦18,999.00
Compare-
ELECTRICAL INDUSTRIAL, TRANSFORMER
MEKSAN Transformer 200kVA 11/415kV
Meksan Transformer manufacture distribution and power transformer from 50 kVA up to 50 MVA. Our products are produced in accordance with the TS 267 and the IEC60076 standards. Our production is documented with the TSE (Türkish Standard Institue) standards confortmity, ISO 9001:2000 quality system and ISO 14001 environmental management system certificates.
SKU: n/a -
Schneider Circuit Breakers, SCHNEIDER SECTIONS
IC60H – miniature circuit breaker – 2P – 25A – C curve A9F84225
Schneider Circuit Breakers, SCHNEIDER SECTIONSIC60H – miniature circuit breaker – 2P – 25A – C curve A9F84225
Main device application Distributionrange Acti 9product name Acti 9 iC60product or component type Miniature circuit-breakerdevice short name IC60Hpoles description 2Pnumber of protected poles 2[In] rated current 25 Anetwork type AC
DCtrip unit technology Thermal-magneticcurve code Cbreaking capacity 10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
42 kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2
10 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2
15 kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2
30 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
15 kA Icu at <= 125 V DC conforming to EN/IEC 60947-2
42 kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2utilisation category Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2suitability for isolation Yes conforming to EN 60898-1
Yes conforming to EN 60947-2
Yes conforming to IEC 60898-1
Yes conforming to IEC 60947-2standards EN 60898-1
EN 60947-2
IEC 60898-1
IEC 60947-2Complementary network frequency 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 15 kA 50 % conforming to EN 60947-2 – 220…240 V AC 50/60 Hz
7.5 kA 50 % conforming to EN 60947-2 – 380…415 V AC 50/60 Hz
5 kA 50 % conforming to EN 60947-2 – 440 V AC 50/60 Hz
15 kA 50 % conforming to IEC 60947-2 – 220…240 V AC 50/60 Hz
7.5 kA 50 % conforming to IEC 60947-2 – 380…415 V AC 50/60 Hz
5 kA 50 % conforming to IEC 60947-2 – 440 V AC 50/60 Hz
7500 A 75 % conforming to EN 60898-1 – 400 V AC 50/60 Hz
7500 A 75 % conforming to IEC 60898-1 – 400 V AC 50/60 Hz
21 kA 50 % conforming to IEC 60947-2 – 12…133 V AC 50/60 Hz
21 kA 50 % conforming to EN 60947-2 – 12…133 V AC 50/60 Hz
15 kA 100 % conforming to IEC 60947-2 – 72…125 V DC
15 kA 100 % conforming to EN 60947-2 – 72…125 V DClimitation class 3 conforming to EN 60898-1
3 conforming to IEC 60898-1[Ui] rated insulation voltage 500 V AC 50/60 Hz conforming to EN 60947-2
500 V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6 kV conforming to EN 60947-2
6 kV conforming to IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Fixedmounting support DIN railcomb busbar and distribution block compatibility Top or bottom: YES9 mm pitches 4height 85 mmwidth 36 mmdepth 78.5 mmnet weight 0.25 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesconnections – terminals Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 2 N.m top or bottomearth-leakage protection Separate blockSKU: n/a -
LIGHT SWITCHES & ELECTRICAL SOCKETS
Lisse – Switched Socket – 2 gang – 13A SP 2USB Satin Brass with Black Interior GGBL30202USBABSBS
LIGHT SWITCHES & ELECTRICAL SOCKETSLisse – Switched Socket – 2 gang – 13A SP 2USB Satin Brass with Black Interior GGBL30202USBABSBS
Main range Lisseaesthetic name Screwless decoproduct or component type Switched socket with USB chargerdevice presentation Complete productoutlet standard Britishcolour tint Interior: black
Cover plate: satin brassearth circuit Standard earthquantity per set Set of 1type of packing BagComplementary switch function 1-polerated current 13 A at 250 V AC 50/60 Hzintegrated connection type 2 USB port 5 V DC 2.1 Aactuator Rockernumber of gangs 2 gangspilot light without LEDfixing mode Concealed screwsconnections – terminals Screw terminalsmaterial Stainless steeltype of installation Indoordepth 31 mmwidth 148 mmheight 87 mmnet weight 0.239 kgSKU: n/a -
SOCKETS, SOCKETS & SWITCHES
ABB CRS213 RCD Switched Socket Outlet 2 Gang 30A
Product features
– Switched socket outlet with extra safety against electric shocks
– Instant disconnection when there is current leakage
– Built-in test button
– Ease of replacement of existing socket outlets
– Ease of use with neon and trip indication Safety features
– Built-in test button
– Continuous protectionSKU: n/a -
SCHNEIDER SECTIONS, Schneider Thorsman Testmeters
Thorsman Voltage Detector Pen IMT23109
Main range Thorsmanproduct or component type Voltage testersupply 2 battery 1.5 V AAAComplementary local signalling Presence of voltage: LED
Presence of voltage: alarm sound indicatormeasurement voltage 5…1000 V ACnetwork frequency 50…400 Hzmeasurement category Category IV 1000 Vlanguage Norwegian
Finnish
English
Danish
Swedishheight 152 mmwidth 32 mmdepth 28 mmSKU: n/a -
Schneider Circuit Breakers, SCHNEIDER SECTIONS
Miniature circuit-breaker, Acti9 iC60H, 2P, 1 A, C curve, 10000 A (IEC 60898-1), 70 kA (IEC 60947-2) A9F84201
Schneider Circuit Breakers, SCHNEIDER SECTIONSMiniature circuit-breaker, Acti9 iC60H, 2P, 1 A, C curve, 10000 A (IEC 60898-1), 70 kA (IEC 60947-2) A9F84201
Main device application Distributionrange Acti 9product name Acti 9 iC60product or component type Miniature circuit-breakerdevice short name IC60Hpoles description 2Pnumber of protected poles 2[In] rated current 1 Anetwork type DC
ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
15 kA Icu at <= 125 V DC conforming to EN/IEC 60947-2
70 kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2
70 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
70 kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2
70 kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2
70 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2utilisation category Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2suitability for isolation Yes conforming to EN 60898-1
Yes conforming to EN 60947-2
Yes conforming to IEC 60898-1
Yes conforming to IEC 60947-2standards EN 60898-1
IEC 60898-1
EN 60947-2
IEC 60947-2quality labels NFComplementary network frequency 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 70 kA 100 % conforming to EN 60947-2 – 220…240 V AC 50/60 Hz
70 kA 100 % conforming to IEC 60947-2 – 220…240 V AC 50/60 Hz
70 kA 100 % conforming to EN 60947-2 – 380…415 V AC 50/60 Hz
70 kA 100 % conforming to IEC 60947-2 – 380…415 V AC 50/60 Hz
7500 A 75 % conforming to EN 60898-1 – 400 V AC 50/60 Hz
7500 A 75 % conforming to IEC 60898-1 – 400 V AC 50/60 Hz
70 kA 100 % conforming to IEC 60947-2 – 12…133 V AC 50/60 Hz
70 kA 100 % conforming to EN 60947-2 – 12…133 V AC 50/60 Hz
50 kA 100 % conforming to EN 60947-2 – 440 V AC 50/60 Hz
50 kA 100 % conforming to IEC 60947-2 – 440 V AC 50/60 Hz
15 kA 100 % conforming to IEC 60947-2 – 72…125 V DC
15 kA 100 % conforming to EN 60947-2 – 72…125 V DClimitation class 3 conforming to EN 60898-1
3 conforming to IEC 60898-1[Ui] rated insulation voltage 500 V AC 50/60 Hz conforming to EN 60947-2
500 V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6 kV conforming to EN 60947-2
6 kV conforming to IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Fixedmounting support DIN railcomb busbar and distribution block compatibility Top or bottom: YES9 mm pitches 4height 85 mmwidth 36 mmdepth 78.5 mmnet weight 0.25 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesconnections – terminals Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 2 N.m top or bottomearth-leakage protection Separate blockSKU: n/a
There are no reviews yet.