Low Voltage Products and Systems, SCHNEIDER SECTIONS
EZC100F3060 – Circuit breaker Easypact EZC100F – TMD – 60 A – 3 poles 3d
range of product |
EasyPact
|
|
---|---|---|
product or component type |
Circuit breaker
|
|
device short name |
Easypact EZC100F
|
|
circuit breaker name |
Easypact EZC100F
|
|
device application |
Distribution
|
|
poles description |
3P
|
|
protected poles description |
3t
|
|
network type |
DC
AC |
|
network frequency |
50/60 Hz
|
|
[In] rated current |
100 A at 40 °C
|
|
[Ui] rated insulation voltage |
690 V AC 50/60 Hz conforming to IEC 60947-2
|
|
[Uimp] rated impulse withstand voltage |
6 kV conforming to IEC 60947-2
|
|
[Ue] rated operational voltage |
550 V AC 50/60 Hz conforming to IEC 60947-2
250 V DC conforming to IEC 60947-2 |
|
breaking capacity code |
F
|
|
breaking capacity |
25 kA Icu at 110…130 V AC 50/60 Hz conforming to IEC 60947-2
25 kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2 5 kA Icu at 125 V DC 1P conforming to IEC 60947-2 5 kA Icu at 250 V DC 2P conforming to IEC 60947-2 5 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 400…415 V AC 50/60 Hz conforming to IEC 60947-2 7.5 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
|
[Ics] rated service breaking capacity |
12.5 kA at 110/130 V AC 50/60 Hz conforming to IEC 60947-2
12.5 kA at 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA at 125 V DC conforming to IEC 60947-2 2.5 kA at 250 V DC conforming to IEC 60947-2 2.5 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2 5 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2 5 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 3.75 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
|
suitability for isolation |
Yes conforming to IEC 60947-2
|
|
utilisation category |
Category A
|
|
trip unit name |
TM-D
|
|
trip unit technology |
Thermal-magnetic
|
|
trip unit rating |
60 A at 50 °C
|
|
protection type |
Overload protection
Short-circuit protection |
|
pollution degree |
3 conforming to IEC 60664-1
3 conforming to IEC 947-1 |
control type |
Toggle
|
|
---|---|---|
mounting mode |
Fixed
|
|
mounting support |
Backplate
|
|
upside connection |
Front
|
|
downside connection |
Front
|
|
mechanical durability |
8500 cycles
|
|
electrical durability |
Category A: 1500 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2
|
|
connection pitch |
25 mm
|
|
local signalling |
Positive contact indication
|
|
neutral protection setting |
Without protection
|
|
earth-leakage protection |
Without
|
|
height |
130 mm
|
|
width |
75 mm
|
|
depth |
60 mm
|
₦17,999.00
Compare-
Schneider Circuit Breakers, SCHNEIDER SECTIONS
Easy9 switch disconnector – 3P – 63 A – 400 V EZ9S16363
Schneider Circuit Breakers, SCHNEIDER SECTIONSEasy9 switch disconnector – 3P – 63 A – 400 V EZ9S16363
Main range Easy9product or component type Switchdevice short name Easy9 switchswitch application DistributionPoles 3Putilisation category AC-22Asuitability for isolation YesComplementary [Ie] rated operational current 63 A at 400 V 50/60 Hz[Ue] rated operational voltage 400 V AC 50/60 Hz[Icm] rated short-circuit making capacity 0.945 kA[Icw] rated short-time withstand current 0.756 kA during 1 s[Ui] rated insulation voltage 500 V AC 50/60 Hz[Uimp] rated impulse withstand voltage 4 kVcontrol type Togglelocal signalling ON/OFF indicationcontact position indicator Yesmounting mode Clip-onmounting support DIN rail9 mm pitches 6height 81 mmwidth 54 mmdepth 66.5 mmcolour Greymechanical durability 8500 cycleselectrical durability 1500 cyclesconnections – terminals Tunnel type terminal (top or bottom) 1…35 mm² rigid
Tunnel type terminal (top or bottom) 1…25 mm² flexibletightening torque 3.5 N.mSKU: n/a -
COMPUTING, LAPTOPS
HP 250 G7 CI3 4GB 1TB FREEDOS + BAG (3C136EA)
HP 250 G7 – Intel® Core™ i3-8103U , 15.6″) diagonal HD SVA anti-glare micro-edge WLED-backlit, 220 nits, NTSC (1366 x 768) Display, 4 GB DDR4-2666 SDRAM (1 x 4GB), 1TB SATA HDD, Intel® HD Graphics 620, Optical drive included, Intel® Wireless-AC 9461 802.11ac (1×1) Wi-Fi® and Bluetooth®, 1 multi-format SD media card reader, 3-cell battery, FREEDOS PLUS LAPTOP BAG
SKU: n/a -
Low Voltage Products and Systems, SCHNEIDER SECTIONS
EZC250N3250 Circuit breaker Easypact EZC250N – TMD – 250 A – 3 poles 3d
Low Voltage Products and Systems, SCHNEIDER SECTIONSEZC250N3250 Circuit breaker Easypact EZC250N – TMD – 250 A – 3 poles 3d
Main range of product EasyPactproduct or component type Circuit breakerdevice short name Easypact EZC250Ncircuit breaker name Easypact EZC250Ndevice application Distributionpoles description 3Pprotected poles description 3tnetwork type DC
ACnetwork frequency 50/60 Hz[In] rated current 250 A at 40 °C[Ui] rated insulation voltage 690 V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947-2[Ue] rated operational voltage 550 V AC 50/60 Hz conforming to IEC 60947-2
250 V DC conforming to IEC 60947-2breaking capacity code Nbreaking capacity 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 110…130 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
20 kA Icu at 125 V DC 1P conforming to IEC 60947-2
20 kA Icu at 250 V DC 2P conforming to IEC 60947-2
25 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2
25 kA Icu at 400…415 V AC 50/60 Hz conforming to IEC 60947-2
8 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2[Ics] rated service breaking capacity 10 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
25 kA at 110/130 V AC 50/60 Hz conforming to IEC 60947-2
10 kA at 125 V DC conforming to IEC 60947-2
10 kA at 250 V DC conforming to IEC 60947-2
25 kA at 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2
4 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2
12.5 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2
12.5 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2suitability for isolation Yes conforming to IEC 60947-2utilisation category Category Atrip unit name TM-Dtrip unit technology Thermal-magnetictrip unit rating 250 A at 50 °Cprotection type Short-circuit protection
Overload protectionpollution degree 3 conforming to IEC 60664-1
3 conforming to IEC 947-1Complementary control type Togglemounting mode Fixedmounting support Backplateupside connection Frontdownside connection Frontmechanical durability 10000 cycleselectrical durability Category A: 5000 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2connection pitch 35 mmlocal signalling Positive contact indicationneutral protection setting Without protectionearth-leakage protection Withoutheight 165 mmwidth 105 mmdepth 60 mmSKU: n/a -
-
COOKER UNIT, Electro, SOCKETS & SWITCHES
BG 45A DP Cooker Control Unit with 13A Socket and Power Indicators
COOKER UNIT, Electro, SOCKETS & SWITCHESBG 45A DP Cooker Control Unit with 13A Socket and Power Indicators
Product Information
- Double Pole switches manufactured to BS EN 60669-1
- Cooker Control Units manufactured to BS4177
- Minimum mounting box depth 47mm
- L&N terminal capacity 4 x 4.0mm², 3 x 6.0mm² & 1 x 16.0mm²
- E terminal capacity 3 x 4.00mm², 6 x 6.0mm² & 1 x 16.0mm²
SKU: n/a -
LIGHT SWITCHES & ELECTRICAL SOCKETS
Lisse – 2-pole switch with indicator lamp – 1 gang – 20AX – white GGBL2011
LIGHT SWITCHES & ELECTRICAL SOCKETSLisse – 2-pole switch with indicator lamp – 1 gang – 20AX – white GGBL2011
Main range Lisseaesthetic name White mouldedproduct or component type Switch with indicator lampdevice presentation Complete productcolour tint Whitequantity per set Set of 10Complementary switch function 2-polecontrol type Rockernumber of gangs 1 gangpilot light Red LEDdevice mounting Wall mountedrated current 20 AXconnections – terminals Screw terminalsmaterial Urea (carbamide)surface finish Matttype of packing Cartonheight 87 mmwidth 87 mmdepth 25 mmnet weight 0.095 kgSKU: n/a
There are no reviews yet.