EZC100N4060 Circuit breaker Easypact EZC100N – TMD – 60 A – 4 poles 3d
range of product |
EasyPact
|
|
---|---|---|
product or component type |
Circuit breaker
|
|
device short name |
Easypact EZC100N
|
|
circuit breaker name |
Easypact EZC100N
|
|
device application |
Distribution
|
|
poles description |
4P
|
|
protected poles description |
3t
|
|
network type |
DC
AC |
|
network frequency |
50/60 Hz
|
|
[In] rated current |
100 A at 40 °C
|
|
[Ui] rated insulation voltage |
690 V AC 50/60 Hz conforming to IEC 60947-2
|
|
[Uimp] rated impulse withstand voltage |
6 kV conforming to IEC 60947-2
|
|
[Ue] rated operational voltage |
550 V AC 50/60 Hz conforming to IEC 60947-2
250 V DC conforming to IEC 60947-2 |
|
breaking capacity code |
N
|
|
breaking capacity |
10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
25 kA Icu at 110…130 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2 5 kA Icu at 125 V DC 1P conforming to IEC 60947-2 5 kA Icu at 250 V DC 2P conforming to IEC 60947-2 5 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 415 V AC 50/60 Hz conforming to IEC 60947-2 18 kA Icu at 380…400 V AC 50/60 Hz conforming to IEC 60947-2 |
|
[Ics] rated service breaking capacity |
5 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
2.5 kA at 125 V DC conforming to IEC 60947-2 2.5 kA at 250 V DC conforming to IEC 60947-2 2.5 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2 12.5 kA at 220…240 V AC 50/60 Hz conforming to IEC 60947-2 12.5 kA at 110…130 V AC 50/60 Hz conforming to IEC 60947-2 9 kA at 380…400 V AC 50/60 Hz conforming to IEC 60947-2 7.5 kA at 415 V AC 50/60 Hz conforming to IEC 60947-2 |
|
suitability for isolation |
Yes conforming to IEC 60947-2
|
|
utilisation category |
Category A
|
|
trip unit name |
TM-D
|
|
trip unit technology |
Thermal-magnetic
|
|
trip unit rating |
60 A at 50 °C
|
|
protection type |
Short-circuit protection
Overload protection |
|
pollution degree |
3 conforming to IEC 60947
|
control type |
Toggle
|
|
---|---|---|
mounting mode |
Fixed
|
|
mounting support |
Backplate
|
|
upside connection |
Front
|
|
downside connection |
Front
|
|
mechanical durability |
8500 cycles
|
|
electrical durability |
Category A: 1500 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2
|
|
connection pitch |
25 mm
|
|
local signalling |
Positive contact indication
|
|
neutral protection setting |
Without protection
|
|
earth-leakage protection |
Without
|
|
height |
130 mm
|
|
width |
100 mm
|
|
depth |
60 mm
|
₦39,999.00
Compare-
CHINT
CHINT Kwh Meter Single
DDSU666 series three phase three wire electronic energy meter (DIN Rail) Summary :
DDSU666 series electronic energy meter is designed for power monitoring and energy measurement such as power system, communication industry, construction industry, etc. to be a new generation of programmable.
DDSU666 series three phase three wire electronic energy meter (DIN Rail)
Summary:
DDSU666 series electronic energy meter is designed for power monitoring and energy measurement such as power system, communication industry, construction industry, etc. to be a new generation of programmable intelligent instrument, integrated with measurement and communication function, mainly used for real-time measurement and display for the electrical parameters such as voltage, current, active power, reactive power, frequency, power factor, energy in the electrical circuit, etc.
1、Main functions and characteristics
◆DIN35mm Standard DIN-Rail, seven modulus with segment LCD display
◆Measurement function: Characterized with measurement for three phase three wire voltage, current, frequency, active power, power factor, active energy and reactive energy
◆communication function: RS485 communication interface, supporting DL/T645-2007 protocol, customizable for MODBUS-RTU protocol
◆Multi-rate function: it supports four rates including top, peak, flat, valley rate.
SKU: n/a -
-
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONS
Easy9 Residual Current Circuit Breaker – 2P – 63 A – 30 mA – AC type – 230 V EZ9R34263
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONSEasy9 Residual Current Circuit Breaker – 2P – 63 A – 30 mA – AC type – 230 V EZ9R34263
Main range of product Easy9product or component type Residual current circuit breaker (RCCB)device short name Easy9 RCCBPoles 2Pneutral position Left[In] rated current 63 Anetwork type ACearth-leakage sensitivity 30 mAearth-leakage protection time delay Instantaneousearth-leakage protection class Type ACrated breaking and making capacity 630 Arated conditional short-circuit current Easy9 MCB: 4500 A 63 AComplementary device location in system Outgoernetwork frequency 50 Hz[Ue] rated operational voltage 230 V AC 50 Hzresidual current tripping technology Voltage dependent[Ui] rated insulation voltage 440 V AC[Uimp] rated impulse withstand voltage 4 kVsurge current 250 Acontact position indicator Yescontrol type Togglemounting mode Clip-onmounting support DIN railcomb busbar and distribution block compatibility Top: YES9 mm pitches 4height 82 mmwidth 36 mmdepth 72 mmcolour Grey (RAL 7035)mechanical durability 5000 cycleselectrical durability AC: 2000 cycles 230 V AC 50 Hzconnections – terminals Tunnel type terminal (top or bottom) 1…25 mm² rigid
Tunnel type terminal (top or bottom) 1…16 mm² flexibletightening torque 2.5 N.m top or bottommarket segment Small commercial
ResidentialSKU: n/a -
ELECTRICAL INDUSTRIAL, Electro, Generators, Generators & Power Solutions
YTO 100kVA Diesel Engine Soundproof Diesel Generator with Stamford Alternator (1year Warranty)
ELECTRICAL INDUSTRIAL, Electro, Generators, Generators & Power SolutionsYTO 100kVA Diesel Engine Soundproof Diesel Generator with Stamford Alternator (1year Warranty)
YTO Diesel Engine Co Ltd specializes in the design and manufacture of diesel generator engines since 1958. YTO has formed international partnerships with world leaders in their respective fields to maintain the latest technologies in their engines and produce a reliable, world-class product. The YTO engines are used internationally in offroad vehicles, tractors, construction machinery, agriculture, combine harvesters and more. The engines are high quality and reliability with a solid history in Africa. These engines include high temperature and low oil, water and fuel protection to protect against engine damage. Generator World is the sole-authorized distributor for YTO Engines in Sub Saharan Africa.
YTO engines are ideal for customers who require reliable performance and reliable power and cover a range of sizes from 10kva- 630kva whether you need prime or standby power- YTO is ready to match your power needs and provide a reliable source of power to ensure your productivity is not impacted. Whether you need a diesel generator for commercial or industrial use, these gensets are the perfect fit for the budget conscious consumer looking for standby power. By choosing one of these generators, you will still enjoy the same build quality and components youʼve come to expect from Generator World.
(2years Warranty of all the component, except the Main Alternator)
SKU: n/a -
Schneider Circuit Breakers, SCHNEIDER SECTIONS
Easy9 miniature circuit breaker- 2P – 32 A – C curve – 6000 A – 230 V EZ9F56232
Schneider Circuit Breakers, SCHNEIDER SECTIONSEasy9 miniature circuit breaker- 2P – 32 A – C curve – 6000 A – 230 V EZ9F56232
Main range Easy9device application Distributionproduct or component type Miniature circuit-breakerdevice short name Easy9 MCBPoles 2Pnumber of protected poles 2[In] rated current 32 Anetwork type ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 10000 A Icn at 220 V AC 50/60 Hz conforming to IEC 60898-1
6000 A Icn at 400 V AC 50/60 Hz conforming to IEC 60898-1suitability for isolation Yes conforming to IEC 60898-1Complementary network frequency 50/60 Hz[Ue] rated operational voltage 220 V AC 50/60 Hz
400 V AC 50/60 Hzmagnetic tripping limit 5…10 x In[Ics] rated service breaking capacity 6 kA 100 % x Icn at 230 V AC 50/60 Hz conforming to IEC 60898-1[Ui] rated insulation voltage 500 V AC 50/60 Hz conforming to IEC 60898-1[Uimp] rated impulse withstand voltage 4 kV conforming to IEC 60898-1contact position indicator Yescontrol type Togglelocal signalling Withoutmounting mode Clip-onmounting support DIN rail9 mm pitches 4height 81 mmwidth 36 mmdepth 66.5 mmcolour Grey (RAL 7035)mechanical durability 10000 cycleselectrical durability 4000 cyclesconnections – terminals Tunnel type terminal (top or bottom) 1…25 mm² flexible
Tunnel type terminal (top or bottom) 1…35 mm² rigidtightening torque 3.5 N.m top or bottomearth-leakage protection WithoutSKU: n/a
There are no reviews yet.