EZC100N4063 Circuit breaker Easypact EZC100N – TMD – 63 A – 4 poles 3d
range of product |
EasyPact
|
|
---|---|---|
product or component type |
Circuit breaker
|
|
device short name |
Easypact EZC100N
|
|
circuit breaker name |
Easypact EZC100N
|
|
device application |
Distribution
|
|
poles description |
4P
|
|
protected poles description |
3t
|
|
network type |
AC
DC |
|
network frequency |
50/60 Hz
|
|
[In] rated current |
100 A at 40 °C
|
|
[Ui] rated insulation voltage |
690 V AC 50/60 Hz conforming to IEC 60947-2
|
|
[Uimp] rated impulse withstand voltage |
6 kV conforming to IEC 60947-2
|
|
[Ue] rated operational voltage |
550 V AC 50/60 Hz conforming to IEC 60947-2
250 V DC conforming to IEC 60947-2 |
|
breaking capacity code |
N
|
|
breaking capacity |
10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
25 kA Icu at 110…130 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2 5 kA Icu at 125 V DC 1P conforming to IEC 60947-2 5 kA Icu at 250 V DC 2P conforming to IEC 60947-2 5 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 415 V AC 50/60 Hz conforming to IEC 60947-2 18 kA Icu at 380…400 V AC 50/60 Hz conforming to IEC 60947-2 |
|
[Ics] rated service breaking capacity |
5 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
2.5 kA at 125 V DC conforming to IEC 60947-2 2.5 kA at 250 V DC conforming to IEC 60947-2 2.5 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2 12.5 kA at 220…240 V AC 50/60 Hz conforming to IEC 60947-2 12.5 kA at 110…130 V AC 50/60 Hz conforming to IEC 60947-2 9 kA at 380…400 V AC 50/60 Hz conforming to IEC 60947-2 7.5 kA at 415 V AC 50/60 Hz conforming to IEC 60947-2 |
|
suitability for isolation |
Yes conforming to IEC 60947-2
|
|
utilisation category |
Category A
|
|
trip unit name |
TM-D
|
|
trip unit technology |
Thermal-magnetic
|
|
trip unit rating |
63 A at 50 °C
|
|
protection type |
Short-circuit protection
Overload protection |
|
pollution degree |
3 conforming to IEC 60947
|
control type |
Toggle
|
|
---|---|---|
mounting mode |
Fixed
|
|
mounting support |
Backplate
|
|
upside connection |
Front
|
|
downside connection |
Front
|
|
mechanical durability |
8500 cycles
|
|
electrical durability |
Category A: 1500 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2
|
|
connection pitch |
25 mm
|
|
local signalling |
Positive contact indication
|
|
neutral protection setting |
Without protection
|
|
earth-leakage protection |
Without
|
|
height |
130 mm
|
|
width |
100 mm
|
|
depth |
60 mm
|
₦43,000.00
Compare-
Electro, SOCKETS & SWITCHES, SWITCHES
BG BRASS GEORGIAN DOUBLE POLE SWITCH WITH NEON 20 AMP
BG NBG31 Brass Georgian Double Pole Switch with Neon 20 Amp
AT A GLANCE…- Top quality Brass finish – lightly lacquered to prevent finger marks
- Matching Brass rocker switch & slim line LED indicator
- No visible plastic around switches
- Specification: 20 amp, double pole (BS EN 60669-1)
- Requires a 25mm metal wall box
- Supplied with colour coded fixing screws
SKU: n/a -
Electro, LED LIGHTS, LIGHTING, OUTDOOR LIGHTS, SOLAR POWERED
PHILIPS ALL-IN-ONE SOLAR BRP110 LED120/757 CN Philip
Electro, LED LIGHTS, LIGHTING, OUTDOOR LIGHTS, SOLAR POWEREDPHILIPS ALL-IN-ONE SOLAR BRP110 LED120/757 CN Philip
Specifications
- General Information
-
Driver included YesOptical cover/lens type PolycarbonateControl interface IR remoteWarranty period 2 yearsMaterial Aluminum - Operating and Electrical
-
Battery type Lithium Ferro PhosphateBattery ampere hour 30 AhBattery voltage 25.6 VBattery charging & discharging cycles 2000Panel type Mono crystallinePanel voltage 36 VPanel peak wattage 120 WCharge controller type MPPTCharge controller wattage 80 W - Controls and Dimming
-
Dimmable YesConfigurability Configurable - Mechanical and Housing
-
Overall length 1321 mmOverall width 525 mmOverall height 161 mm - Approval and Application
-
Ingress protection code IP65 [ Dust penetration-protected, jet-proof]Mech. impact protection code IK08 [ 5 J vandal-protected] - Initial Performance (IEC Compliant)
-
Initial luminous flux (system flux) 12000 lmInit. Corr. Color Temperature 5700 KInit. Color Rendering Index >70 - Application Conditions
-
Ambient temperature range -20 to +50 °CAmbient temperature range for charging 0 to +45 °CAmbient temperature range for discharging (when light is on) -20 to +50 °CAutonomy up to 24 hSolar dimming profile First 2 Hrs – On motion : 100%, without motion :30%Next 3 Hrs – On motion : 60%, without motion :20%Next 6 Hrs On motion : 30%, without motion :10%Rest of the Night: On motion : 50%, without motion :30%Grid connection type Off gridBattery location Inside Luminaire - Product Data
-
Full product code 692382864085900Order product name BRP110 LED120/757 CNEAN/UPC – Product 6923828640859Order code 911401864181Numerator – Quantity Per Pack 1Numerator – Packs per outer box 1Material Nr. (12NC) 911401864181Net Weight (Piece) 28.300 kg
SKU: n/a -
ELECTRICAL INDUSTRIAL, TRANSFORMER
BETA 750KVA/33/0.415V COPPER/COPPER WINDING TRANSFORMER
Produced within a power range between 10 – 100.000 kVA , up to 170 kV high voltage level, three phase or single phase, oil immersed, ONAN, ONAF, OFWF, with Off-Load or On-Load Tap Changer, used both external and internal.
Dimensions of transformer conservator are determined and designed after several heat calculations of the oil stored in expansion tank and oil level changes by heat.
Being open to atmosphere, oil pressure changes continuously in Conservator Type Transformers due to thermal effects and exchange of air is dehumidified via air breather silicagel.SKU: n/a -
CABLE AND CABLE MANAGEMENT, Electro, SINGLE CORE WIRE
Doncaster Cables 4mm Single Core – Black
Product Description
Manufactured to BS 6004:2012 Table 3
Annealed Stranded Copper Conductor / PVC Insulated / PVC Sheathed. 300/500V
Designed for use in light industrial and domestic wiring. These cables are particularly suited for installation as meter tails and are intended for fixed installation in dry or damp premises.
These cables can be installed in conduit, in cable trunking and in cable ducting. Or where there is deemed little risk of mechanical damage these cables can be clipped direct, on cable tray, embedded or in free air. These cables are not intended to be laid underground.
Product Details
Harmonisation Code Nominal Cross Sectional Area of Conductor (mm2) Nominal Stranding of Conductor (mm) Nominal Radial Thickness of insulation (mm) Nominal Radial Thickness of sheath (mm) Overall Diameter Lower Limit (mm) Overall Diameter Upper Limit (mm) Approximate Weight(kg/km) National Type 1.0 1 / 1.13 0.6 0.8 3.8 4.5 26 National Type 1.5 1 / 1.38 0.7 0.8 4.2 4.9 35 National Type 2.5 1 / 1.78 0.8 0.8 4.8 5.8 55 National Type 4.0 7 / 0.85 0.8 0.9 5.4 6.8 75 National Type 6.0 7 / 1.04 0.8 0.9 6.0 7.4 95 National Type 10.0 7 / 1.35 1.0 0.9 7.2 8.8 155 National Type 16.0 7 / 1.70 1.0 1.0 8.4 10.5 225 National Type 25.0 7 / 2.14 1.2 1.1 10.0 12.5 340 National Type 35.0 7 / 2.52 1.2 1.1 11.0 13.5 445 SKU: n/a
There are no reviews yet.