EZC250N4200 Circuit breaker Easypact EZC250N – TMD – 200 A – 4 poles 3d
range of product |
EasyPact
|
|
---|---|---|
product or component type |
Circuit breaker
|
|
device short name |
Easypact EZC250N
|
|
circuit breaker name |
Easypact EZC250N
|
|
device application |
Distribution
|
|
poles description |
4P
|
|
protected poles description |
3t
|
|
network type |
DC
AC |
|
network frequency |
50/60 Hz
|
|
[In] rated current |
250 A at 40 °C
|
|
[Ui] rated insulation voltage |
690 V AC 50/60 Hz conforming to IEC 60947-2
|
|
[Uimp] rated impulse withstand voltage |
6 kV conforming to IEC 60947-2
|
|
[Ue] rated operational voltage |
550 V AC 50/60 Hz conforming to IEC 60947-2
250 V DC conforming to IEC 60947-2 |
|
breaking capacity code |
N
|
|
breaking capacity |
20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 125 V DC 1P conforming to IEC 60947-2 20 kA Icu at 250 V DC 2P conforming to IEC 60947-2 8 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 380…415 V AC 50/60 Hz conforming to IEC 60947-2 |
|
[Ics] rated service breaking capacity |
10 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
25 kA at 220…240 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 125 V DC conforming to IEC 60947-2 10 kA at 250 V DC conforming to IEC 60947-2 4 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2 12.5 kA at 380…415 V AC 50/60 Hz conforming to IEC 60947-2 |
|
suitability for isolation |
Yes conforming to IEC 60947-2
|
|
utilisation category |
Category A
|
|
trip unit name |
TM-D
|
|
trip unit technology |
Thermal-magnetic
|
|
trip unit rating |
200 A at 50 °C
|
|
protection type |
Short-circuit protection
Overload protection |
|
pollution degree |
3 conforming to IEC 60947
|
control type |
Toggle
|
|
---|---|---|
mounting mode |
Fixed
|
|
mounting support |
Backplate
|
|
upside connection |
Front
|
|
downside connection |
Front
|
|
mechanical durability |
10000 cycles
|
|
electrical durability |
Category A: 5000 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2
|
|
connection pitch |
35 mm
|
|
local signalling |
Positive contact indication
|
|
neutral protection setting |
Without protection
|
|
earth-leakage protection |
Without
|
|
height |
165 mm
|
|
width |
140 mm
|
|
depth |
60 mm
|
₦99,999.00
Compare-
CIRCUIT BREAKERS
Circuit breaker Easypact EZC100H – TMD – 63 A – 4 poles 3d
Main range of product EasyPactproduct or component type Circuit breakerdevice short name Easypact EZC100Hcircuit breaker name Easypact EZC100Hdevice application Distributionpoles description 4Pprotected poles description 3tnetwork type AC
DCnetwork frequency 50/60 Hz[In] rated current 100 A at 40 °C[Ui] rated insulation voltage 690 V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947-2[Ue] rated operational voltage 550 V AC 50/60 Hz conforming to IEC 60947-2
250 V DC conforming to IEC 60947-2breaking capacity code Hbreaking capacity 10 kA Icu at 125 V DC 1P conforming to IEC 60947-2
10 kA Icu at 250 V DC 2P conforming to IEC 60947-2
10 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2
100 kA Icu at 110…130 V AC 50/60 Hz conforming to IEC 60947-2
20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
30 kA Icu at 380…400 V AC 50/60 Hz conforming to IEC 60947-2
30 kA Icu at 415 V AC 50/60 Hz conforming to IEC 60947-2[Ics] rated service breaking capacity 5 kA at 125 V DC conforming to IEC 60947-2
5 kA at 250 V DC conforming to IEC 60947-2
5 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
2.5 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2
15 kA at 380…400 V AC 50/60 Hz conforming to IEC 60947-2
25 kA at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
50 kA at 110…130 V AC 50/60 Hz conforming to IEC 60947-2
7.5 kA at 415 V AC 50/60 Hz conforming to IEC 60947-2suitability for isolation Yes conforming to IEC 60947-2utilisation category Category Atrip unit name TM-Dtrip unit technology Thermal-magnetictrip unit rating 63 A at 50 °Cprotection type Overload protection
Short-circuit protectionpollution degree 3 conforming to IEC 60947Complementary control type Togglemounting mode Fixedmounting support Backplateupside connection Frontdownside connection Frontmechanical durability 8500 cycleselectrical durability Category A: 1500 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2connection pitch 25 mmlocal signalling Positive contact indicationneutral protection setting Without protectionearth-leakage protection Withoutheight 130 mmwidth 100 mmdepth 60 mmSKU: n/a -
ACCESSORIES, ELECTRICAL INDUSTRIAL
Xpelair 12inches Window Mounted Extractor Fan
Extractor Fan
Suitable for both single and double glazed windows
Feature a pullcord for easy on/off operation.
Shutters can be set partially open to provide background trickle ventilation
Motor isolated when the cover is removed
Brilliant white interior and brown exterior grille
Quick release front cover and impeller
Auto shutter model has a thermo actuator opening/closing operation which is ideal for use with a remote humidistat. Actuator time delay 30s on opening, 3min. on closing
On-site warranty
230 Vac mains powered.SKU: Xpelair 90800AW Window Mounted Extractor Fan-1-2 -
LIGHT SWITCHES & ELECTRICAL SOCKETS
Lisse – Switched Socket – 2 gang – 13A Polished Chrome with white Interior GGBL3020WPC
LIGHT SWITCHES & ELECTRICAL SOCKETSLisse – Switched Socket – 2 gang – 13A Polished Chrome with white Interior GGBL3020WPC
Main range Lisseaesthetic name Screwless decoproduct or component type Switched socketdevice presentation Complete productoutlet standard Britishquantity per set Set of 5type of packing BoxComplementary switch function 1-poleactuator Rockernumber of gangs 2 gangsfixing mode Concealed screwsconnections – terminals Screw terminalsmaterial Stainless steeltype of installation Indoordepth 36 mmwidth 148 mmheight 87 mmnet weight 0.198 kgSKU: n/a -
Schneider Circuit Breakers, SCHNEIDER SECTIONS
Acti9 iC60N 2P 4A C Miniature Circuit breaker A9F44204
Schneider Circuit Breakers, SCHNEIDER SECTIONSActi9 iC60N 2P 4A C Miniature Circuit breaker A9F44204
Main range Acti 9product name Disbo iC60product or component type Miniature circuit-breakerdevice short name IC60Npoles description 2Pnumber of protected poles 2[In] rated current 4 Anetwork type ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 50 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
50 kA Icu at 12…133 V AC 50/60 Hz conforming to EN/IEC 60947-2
50 kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2
25 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2
6 kA Icu at 100…133 V DC conforming to EN/IEC 60947-2
6000 A Icn at 415 V AC 50/60 Hz conforming to EN/IEC 60898-1utilisation category Category A conforming to EN/IEC 60947-2Complementary network frequency 50/60 Hz[Ue] rated operational voltage 440 V AC 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 50 kA 100 % conforming to EN/IEC 60947-2 – 220…240 V AC 50/60 Hz
50 kA 100 % conforming to EN/IEC 60947-2 – 12…133 V AC 50/60 Hz
50 kA 100 % conforming to EN/IEC 60947-2 – 380…415 V AC 50/60 Hz
25 kA 100 % conforming to EN/IEC 60947-2 – 440 V AC 50/60 Hz
6000 A 100 % conforming to EN/IEC 60898-1 – 415 V AC 50/60 Hz
6 kA 100 % conforming to EN/IEC 60947-2 – 100…133 V DClimitation class 3 conforming to EN/IEC 60947-2[Ui] rated insulation voltage 500 V AC 50/60 Hz[Uimp] rated impulse withstand voltage 6 kV conforming to EN/IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Clip-onmounting support Rail9 mm pitches 4height 85 mmwidth 36 mmdepth 78.5 mmnet weight 0.25 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesprovision for padlocking Padlockableconnections – terminals Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 2 N.m top or bottomearth-leakage protection Separate blockSKU: n/a -
CHINT
CHINT NXB63 Miniature Circuit Breaker MCB
Protection of circuits against short-circuit currents, protection of circuits against overload currents, switch, isolation, NXB63 circuit-breakers are used in domestic installation, as well as in commercial and industry electrical distribution systems.
DESCRIPTION
- Rated current from : 6A to 63A
- Icu 6kA
- Rated Voltage Ue (V) : 230/400 ~ 240/415
- Standard: IEC/EN 60898
- Rate Frequency : 50/60Hz
SKU: n/a