IC60H – miniature circuit breaker – 1P – 32A – C curve A9F84132
device application |
Distribution
|
|
---|---|---|
range |
Acti 9
|
|
product name |
Acti 9 iC60
|
|
product or component type |
Miniature circuit-breaker
|
|
device short name |
IC60H
|
|
poles description |
1P
|
|
number of protected poles |
1
|
|
[In] rated current |
32 A
|
|
network type |
DC
AC |
|
trip unit technology |
Thermal-magnetic
|
|
curve code |
C
|
|
breaking capacity |
10000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
15 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2 42 kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2 30 kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 60…72 V DC conforming to EN/IEC 60947-2 20 kA Icu at 12…60 V DC conforming to EN/IEC 60947-2 |
|
utilisation category |
Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2 |
|
suitability for isolation |
Yes conforming to EN 60898-1
Yes conforming to EN 60947-2 Yes conforming to IEC 60898-1 Yes conforming to IEC 60947-2 |
|
standards |
IEC 60947-2
IEC 60898-1 EN 60898-1 EN 60947-2 |
network frequency |
50/60 Hz
|
|
---|---|---|
magnetic tripping limit |
8 x In +/- 20 %
|
|
[Ics] rated service breaking capacity |
21 kA 50 % conforming to EN 60947-2 – 12…60 V AC 50/60 Hz
7.5 kA 50 % conforming to EN 60947-2 – 220…240 V AC 50/60 Hz 21 kA 50 % conforming to IEC 60947-2 – 12…60 V AC 50/60 Hz 7.5 kA 50 % conforming to IEC 60947-2 – 220…240 V AC 50/60 Hz 7500 A 75 % conforming to EN 60898-1 – 230 V AC 50/60 Hz 7500 A 75 % conforming to IEC 60898-1 – 230 V AC 50/60 Hz 15 kA 50 % conforming to IEC 60947-2 – 100…133 V AC 50/60 Hz 15 kA 50 % conforming to EN 60947-2 – 100…133 V AC 50/60 Hz 15 kA 100 % conforming to EN 60947-2 – 72 V DC 15 kA 100 % conforming to IEC 60947-2 – 72 V DC 20 kA 100 % conforming to EN 60947-2 – 12…60 V DC 20 kA 100 % conforming to IEC 60947-2 – 12…60 V DC |
|
limitation class |
3 conforming to EN 60898-1
3 conforming to IEC 60898-1 |
|
[Ui] rated insulation voltage |
500 V AC 50/60 Hz conforming to EN 60947-2
500 V AC 50/60 Hz conforming to IEC 60947-2 |
|
[Uimp] rated impulse withstand voltage |
6 kV conforming to EN 60947-2
6 kV conforming to IEC 60947-2 |
|
contact position indicator |
Yes
|
|
control type |
Toggle
|
|
local signalling |
Trip indicator
|
|
mounting mode |
Fixed
|
|
mounting support |
DIN rail
|
|
comb busbar and distribution block compatibility |
Top or bottom: YES
|
|
9 mm pitches |
2
|
|
height |
85 mm
|
|
width |
18 mm
|
|
depth |
78.5 mm
|
|
net weight |
0.215 kg
|
|
colour |
White
|
|
mechanical durability |
20000 cycles
|
|
electrical durability |
10000 cycles
|
|
connections – terminals |
Single terminal (top or bottom) 1…35 mm² rigid
Single terminal (top or bottom) 1…25 mm² flexible |
|
wire stripping length |
14 mm for top or bottom connection
|
|
tightening torque |
3.5 N.m top or bottom
|
|
earth-leakage protection |
Without
|
₦3,999.00
Compare-
COOKER UNIT, Electro, SOCKETS & SWITCHES
BG 45A DP Cooker Control Unit with 13A Socket and Power Indicators
COOKER UNIT, Electro, SOCKETS & SWITCHESBG 45A DP Cooker Control Unit with 13A Socket and Power Indicators
Product Information
- Double Pole switches manufactured to BS EN 60669-1
- Cooker Control Units manufactured to BS4177
- Minimum mounting box depth 47mm
- L&N terminal capacity 4 x 4.0mm², 3 x 6.0mm² & 1 x 16.0mm²
- E terminal capacity 3 x 4.00mm², 6 x 6.0mm² & 1 x 16.0mm²
SKU: n/a -
CABLE AND CABLE MANAGEMENT, Electro, SINGLE CORE WIRE
KABLEMETAL 25mm Single Core – Black
We offer other range of products across various categories and sub categories and our services are Procurement, installation and Management etc of electrical products, should you have any inquiry we are always here to do our best to promptly answer you.
SKU: n/a -
ELECTRICAL INDUSTRIAL, Electro, TRANSFORMER, Uncategorized
ABB 1000KVA 11/400KV Distribution Transformer
ELECTRICAL INDUSTRIAL, Electro, TRANSFORMER, UncategorizedABB 1000KVA 11/400KV Distribution Transformer
Distribution transformers are typically oil-immersed and suitable for pole-, pad- or ground-mounting. They represent an economical option for certain networks, particularly those with low population densities.
Depending upon requirements, transformers may be connected between two phases of a three-phase system (two high voltage bushings) or from one phase to ground (single high voltage bushing).
The units are suitable for residential overhead distribution loads, as well as light commercial or industrial loads and diversified power applications.
Product scope
- Primary voltage: up to 36 kV
- Typical fluid: mineral oil
SKU: n/a
There are no reviews yet.