IC60H – miniature circuit breaker – 2P – 25A – C curve A9F84225
device application |
Distribution
|
|
---|---|---|
range |
Acti 9
|
|
product name |
Acti 9 iC60
|
|
product or component type |
Miniature circuit-breaker
|
|
device short name |
IC60H
|
|
poles description |
2P
|
|
number of protected poles |
2
|
|
[In] rated current |
25 A
|
|
network type |
AC
DC |
|
trip unit technology |
Thermal-magnetic
|
|
curve code |
C
|
|
breaking capacity |
10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
42 kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2 30 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at <= 125 V DC conforming to EN/IEC 60947-2 42 kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
|
utilisation category |
Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2 |
|
suitability for isolation |
Yes conforming to EN 60898-1
Yes conforming to EN 60947-2 Yes conforming to IEC 60898-1 Yes conforming to IEC 60947-2 |
|
standards |
EN 60898-1
EN 60947-2 IEC 60898-1 IEC 60947-2 |
network frequency |
50/60 Hz
|
|
---|---|---|
magnetic tripping limit |
8 x In +/- 20 %
|
|
[Ics] rated service breaking capacity |
15 kA 50 % conforming to EN 60947-2 – 220…240 V AC 50/60 Hz
7.5 kA 50 % conforming to EN 60947-2 – 380…415 V AC 50/60 Hz 5 kA 50 % conforming to EN 60947-2 – 440 V AC 50/60 Hz 15 kA 50 % conforming to IEC 60947-2 – 220…240 V AC 50/60 Hz 7.5 kA 50 % conforming to IEC 60947-2 – 380…415 V AC 50/60 Hz 5 kA 50 % conforming to IEC 60947-2 – 440 V AC 50/60 Hz 7500 A 75 % conforming to EN 60898-1 – 400 V AC 50/60 Hz 7500 A 75 % conforming to IEC 60898-1 – 400 V AC 50/60 Hz 21 kA 50 % conforming to IEC 60947-2 – 12…133 V AC 50/60 Hz 21 kA 50 % conforming to EN 60947-2 – 12…133 V AC 50/60 Hz 15 kA 100 % conforming to IEC 60947-2 – 72…125 V DC 15 kA 100 % conforming to EN 60947-2 – 72…125 V DC |
|
limitation class |
3 conforming to EN 60898-1
3 conforming to IEC 60898-1 |
|
[Ui] rated insulation voltage |
500 V AC 50/60 Hz conforming to EN 60947-2
500 V AC 50/60 Hz conforming to IEC 60947-2 |
|
[Uimp] rated impulse withstand voltage |
6 kV conforming to EN 60947-2
6 kV conforming to IEC 60947-2 |
|
contact position indicator |
Yes
|
|
control type |
Toggle
|
|
local signalling |
Trip indicator
|
|
mounting mode |
Fixed
|
|
mounting support |
DIN rail
|
|
comb busbar and distribution block compatibility |
Top or bottom: YES
|
|
9 mm pitches |
4
|
|
height |
85 mm
|
|
width |
36 mm
|
|
depth |
78.5 mm
|
|
net weight |
0.25 kg
|
|
colour |
White
|
|
mechanical durability |
20000 cycles
|
|
electrical durability |
10000 cycles
|
|
connections – terminals |
Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexible |
|
wire stripping length |
14 mm for top or bottom connection
|
|
tightening torque |
2 N.m top or bottom
|
|
earth-leakage protection |
Separate block
|
₦7,999.00
Compare-
SCHNEIDER SECTIONS, Schneider Thorsman Testmeters
Thorsman IR Thermometer 520°C IMT23107
Main range Thorsmanproduct or component type Thermometersupply battery 9 Vtechnology type LaserComplementary display type Handheld infrared thermometer: backlit LCDmeasurement temperature Handheld infrared thermometer: -20…520 °Clanguage Swedish
English
Danish
Finnish
Norwegianheight 180 mmwidth 85 mmdepth 50 mmnet weight 150 g without batterySKU: n/a -
ELECTRICAL INDUSTRIAL, TRANSFORMER
BETA 300KVA/33/0.415V COPPER/COPPER WINDING TRANSFORMER
Produced within a power range between 10 – 100.000 kVA , up to 170 kV high voltage level, three phase or single phase, oil immersed, ONAN, ONAF, OFWF, with Off-Load or On-Load Tap Changer, used both external and internal.
Dimensions of transformer conservator are determined and designed after several heat calculations of the oil stored in expansion tank and oil level changes by heat.
Being open to atmosphere, oil pressure changes continuously in Conservator Type Transformers due to thermal effects and exchange of air is dehumidified via air breather silicagel.SKU: n/a -
Electro, Schneider "Consort Dado" Trunking, SCHNEIDER SECTIONS
DPI3W Mita – Cableline 50 – internal corner – 180W x 52 mm DPI3W
Electro, Schneider "Consort Dado" Trunking, SCHNEIDER SECTIONSDPI3W Mita – Cableline 50 – internal corner – 180W x 52 mm DPI3W
Main range of product Mitaproduct name Cableline 50product or component type Internal cornercolour tint Whitequantity per set Set of 1Complementary fixing mode By screws extra securitymaterial with surface finish UPVC (unplasticized polyvinyl chloride)SKU: n/a -
Schneider Circuit Breakers, SCHNEIDER SECTIONS
Miniature circuit-breaker, Acti9 iC60H, 2P, 6 A, C curve, 10000 A (IEC 60898-1), 15 kA (IEC 60947-2) A9F84206
Schneider Circuit Breakers, SCHNEIDER SECTIONSMiniature circuit-breaker, Acti9 iC60H, 2P, 6 A, C curve, 10000 A (IEC 60898-1), 15 kA (IEC 60947-2) A9F84206
Main device application Distributionrange Acti 9product name Acti 9 iC60product or component type Miniature circuit-breakerdevice short name IC60Hpoles description 2Pnumber of protected poles 2[In] rated current 6 Anetwork type DC
ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
42 kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2
10 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2
15 kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2
30 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
15 kA Icu at <= 125 V DC conforming to EN/IEC 60947-2
42 kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2utilisation category Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2suitability for isolation Yes conforming to EN 60898-1
Yes conforming to EN 60947-2
Yes conforming to IEC 60898-1
Yes conforming to IEC 60947-2standards IEC 60947-2
IEC 60898-1
EN 60947-2
EN 60898-1Complementary network frequency 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 15 kA 50 % conforming to EN 60947-2 – 220…240 V AC 50/60 Hz
7.5 kA 50 % conforming to EN 60947-2 – 380…415 V AC 50/60 Hz
5 kA 50 % conforming to EN 60947-2 – 440 V AC 50/60 Hz
15 kA 50 % conforming to IEC 60947-2 – 220…240 V AC 50/60 Hz
7.5 kA 50 % conforming to IEC 60947-2 – 380…415 V AC 50/60 Hz
5 kA 50 % conforming to IEC 60947-2 – 440 V AC 50/60 Hz
7500 A 75 % conforming to EN 60898-1 – 400 V AC 50/60 Hz
7500 A 75 % conforming to IEC 60898-1 – 400 V AC 50/60 Hz
21 kA 50 % conforming to IEC 60947-2 – 12…133 V AC 50/60 Hz
21 kA 50 % conforming to EN 60947-2 – 12…133 V AC 50/60 Hz
15 kA 100 % conforming to IEC 60947-2 – 72…125 V DC
15 kA 100 % conforming to EN 60947-2 – 72…125 V DClimitation class 3 conforming to EN 60898-1
3 conforming to IEC 60898-1[Ui] rated insulation voltage 500 V AC 50/60 Hz conforming to EN 60947-2
500 V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6 kV conforming to EN 60947-2
6 kV conforming to IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Fixedmounting support DIN railcomb busbar and distribution block compatibility Top or bottom: YES9 mm pitches 4height 85 mmwidth 36 mmdepth 78.5 mmnet weight 0.25 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesconnections – terminals Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 2 N.m top or bottomearth-leakage protection Separate blockSKU: n/a -
ACCESSORIES, CIRCUIT BREAKERS, DISTRIBUTION BOARDS, ELECTRICAL INDUSTRIAL, Electro
ABB Contactor AF400-30-22 100-250V
ACCESSORIES, CIRCUIT BREAKERS, DISTRIBUTION BOARDS, ELECTRICAL INDUSTRIAL, ElectroABB Contactor AF400-30-22 100-250V
A 3-phase Contactor suitable for various applications such as Motor starting, Isolation, By-pass and Distribution application up to max 1000 V. Operated with wide control voltage range 100-250 V, AC/DC
Categories
- Products » Low Voltage Products and Systems » Control Products » Contactors » Block Contactors
SKU: n/a -
Schneider Circuit Breakers, SCHNEIDER SECTIONS
Easy9 miniature circuit breaker- 3P – 40 A – C curve – 6000 A – 400 V EZ9F56340
Schneider Circuit Breakers, SCHNEIDER SECTIONSEasy9 miniature circuit breaker- 3P – 40 A – C curve – 6000 A – 400 V EZ9F56340
Main range Easy9device application Distributionproduct or component type Miniature circuit-breakerdevice short name Easy9 MCBPoles 3Pnumber of protected poles 3[In] rated current 40 Anetwork type ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 10000 A Icn at 220 V AC 50/60 Hz conforming to IEC 60898-1
6000 A Icn at 400 V AC 50/60 Hz conforming to IEC 60898-1suitability for isolation Yes conforming to IEC 60898-1Complementary network frequency 50/60 Hz[Ue] rated operational voltage 220 V AC 50/60 Hz
400 V AC 50/60 Hzmagnetic tripping limit 5…10 x In[Ics] rated service breaking capacity 6 kA 100 % x Icn at 400 V AC 50/60 Hz conforming to IEC 60898-1[Ui] rated insulation voltage 500 V AC 50/60 Hz conforming to IEC 60898-1[Uimp] rated impulse withstand voltage 4 kV conforming to IEC 60898-1contact position indicator Yescontrol type Togglelocal signalling Withoutmounting mode Clip-onmounting support DIN rail9 mm pitches 6height 81 mmwidth 54 mmdepth 66.5 mmcolour Grey (RAL 7035)mechanical durability 10000 cycleselectrical durability 4000 cyclesconnections – terminals Tunnel type terminal (top or bottom) 1…25 mm² flexible
Tunnel type terminal (top or bottom) 1…35 mm² rigidtightening torque 3.5 N.m top or bottomearth-leakage protection WithoutSKU: n/a
There are no reviews yet.