IC60N – miniature circuit breaker – 3P – 63A – C curve
device application |
Distribution
|
|
---|---|---|
range |
Acti 9
|
|
product name |
Acti 9 iC60
|
|
product or component type |
Miniature circuit-breaker
|
|
device short name |
IC60N
|
|
poles description |
3P
|
|
number of protected poles |
3
|
|
[In] rated current |
63Â A
|
|
network type |
DC
AC |
|
trip unit technology |
Thermal-magnetic
|
|
curve code |
C
|
|
breaking capacity |
6000Â A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
36Â kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2 10Â kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2 20Â kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2 6Â kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 36Â kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2 10Â kA Icu at <= 180 V DC conforming to EN/IEC 60947-2 |
|
utilisation category |
Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2 |
|
suitability for isolation |
Yes conforming to EN 60898-1
Yes conforming to EN 60947-2 Yes conforming to IEC 60898-1 Yes conforming to IEC 60947-2 |
|
standards |
EN 60898-1
EN 60947-2 IEC 60898-1 IEC 60947-2 |
network frequency |
50/60 Hz
|
|
---|---|---|
magnetic tripping limit |
8 x In +/- 20 %
|
|
[Ics] rated service breaking capacity |
15Â kA 75Â % conforming to EN 60947-2 – 220…240 V AC 50/60 Hz
7.5Â kA 75Â % conforming to EN 60947-2 – 380…415 V AC 50/60 Hz 4.5Â kA 75Â % conforming to EN 60947-2 – 440 V AC 50/60 Hz 15Â kA 75Â % conforming to IEC 60947-2 – 220…240 V AC 50/60 Hz 7.5Â kA 75Â % conforming to IEC 60947-2 – 380…415 V AC 50/60 Hz 4.5Â kA 75Â % conforming to IEC 60947-2 – 440 V AC 50/60 Hz 27Â kA 75Â % conforming to IEC 60947-2 – 12…133 V AC 50/60 Hz 27Â kA 75Â % conforming to EN 60947-2 – 12…133 V AC 50/60 Hz 6000Â A 100Â % conforming to EN 60898-1 – 400 V AC 50/60 Hz 6000Â A 100Â % conforming to IEC 60898-1 – 400 V AC 50/60 Hz 10Â kA 100Â % conforming to IEC 60947-2 – 125…180 V DC 10Â kA 100Â % conforming to EN 60947-2 – 125…180 V DC |
|
[Ui] rated insulation voltage |
500Â V AC 50/60 Hz conforming to EN 60947-2
500Â V AC 50/60 Hz conforming to IEC 60947-2 |
|
[Uimp] rated impulse withstand voltage |
6Â kV conforming to EN 60947-2
6Â kV conforming to IEC 60947-2 |
|
contact position indicator |
Yes
|
|
control type |
Toggle
|
|
local signalling |
Trip indicator
|
|
mounting mode |
Fixed
|
|
mounting support |
DIN rail
|
|
comb busbar and distribution block compatibility |
Top or bottom: YES
|
|
9 mm pitches |
6
|
|
height |
85Â mm
|
|
width |
54Â mm
|
|
depth |
78.5Â mm
|
|
net weight |
0.375Â kg
|
|
colour |
White
|
|
mechanical durability |
20000Â cycles
|
|
electrical durability |
10000Â cycles
|
|
connections – terminals |
Single terminal (top or bottom) 1…35 mm² rigid
Single terminal (top or bottom) 1…25 mm² flexible |
|
wire stripping length |
14Â mm for top or bottom connection
|
|
tightening torque |
3.5Â N.m top or bottom
|
|
earth-leakage protection |
Separate block
|
₦16,000.00
Compare-
Schneider Circuit Breakers, SCHNEIDER SECTIONS
Acti9 iC60N 1P 63A C Miniature Circuit breaker A9F44163
Schneider Circuit Breakers, SCHNEIDER SECTIONSActi9 iC60N 1P 63A C Miniature Circuit breaker A9F44163
Main range Acti 9product name Disbo iC60product or component type Miniature circuit-breakerdevice short name IC60Npoles description 1Pnumber of protected poles 1[In] rated current 63Â Anetwork type ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 15Â kA Icu at 12…48 V DC conforming to EN/IEC 60947-2
6Â kA Icu at 72 V DC conforming to EN/IEC 60947-2
6000Â A Icn at 240 V AC 50/60 Hz conforming to EN/IEC 60898-1
36Â kA Icu at 10…60 V AC 50/60 Hz conforming to EN/IEC 60947-2
20Â kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2
10Â kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2utilisation category Category A conforming to EN/IEC 60947-2Complementary network frequency 50/60 Hz[Ue] rated operational voltage 240 V AC 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 27Â kA 75Â % conforming to EN/IEC 60947-2 – 10…60 V AC 50/60 Hz
15Â kA 75Â % conforming to EN/IEC 60947-2 – 100…133 V AC 50/60 Hz
7.5Â kA 75Â % conforming to EN/IEC 60947-2 – 220…240 V AC 50/60 Hz
6000Â A 100Â % conforming to EN/IEC 60898-1 – 240 V AC 50/60 Hz
15Â kA 100Â % conforming to EN/IEC 60947-2 – 12…48 V DC
6 kA 100 % conforming to EN/IEC 60947-2 – 72 V DClimitation class 3 conforming to EN/IEC 60947-2[Ui] rated insulation voltage 500 V AC 50/60 Hz[Uimp] rated impulse withstand voltage 6 kV conforming to EN/IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Clip-onmounting support Rail9 mm pitches 2height 85 mmwidth 18 mmdepth 78.5 mmnet weight 0.125 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesprovision for padlocking Padlockableconnections – terminals Single terminal (top or bottom) 1…35 mm² rigid
Single terminal (top or bottom) 1…25 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 3.5 N.m top or bottomearth-leakage protection Separate blockSKU: n/a -
ELECTRICAL INDUSTRIAL, Electro, Generators, Generators & Power Solutions
YTO Diesel Engine Soundproof Diesel Generator with Stamford Alternator 15kVA ((1year Warranty)
ELECTRICAL INDUSTRIAL, Electro, Generators, Generators & Power SolutionsYTO Diesel Engine Soundproof Diesel Generator with Stamford Alternator 15kVA ((1year Warranty)
YTO Diesel Engine Co Ltd specializes in the design and manufacture of diesel generator engines since 1958. YTO has formed international partnerships with world leaders in their respective fields to maintain the latest technologies in their engines and produce a reliable, world-class product. The YTO engines are used internationally in offroad vehicles, tractors, construction machinery, agriculture, combine harvesters and more. The engines are high quality and reliability with a solid history in Africa. These engines include high temperature and low oil, water and fuel protection to protect against engine damage. Generator World is the sole-authorized distributor for YTO Engines in Sub Saharan Africa.
YTO engines are ideal for customers who require reliable performance and reliable power and cover a range of sizes from 10kva- 630kva whether you need prime or standby power- YTO is ready to match your power needs and provide a reliable source of power to ensure your productivity is not impacted. Whether you need a diesel generator for commercial or industrial use, these gensets are the perfect fit for the budget conscious consumer looking for standby power. By choosing one of these generators, you will still enjoy the same build quality and components youʼve come to expect from Generator World.
(2years Warranty of all the component, except the Main Alternator)
SKU: n/a -
ACCESSORIES, CIRCUIT BREAKERS, DISTRIBUTION BOARDS, ELECTRICAL INDUSTRIAL
Contactor AF400-30-11 100-250 1SFL577001R7011
ACCESSORIES, CIRCUIT BREAKERS, DISTRIBUTION BOARDS, ELECTRICAL INDUSTRIALContactor AF400-30-11 100-250 1SFL577001R7011
Long Description:
A 3-phase Contactor suitable for various applications such as Motor starting, Isolation, By-pass and Distribution application up to max 1000 V. Operated with wide control voltage range 100-250 V, AC/DC
Categories
- Products » Low Voltage Products and Systems » Control Products » Contactors » Block Contactors
- Parts & Services » Drives » Low voltage AC drives » Legacy AC drives » MoCon
SKU: n/a -
Schneider Circuit Breakers, SCHNEIDER SECTIONS
Miniature circuit-breaker, Acti9 iC60H, 2P, 40 A, C curve, 10000 A (IEC 60898-1), 15 kA (IEC 60947-2) A9F84240
Schneider Circuit Breakers, SCHNEIDER SECTIONSMiniature circuit-breaker, Acti9 iC60H, 2P, 40 A, C curve, 10000 A (IEC 60898-1), 15 kA (IEC 60947-2) A9F84240
Main device application Distributionrange Acti 9product name Acti 9 iC60product or component type Miniature circuit-breakerdevice short name IC60Hpoles description 2Pnumber of protected poles 2[In] rated current 40Â Anetwork type AC
DCtrip unit technology Thermal-magneticcurve code Cbreaking capacity 10000Â A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
42Â kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2
10Â kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2
15Â kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2
30Â kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
15Â kA Icu at <= 125 V DC conforming to EN/IEC 60947-2
42Â kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2utilisation category Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2suitability for isolation Yes conforming to EN 60898-1
Yes conforming to EN 60947-2
Yes conforming to IEC 60898-1
Yes conforming to IEC 60947-2standards EN 60898-1
EN 60947-2
IEC 60898-1
IEC 60947-2Complementary network frequency 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 15Â kA 50Â % conforming to EN 60947-2 – 220…240 V AC 50/60 Hz
7.5Â kA 50Â % conforming to EN 60947-2 – 380…415 V AC 50/60 Hz
5Â kA 50Â % conforming to EN 60947-2 – 440 V AC 50/60 Hz
15Â kA 50Â % conforming to IEC 60947-2 – 220…240 V AC 50/60 Hz
7.5Â kA 50Â % conforming to IEC 60947-2 – 380…415 V AC 50/60 Hz
5Â kA 50Â % conforming to IEC 60947-2 – 440 V AC 50/60 Hz
7500Â A 75Â % conforming to EN 60898-1 – 400 V AC 50/60 Hz
7500Â A 75Â % conforming to IEC 60898-1 – 400 V AC 50/60 Hz
21Â kA 50Â % conforming to IEC 60947-2 – 12…133 V AC 50/60 Hz
21Â kA 50Â % conforming to EN 60947-2 – 12…133 V AC 50/60 Hz
15Â kA 100Â % conforming to IEC 60947-2 – 72…125 V DC
15Â kA 100Â % conforming to EN 60947-2 – 72…125 V DClimitation class 3 conforming to EN 60898-1
3 conforming to IEC 60898-1[Ui] rated insulation voltage 500Â V AC 50/60 Hz conforming to EN 60947-2
500Â V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6Â kV conforming to EN 60947-2
6 kV conforming to IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Fixedmounting support DIN railcomb busbar and distribution block compatibility Top or bottom: YES9 mm pitches 4height 85 mmwidth 36 mmdepth 78.5 mmnet weight 0.25 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesconnections – terminals Single terminal (top or bottom) 1…35 mm² rigid
Single terminal (top or bottom) 1…25 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 3.5 N.m top or bottomearth-leakage protection Separate blockSKU: n/a -
CABLE AND CABLE MANAGEMENT, Electro, SINGLE CORE WIRE
Doncaster Cables 10mm Single Core – Black
Product Description
Manufactured to BS 6004:2012 Table 3
Annealed Stranded Copper Conductor / PVC Insulated / PVC Sheathed. 300/500V
Designed for use in light industrial and domestic wiring. These cables are particularly suited for installation as meter tails and are intended for fixed installation in dry or damp premises.
These cables can be installed in conduit, in cable trunking and in cable ducting. Or where there is deemed little risk of mechanical damage these cables can be clipped direct, on cable tray, embedded or in free air. These cables are not intended to be laid underground.
Product Details
 Harmonisation Code Nominal Cross Sectional Area of Conductor (mm2) Nominal Stranding of Conductor (mm) Nominal Radial Thickness of insulation (mm) Nominal Radial Thickness of sheath (mm) Overall Diameter Lower Limit (mm) Overall Diameter Upper Limit (mm) Approximate Weight(kg/km) National Type 1.0 1 / 1.13 0.6 0.8 3.8 4.5 26 National Type 1.5 1 / 1.38 0.7 0.8 4.2 4.9 35 National Type 2.5 1 / 1.78 0.8 0.8 4.8 5.8 55 National Type 4.0 7 / 0.85 0.8 0.9 5.4 6.8 75 National Type 6.0 7 / 1.04 0.8 0.9 6.0 7.4 95 National Type 10.0 7 / 1.35 1.0 0.9 7.2 8.8 155 National Type 16.0 7 / 1.70 1.0 1.0 8.4 10.5 225 National Type 25.0 7 / 2.14 1.2 1.1 10.0 12.5 340 National Type 35.0 7 / 2.52 1.2 1.1 11.0 13.5 445 SKU: n/a
There are no reviews yet.