Schneider Circuit Breakers, SCHNEIDER SECTIONS
Miniature circuit-breaker, Acti9 iC60H, 1P, 10 A, C curve, 10000 A (IEC 60898-1), 15 kA (IEC 60947-2) A9F84110
device application |
Distribution
|
|
---|---|---|
range |
Acti 9
|
|
product name |
Acti 9 iC60
|
|
product or component type |
Miniature circuit-breaker
|
|
device short name |
IC60H
|
|
poles description |
1P
|
|
number of protected poles |
1
|
|
[In] rated current |
10 A
|
|
network type |
DC
AC |
|
trip unit technology |
Thermal-magnetic
|
|
curve code |
C
|
|
breaking capacity |
10000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
15 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2 42 kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2 30 kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 60…72 V DC conforming to EN/IEC 60947-2 20 kA Icu at 12…60 V DC conforming to EN/IEC 60947-2 |
|
utilisation category |
Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2 |
|
suitability for isolation |
Yes conforming to EN 60898-1
Yes conforming to EN 60947-2 Yes conforming to IEC 60898-1 Yes conforming to IEC 60947-2 |
|
standards |
EN 60898-1
EN 60947-2 IEC 60898-1 IEC 60947-2 |
network frequency |
50/60 Hz
|
|
---|---|---|
magnetic tripping limit |
8 x In +/- 20 %
|
|
[Ics] rated service breaking capacity |
21 kA 50 % conforming to EN 60947-2 – 12…60 V AC 50/60 Hz
7.5 kA 50 % conforming to EN 60947-2 – 220…240 V AC 50/60 Hz 21 kA 50 % conforming to IEC 60947-2 – 12…60 V AC 50/60 Hz 7.5 kA 50 % conforming to IEC 60947-2 – 220…240 V AC 50/60 Hz 7500 A 75 % conforming to EN 60898-1 – 230 V AC 50/60 Hz 7500 A 75 % conforming to IEC 60898-1 – 230 V AC 50/60 Hz 15 kA 50 % conforming to IEC 60947-2 – 100…133 V AC 50/60 Hz 15 kA 50 % conforming to EN 60947-2 – 100…133 V AC 50/60 Hz 15 kA 100 % conforming to EN 60947-2 – 72 V DC 15 kA 100 % conforming to IEC 60947-2 – 72 V DC 20 kA 100 % conforming to EN 60947-2 – 12…60 V DC 20 kA 100 % conforming to IEC 60947-2 – 12…60 V DC |
|
limitation class |
3 conforming to EN 60898-1
3 conforming to IEC 60898-1 |
|
[Ui] rated insulation voltage |
500 V AC 50/60 Hz conforming to EN 60947-2
500 V AC 50/60 Hz conforming to IEC 60947-2 |
|
[Uimp] rated impulse withstand voltage |
6 kV conforming to EN 60947-2
6 kV conforming to IEC 60947-2 |
|
contact position indicator |
Yes
|
|
control type |
Toggle
|
|
local signalling |
Trip indicator
|
|
mounting mode |
Fixed
|
|
mounting support |
DIN rail
|
|
comb busbar and distribution block compatibility |
Top or bottom: YES
|
|
9 mm pitches |
2
|
|
height |
85 mm
|
|
width |
18 mm
|
|
depth |
78.5 mm
|
|
net weight |
0.215 kg
|
|
colour |
White
|
|
mechanical durability |
20000 cycles
|
|
electrical durability |
10000 cycles
|
|
connections – terminals |
Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexible |
|
wire stripping length |
14 mm for top or bottom connection
|
|
tightening torque |
2 N.m top or bottom
|
|
earth-leakage protection |
Without
|
IP degree of protection |
IP20 conforming to IEC 60529
IP20 conforming to EN 60529 |
|
---|---|---|
pollution degree |
3 conforming to EN 60947-2
3 conforming to IEC 60947-2 |
|
overvoltage category |
IV
|
|
tropicalisation |
2 conforming to IEC 60068-1
|
|
relative humidity |
95 % at 55 °C
|
|
operating altitude |
0…2000 m
|
|
ambient air temperature for operation |
-35…70 °C
|
|
ambient air temperature for storage |
-40…85 °C
|
₦4,999.00
Compare-
Schneider Circuit Breakers, SCHNEIDER SECTIONS
EZ9F56225 Easy9 miniature circuit breaker- 2P – 25 A – C curve – 6000 A – 230 V
Schneider Circuit Breakers, SCHNEIDER SECTIONSEZ9F56225 Easy9 miniature circuit breaker- 2P – 25 A – C curve – 6000 A – 230 V
Main range Easy9device application Distributionproduct or component type Miniature circuit-breakerdevice short name Easy9 MCBPoles 2Pnumber of protected poles 2[In] rated current 25 Anetwork type ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 10000 A Icn at 220 V AC 50/60 Hz conforming to IEC 60898-1
6000 A Icn at 400 V AC 50/60 Hz conforming to IEC 60898-1suitability for isolation Yes conforming to IEC 60898-1Complementary network frequency 50/60 Hz[Ue] rated operational voltage 220 V AC 50/60 Hz
400 V AC 50/60 Hzmagnetic tripping limit 5…10 x In[Ics] rated service breaking capacity 6 kA 100 % x Icn at 230 V AC 50/60 Hz conforming to IEC 60898-1[Ui] rated insulation voltage 500 V AC 50/60 Hz conforming to IEC 60898-1[Uimp] rated impulse withstand voltage 4 kV conforming to IEC 60898-1contact position indicator Yescontrol type Togglelocal signalling Withoutmounting mode Clip-onmounting support DIN rail9 mm pitches 4height 81 mmwidth 36 mmdepth 66.5 mmcolour Grey (RAL 7035)mechanical durability 10000 cycleselectrical durability 4000 cyclesconnections – terminals Tunnel type terminal (top or bottom) 1…25 mm² rigid
Tunnel type terminal (top or bottom) 1…16 mm² flexibletightening torque 2 N.m top or bottomearth-leakage protection WithoutSKU: n/a -
CABLE AND CABLE MANAGEMENT, Electro, SINGLE CORE WIRE
Doncaster Cables 16mm Single Core – Red
Product Description
Manufactured to BS 6004:2012 Table 3
Annealed Stranded Copper Conductor / PVC Insulated / PVC Sheathed. 300/500V
Designed for use in light industrial and domestic wiring. These cables are particularly suited for installation as meter tails and are intended for fixed installation in dry or damp premises.
These cables can be installed in conduit, in cable trunking and in cable ducting. Or where there is deemed little risk of mechanical damage these cables can be clipped direct, on cable tray, embedded or in free air. These cables are not intended to be laid underground.
Product Details
Harmonisation Code Nominal Cross Sectional Area of Conductor (mm2) Nominal Stranding of Conductor (mm) Nominal Radial Thickness of insulation (mm) Nominal Radial Thickness of sheath (mm) Overall Diameter Lower Limit (mm) Overall Diameter Upper Limit (mm) Approximate Weight(kg/km) National Type 1.0 1 / 1.13 0.6 0.8 3.8 4.5 26 National Type 1.5 1 / 1.38 0.7 0.8 4.2 4.9 35 National Type 2.5 1 / 1.78 0.8 0.8 4.8 5.8 55 National Type 4.0 7 / 0.85 0.8 0.9 5.4 6.8 75 National Type 6.0 7 / 1.04 0.8 0.9 6.0 7.4 95 National Type 10.0 7 / 1.35 1.0 0.9 7.2 8.8 155 National Type 16.0 7 / 1.70 1.0 1.0 8.4 10.5 225 National Type 25.0 7 / 2.14 1.2 1.1 10.0 12.5 340 National Type 35.0 7 / 2.52 1.2 1.1 11.0 13.5 445 SKU: n/a -
LIGHT SWITCHES & ELECTRICAL SOCKETS, SCHNEIDER SECTIONS
Ultimate Screwless dimmer switch 400W/VA, 1gang, 2way, main & LV, st.steel GU6412CSS
LIGHT SWITCHES & ELECTRICAL SOCKETS, SCHNEIDER SECTIONSUltimate Screwless dimmer switch 400W/VA, 1gang, 2way, main & LV, st.steel GU6412CSS
Main range of product Ultimaterange Ultimateaesthetic name Screwless flat plateproduct or component type Dimmerdevice application Controlload type Incandescent lamp
230 V AC halogen lamp: 400 Wcolour tint Stainless steelquantity per set Set of 1Complementary switch function 2-waydevice mounting Wall mounteddimmer application Resistive load
Inductive load[Ue] rated operational voltage 230 V AC 50 Hznumber of gangs 1 gangconnections – terminals Screwless terminalsfixing mode By screws M3.5 x 25 mmheight 88 mmwidth 88 mmdepth 25 mmSKU: n/a -
Schneider Circuit Breakers, SCHNEIDER SECTIONS
Acti9 iC60N 3P 2A C Miniature Circuit breaker A9F44302
Schneider Circuit Breakers, SCHNEIDER SECTIONSActi9 iC60N 3P 2A C Miniature Circuit breaker A9F44302
Main range Acti 9product name Disbo iC60product or component type Miniature circuit-breakerdevice short name IC60Npoles description 3Pnumber of protected poles 3[In] rated current 2 Anetwork type ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 50 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
50 kA Icu at 12…133 V AC 50/60 Hz conforming to EN/IEC 60947-2
50 kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2
25 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2
6000 A Icn at 415 V AC 50/60 Hz conforming to EN/IEC 60898-1
15 kA Icu at 100…133 V DC conforming to EN/IEC 60947-2utilisation category Category A conforming to EN/IEC 60947-2Complementary network frequency 50/60 Hz[Ue] rated operational voltage 440 V AC 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 50 kA 100 % conforming to EN/IEC 60947-2 – 220…240 V AC 50/60 Hz
50 kA 100 % conforming to EN/IEC 60947-2 – 12…133 V AC 50/60 Hz
50 kA 100 % conforming to EN/IEC 60947-2 – 380…415 V AC 50/60 Hz
25 kA 100 % conforming to EN/IEC 60947-2 – 440 V AC 50/60 Hz
6000 A 100 % conforming to EN/IEC 60898-1 – 415 V AC 50/60 Hz
15 kA 100 % conforming to EN/IEC 60947-2 – 100…133 V DClimitation class 3 conforming to EN/IEC 60947-2[Ui] rated insulation voltage 500 V AC 50/60 Hz[Uimp] rated impulse withstand voltage 6 kV conforming to EN/IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Clip-onmounting support Rail9 mm pitches 6height 85 mmwidth 54 mmdepth 78.5 mmnet weight 0.375 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesprovision for padlocking Padlockableconnections – terminals Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 2 N.m top or bottomearth-leakage protection Separate blockSKU: n/a -
Electro, LIGHT SWITCHES & ELECTRICAL SOCKETS
Lisse – Switched Socket – 1 gang – 13A Mocha Bronze with Black Interior GGBL3010BMB
Electro, LIGHT SWITCHES & ELECTRICAL SOCKETSLisse – Switched Socket – 1 gang – 13A Mocha Bronze with Black Interior GGBL3010BMB
Main range Lisseaesthetic name Screwless decoproduct or component type Switched socketdevice presentation Complete productoutlet standard Britishquantity per set Set of 10type of packing BoxComplementary switch function 1-poleactuator Rockernumber of gangs 1 gangfixing mode Concealed screwsconnections – terminals Screw terminalsmaterial Stainless steeltype of installation Indoordepth 33 mmwidth 87 mmheight 87 mmnet weight 0.123 kgSKU: n/a -
Schneider Circuit Breakers, SCHNEIDER SECTIONS
Easy9 miniature circuit breaker- 3P – 6 A – C curve – 6000 A – 400 V EZ9F56306
Schneider Circuit Breakers, SCHNEIDER SECTIONSEasy9 miniature circuit breaker- 3P – 6 A – C curve – 6000 A – 400 V EZ9F56306
Main range Easy9device application Distributionproduct or component type Miniature circuit-breakerdevice short name Easy9 MCBPoles 3Pnumber of protected poles 3[In] rated current 6 Anetwork type ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 10000 A Icn at 220 V AC 50/60 Hz conforming to IEC 60898-1
6000 A Icn at 400 V AC 50/60 Hz conforming to IEC 60898-1suitability for isolation Yes conforming to IEC 60898-1Complementary network frequency 50 Hz[Ue] rated operational voltage 220 V AC 50/60 Hz
400 V AC 50/60 Hzmagnetic tripping limit 5…10 x In[Ics] rated service breaking capacity 6 kA 100 % x Icn at 400 V AC 50/60 Hz conforming to IEC 60898-1[Ui] rated insulation voltage 500 V AC 50/60 Hz conforming to IEC 60898-1[Uimp] rated impulse withstand voltage 4 kV conforming to IEC 60898-1contact position indicator Yescontrol type Togglelocal signalling Withoutmounting mode Clip-onmounting support DIN rail9 mm pitches 6height 81 mmwidth 54 mmdepth 66.5 mmcolour Grey (RAL 7035)mechanical durability 10000 cycleselectrical durability 4000 cyclesconnections – terminals Tunnel type terminal (top or bottom) 1…25 mm² rigid
Tunnel type terminal (top or bottom) 1…16 mm² flexibletightening torque 2 N.m top or bottomSKU: n/a
There are no reviews yet.