Schneider Circuit Breakers, SCHNEIDER SECTIONS
Miniature circuit-breaker, Acti9 iC60H, 2P, 1 A, C curve, 10000 A (IEC 60898-1), 70 kA (IEC 60947-2) A9F84201
device application |
Distribution
|
|
---|---|---|
range |
Acti 9
|
|
product name |
Acti 9 iC60
|
|
product or component type |
Miniature circuit-breaker
|
|
device short name |
IC60H
|
|
poles description |
2P
|
|
number of protected poles |
2
|
|
[In] rated current |
1 A
|
|
network type |
DC
AC |
|
trip unit technology |
Thermal-magnetic
|
|
curve code |
C
|
|
breaking capacity |
10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
15 kA Icu at <= 125 V DC conforming to EN/IEC 60947-2 70 kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2 70 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2 70 kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2 70 kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2 70 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
|
utilisation category |
Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2 |
|
suitability for isolation |
Yes conforming to EN 60898-1
Yes conforming to EN 60947-2 Yes conforming to IEC 60898-1 Yes conforming to IEC 60947-2 |
|
standards |
EN 60898-1
IEC 60898-1 EN 60947-2 IEC 60947-2 |
|
quality labels |
NF
|
network frequency |
50/60 Hz
|
|
---|---|---|
magnetic tripping limit |
8 x In +/- 20 %
|
|
[Ics] rated service breaking capacity |
70 kA 100 % conforming to EN 60947-2 – 220…240 V AC 50/60 Hz
70 kA 100 % conforming to IEC 60947-2 – 220…240 V AC 50/60 Hz 70 kA 100 % conforming to EN 60947-2 – 380…415 V AC 50/60 Hz 70 kA 100 % conforming to IEC 60947-2 – 380…415 V AC 50/60 Hz 7500 A 75 % conforming to EN 60898-1 – 400 V AC 50/60 Hz 7500 A 75 % conforming to IEC 60898-1 – 400 V AC 50/60 Hz 70 kA 100 % conforming to IEC 60947-2 – 12…133 V AC 50/60 Hz 70 kA 100 % conforming to EN 60947-2 – 12…133 V AC 50/60 Hz 50 kA 100 % conforming to EN 60947-2 – 440 V AC 50/60 Hz 50 kA 100 % conforming to IEC 60947-2 – 440 V AC 50/60 Hz 15 kA 100 % conforming to IEC 60947-2 – 72…125 V DC 15 kA 100 % conforming to EN 60947-2 – 72…125 V DC |
|
limitation class |
3 conforming to EN 60898-1
3 conforming to IEC 60898-1 |
|
[Ui] rated insulation voltage |
500 V AC 50/60 Hz conforming to EN 60947-2
500 V AC 50/60 Hz conforming to IEC 60947-2 |
|
[Uimp] rated impulse withstand voltage |
6 kV conforming to EN 60947-2
6 kV conforming to IEC 60947-2 |
|
contact position indicator |
Yes
|
|
control type |
Toggle
|
|
local signalling |
Trip indicator
|
|
mounting mode |
Fixed
|
|
mounting support |
DIN rail
|
|
comb busbar and distribution block compatibility |
Top or bottom: YES
|
|
9 mm pitches |
4
|
|
height |
85 mm
|
|
width |
36 mm
|
|
depth |
78.5 mm
|
|
net weight |
0.25 kg
|
|
colour |
White
|
|
mechanical durability |
20000 cycles
|
|
electrical durability |
10000 cycles
|
|
connections – terminals |
Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexible |
|
wire stripping length |
14 mm for top or bottom connection
|
|
tightening torque |
2 N.m top or bottom
|
|
earth-leakage protection |
Separate block
|
₦12,999.00
Compare-
CHANGEOVER SWITCHES, Electro, GEAR SWITCHES & CHANGEOVER
ABB CHANGEOVER SWITCH 800A with Enclosure
-
-
-
- Long Description:
- Including a black plastic IP65 I-0-II pistol type handle (see the table below), shaft and bolt set for the cable connection. Handle not padlockable and no door interlocking. Operating angle 90° to achieve fast switching. Minimum OFF-time between transfer from I-II or II-I is 20 ms.
Categories
- Products » Low Voltage Products and Systems » Switches » Change-over and Transfer Switches » Manual Change-over Switches
-
-
Technical
-
- Rated Operational Current AC-21A (Ie):
- (380 … 415 V) 800 A
(500 V) 800 A
(690 V) 800 A
-
- Rated Operational Current AC-22A (Ie):
- (380 … 415 V) 800 A
(500 V) 800 A
(690 V) 800 A
-
- Rated Operational Current AC-23A (Ie):
- (380 … 415 V) 800 A
(500 V) 800 A
(690 V) 800 A
-
- Rated Operational Current AC-31B (Ie):
- (380 … 415 V) 800 A
-
- Rated Operational Current AC-33B (Ie):
- (380 … 415 V) 800 A
-
- Rated Operational Power AC-23A (Pe):
- (380 … 415 V) 450 kW
(500 V) 560 kW
(690 V) 800 kW
-
- Conventional Free-air Thermal Current (Ith):
- q = 40 °C 800 A
-
- Conventional Thermal Current (Ithe):
- Fully Enclosed 800 A
-
- Rated Impulse Withstand Voltage (Uimp):
- 12 kV
-
- Rated Insulation Voltage (Ui):
- 1000 V
-
- Rated Operational Voltage:
- 1000 V
-
- Rated Short-time Withstand Current (Icw):
- for 1 s 20 kiloampere rms
-
- Power Loss:
- 40 W
SKU: n/a -
-
Schneider Circuit Breakers, SCHNEIDER SECTIONS
Easy9 Residual Current Circuit Breaker – 4P – 63 A – 30 mA – AC type – 400 V EZ9R34463
Schneider Circuit Breakers, SCHNEIDER SECTIONSEasy9 Residual Current Circuit Breaker – 4P – 63 A – 30 mA – AC type – 400 V EZ9R34463
Main range of product Easy9product or component type Residual current circuit breaker (RCCB)device short name Easy9 RCCBPoles 4Pneutral position Left[In] rated current 63 Anetwork type ACearth-leakage sensitivity 30 mAearth-leakage protection time delay Instantaneousearth-leakage protection class Type ACrated breaking and making capacity 630 Arated conditional short-circuit current Easy9 MCB: 4500 A 63 AComplementary device location in system Outgoernetwork frequency 50 Hz[Ue] rated operational voltage 400 V AC 50 Hzresidual current tripping technology Voltage independent[Ui] rated insulation voltage 440 V AC[Uimp] rated impulse withstand voltage 4 kVsurge current 250 Acontact position indicator Yescontrol type Togglemounting mode Clip-onmounting support DIN railcomb busbar and distribution block compatibility Top: YES9 mm pitches 8height 82 mmwidth 72 mmdepth 72 mmcolour Grey (RAL 7035)mechanical durability 5000 cycleselectrical durability AC: 2000 cycles 400 V AC 50 Hzconnections – terminals Tunnel type terminal (top or bottom) 1…35 mm² rigid
Tunnel type terminal (top or bottom) 1…25 mm² flexibletightening torque 3.5 N.m top or bottommarket segment Residential
Small commercialSKU: n/a -
Schneider Circuit Breakers, SCHNEIDER SECTIONS
Acti9 iC60N 3P 16A C Miniature Circuit breaker A9F44316
Schneider Circuit Breakers, SCHNEIDER SECTIONSActi9 iC60N 3P 16A C Miniature Circuit breaker A9F44316
Main range Acti 9product name Disbo iC60product or component type Miniature circuit-breakerdevice short name IC60Npoles description 3Pnumber of protected poles 3[In] rated current 16 Anetwork type ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 6000 A Icn at 415 V AC 50/60 Hz conforming to EN/IEC 60898-1
36 kA Icu at 12…133 V AC 50/60 Hz conforming to EN/IEC 60947-2
20 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
10 kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2
6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2
15 kA Icu at 100…133 V DC conforming to EN/IEC 60947-2utilisation category Category A conforming to EN/IEC 60947-2Complementary network frequency 50/60 Hz[Ue] rated operational voltage 440 V AC 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 27 kA 75 % conforming to EN/IEC 60947-2 – 12…133 V AC 50/60 Hz
15 kA 75 % conforming to EN/IEC 60947-2 – 220…240 V AC 50/60 Hz
7.5 kA 75 % conforming to EN/IEC 60947-2 – 380…415 V AC 50/60 Hz
4.5 kA 75 % conforming to EN/IEC 60947-2 – 440 V AC 50/60 Hz
6000 A 100 % conforming to EN/IEC 60898-1 – 415 V AC 50/60 Hz
15 kA 100 % conforming to EN/IEC 60947-2 – 100…133 V DClimitation class 3 conforming to EN/IEC 60947-2[Ui] rated insulation voltage 500 V AC 50/60 Hz[Uimp] rated impulse withstand voltage 6 kV conforming to EN/IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Clip-onmounting support Rail9 mm pitches 6height 85 mmwidth 54 mmdepth 78.5 mmnet weight 0.375 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesprovision for padlocking Padlockableconnections – terminals Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 2 N.m top or bottomearth-leakage protection Separate blockSKU: n/a -
-
Schneider Industrial Sockets, SCHNEIDER SECTIONS
Thorsman – Cable reel 25m HO5VVF 3G1.5 IP44 BS 110V IMT33144
Schneider Industrial Sockets, SCHNEIDER SECTIONSThorsman – Cable reel 25m HO5VVF 3G1.5 IP44 BS 110V IMT33144
Main range PROchantierproduct or component type Cable reeldevice application Power supply[In] rated current 13 AComplementary cable length 25 mcable cross section 1.5 mm²type of cable H05VV-F3G1.5quantity per set Set of 1height 260 mmwidth 352 mmdepth 205 mmnet weight 5.13 kgSKU: n/a -
Schneider Circuit Breakers, SCHNEIDER SECTIONS
Miniature circuit-breaker, Acti9 iC60H, 2P, 63 A, C curve, 10000 A (IEC 60898-1), 15 kA (IEC 60947-2) A9F84263
Schneider Circuit Breakers, SCHNEIDER SECTIONSMiniature circuit-breaker, Acti9 iC60H, 2P, 63 A, C curve, 10000 A (IEC 60898-1), 15 kA (IEC 60947-2) A9F84263
Main device application Distributionrange Acti 9product name Acti 9 iC60product or component type Miniature circuit-breakerdevice short name IC60Hpoles description 2Pnumber of protected poles 2[In] rated current 63 Anetwork type DC
ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
42 kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2
10 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2
15 kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2
30 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
15 kA Icu at <= 125 V DC conforming to EN/IEC 60947-2
42 kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2utilisation category Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2suitability for isolation Yes conforming to EN 60898-1
Yes conforming to EN 60947-2
Yes conforming to IEC 60898-1
Yes conforming to IEC 60947-2standards IEC 60947-2
IEC 60898-1
EN 60947-2
EN 60898-1Complementary network frequency 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 15 kA 50 % conforming to EN 60947-2 – 220…240 V AC 50/60 Hz
7.5 kA 50 % conforming to EN 60947-2 – 380…415 V AC 50/60 Hz
5 kA 50 % conforming to EN 60947-2 – 440 V AC 50/60 Hz
15 kA 50 % conforming to IEC 60947-2 – 220…240 V AC 50/60 Hz
7.5 kA 50 % conforming to IEC 60947-2 – 380…415 V AC 50/60 Hz
5 kA 50 % conforming to IEC 60947-2 – 440 V AC 50/60 Hz
7500 A 75 % conforming to EN 60898-1 – 400 V AC 50/60 Hz
7500 A 75 % conforming to IEC 60898-1 – 400 V AC 50/60 Hz
21 kA 50 % conforming to IEC 60947-2 – 12…133 V AC 50/60 Hz
21 kA 50 % conforming to EN 60947-2 – 12…133 V AC 50/60 Hz
15 kA 100 % conforming to IEC 60947-2 – 72…125 V DC
15 kA 100 % conforming to EN 60947-2 – 72…125 V DC[Ui] rated insulation voltage 500 V AC 50/60 Hz conforming to EN 60947-2
500 V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6 kV conforming to EN 60947-2
6 kV conforming to IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Fixedmounting support DIN railcomb busbar and distribution block compatibility Top or bottom: YES9 mm pitches 4height 85 mmwidth 36 mmdepth 78.5 mmnet weight 0.25 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesconnections – terminals Single terminal (top or bottom) 1…35 mm² rigid
Single terminal (top or bottom) 1…25 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 3.5 N.m top or bottomearth-leakage protection Separate blockSKU: n/a