Miniature circuit-breaker, Acti9 iC60H, 2P, 16 A, C curve, 10000 A (IEC 60898-1), 15 kA (IEC 60947-2) A9F84216
device application |
Distribution
|
|
---|---|---|
range |
Acti 9
|
|
product name |
Acti 9 iC60
|
|
product or component type |
Miniature circuit-breaker
|
|
device short name |
IC60H
|
|
poles description |
2P
|
|
number of protected poles |
2
|
|
[In] rated current |
16 A
|
|
network type |
DC
AC |
|
trip unit technology |
Thermal-magnetic
|
|
curve code |
C
|
|
breaking capacity |
10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
42 kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2 30 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at <= 125 V DC conforming to EN/IEC 60947-2 42 kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
|
utilisation category |
Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2 |
|
suitability for isolation |
Yes conforming to EN 60898-1
Yes conforming to EN 60947-2 Yes conforming to IEC 60898-1 Yes conforming to IEC 60947-2 |
|
standards |
EN 60898-1
IEC 60898-1 EN 60947-2 IEC 60947-2 |
network frequency |
50/60 Hz
|
|
---|---|---|
magnetic tripping limit |
8 x In +/- 20 %
|
|
[Ics] rated service breaking capacity |
15 kA 50 % conforming to EN 60947-2 – 220…240 V AC 50/60 Hz
7.5 kA 50 % conforming to EN 60947-2 – 380…415 V AC 50/60 Hz 5 kA 50 % conforming to EN 60947-2 – 440 V AC 50/60 Hz 15 kA 50 % conforming to IEC 60947-2 – 220…240 V AC 50/60 Hz 7.5 kA 50 % conforming to IEC 60947-2 – 380…415 V AC 50/60 Hz 5 kA 50 % conforming to IEC 60947-2 – 440 V AC 50/60 Hz 7500 A 75 % conforming to EN 60898-1 – 400 V AC 50/60 Hz 7500 A 75 % conforming to IEC 60898-1 – 400 V AC 50/60 Hz 21 kA 50 % conforming to IEC 60947-2 – 12…133 V AC 50/60 Hz 21 kA 50 % conforming to EN 60947-2 – 12…133 V AC 50/60 Hz 15 kA 100 % conforming to IEC 60947-2 – 72…125 V DC 15 kA 100 % conforming to EN 60947-2 – 72…125 V DC |
|
limitation class |
3 conforming to EN 60898-1
3 conforming to IEC 60898-1 |
|
[Ui] rated insulation voltage |
500 V AC 50/60 Hz conforming to EN 60947-2
500 V AC 50/60 Hz conforming to IEC 60947-2 |
|
[Uimp] rated impulse withstand voltage |
6 kV conforming to EN 60947-2
6 kV conforming to IEC 60947-2 |
|
contact position indicator |
Yes
|
|
control type |
Toggle
|
|
local signalling |
Trip indicator
|
|
mounting mode |
Fixed
|
|
mounting support |
DIN rail
|
|
comb busbar and distribution block compatibility |
Top or bottom: YES
|
|
9 mm pitches |
4
|
|
height |
85 mm
|
|
width |
36 mm
|
|
depth |
78.5 mm
|
|
net weight |
0.25 kg
|
|
colour |
White
|
|
mechanical durability |
20000 cycles
|
|
electrical durability |
10000 cycles
|
|
connections – terminals |
Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexible |
|
wire stripping length |
14 mm for top or bottom connection
|
|
tightening torque |
2 N.m top or bottom
|
|
earth-leakage protection |
Separate block
|
₦7,999.00
Compare-
ELECTRICAL INDUSTRIAL, TRANSFORMER
MEKSAN Transformer 50kVA 33/415kV
Meksan Transformer manufacture distribution and power transformer from 50 kVA up to 50 MVA. Our products are produced in accordance with the TS 267 and the IEC60076 standards. Our production is documented with the TSE (Türkish Standard Institue) standards confortmity, ISO 9001:2000 quality system and ISO 14001 environmental management system certificates.
SKU: n/a -
Schneider Circuit Breakers, SCHNEIDER SECTIONS
Easy9 miniature circuit breaker- 4P – 6 A – C curve – 6000 A – 400 V EZ9F56406
Schneider Circuit Breakers, SCHNEIDER SECTIONSEasy9 miniature circuit breaker- 4P – 6 A – C curve – 6000 A – 400 V EZ9F56406
Main range Easy9device application Distributionproduct or component type Miniature circuit-breakerdevice short name Easy9 MCBPoles 4Pnumber of protected poles 4[In] rated current 6 Anetwork type ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 10000 A Icn at 220 V AC 50/60 Hz conforming to IEC 60898-1
6000 A Icn at 400 V AC 50/60 Hz conforming to IEC 60898-1suitability for isolation Yes conforming to IEC 60898-1Complementary network frequency 50 Hz[Ue] rated operational voltage 220 V AC 50/60 Hz
400 V AC 50/60 Hzmagnetic tripping limit 5…10 x In[Ics] rated service breaking capacity 6 kA 100 % x Icn at 400 V AC 50/60 Hz conforming to IEC 60898-1[Ui] rated insulation voltage 500 V AC 50/60 Hz conforming to IEC 60898-1[Uimp] rated impulse withstand voltage 4 kV conforming to IEC 60898-1contact position indicator Yescontrol type Togglelocal signalling Withoutmounting mode Clip-onmounting support DIN rail9 mm pitches 8height 81 mmwidth 72 mmdepth 66.5 mmcolour Grey (RAL 7035)mechanical durability 10000 cycleselectrical durability 4000 cyclesconnections – terminals Tunnel type terminal (top or bottom) 1…25 mm² rigid
Tunnel type terminal (top or bottom) 1…16 mm² flexibletightening torque 2 N.m top or bottomSKU: n/a -
-
CHANGEOVER SWITCHES, Electro, GEAR SWITCHES & CHANGEOVER
ABB CHANGEOVER SWITCH 800A with Enclosure
-
-
-
- Long Description:
- Including a black plastic IP65 I-0-II pistol type handle (see the table below), shaft and bolt set for the cable connection. Handle not padlockable and no door interlocking. Operating angle 90° to achieve fast switching. Minimum OFF-time between transfer from I-II or II-I is 20 ms.
Categories
- Products » Low Voltage Products and Systems » Switches » Change-over and Transfer Switches » Manual Change-over Switches
-
-
Technical
-
- Rated Operational Current AC-21A (Ie):
- (380 … 415 V) 800 A
(500 V) 800 A
(690 V) 800 A
-
- Rated Operational Current AC-22A (Ie):
- (380 … 415 V) 800 A
(500 V) 800 A
(690 V) 800 A
-
- Rated Operational Current AC-23A (Ie):
- (380 … 415 V) 800 A
(500 V) 800 A
(690 V) 800 A
-
- Rated Operational Current AC-31B (Ie):
- (380 … 415 V) 800 A
-
- Rated Operational Current AC-33B (Ie):
- (380 … 415 V) 800 A
-
- Rated Operational Power AC-23A (Pe):
- (380 … 415 V) 450 kW
(500 V) 560 kW
(690 V) 800 kW
-
- Conventional Free-air Thermal Current (Ith):
- q = 40 °C 800 A
-
- Conventional Thermal Current (Ithe):
- Fully Enclosed 800 A
-
- Rated Impulse Withstand Voltage (Uimp):
- 12 kV
-
- Rated Insulation Voltage (Ui):
- 1000 V
-
- Rated Operational Voltage:
- 1000 V
-
- Rated Short-time Withstand Current (Icw):
- for 1 s 20 kiloampere rms
-
- Power Loss:
- 40 W
SKU: n/a -
-
CHINT
Chint 2 Gang Switch
Founded in 1984, CHINT is a leading global provider of smart energy solutions. It is actively deploying “4+1” industrial sectors including smart electrics, green energy, industrial control and automation, smart home and incubator, forming an integrated whole industry chain of “power generation, storage, transmission, substation, distribution, sales and consumption”.