Schneider Circuit Breakers, SCHNEIDER SECTIONS
Miniature circuit-breaker, Acti9 iC60H, 2P, 4 A, C curve, 10000 A (IEC 60898-1), 70 kA (IEC 60947-2) A9F84204
device application |
Distribution
|
|
---|---|---|
range |
Acti 9
|
|
product name |
Acti 9 iC60
|
|
product or component type |
Miniature circuit-breaker
|
|
device short name |
IC60H
|
|
poles description |
2P
|
|
number of protected poles |
2
|
|
[In] rated current |
4 A
|
|
network type |
AC
DC |
|
trip unit technology |
Thermal-magnetic
|
|
curve code |
C
|
|
breaking capacity |
10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
15 kA Icu at <= 125 V DC conforming to EN/IEC 60947-2 70 kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2 70 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2 70 kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2 70 kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2 70 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
|
utilisation category |
Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2 |
|
suitability for isolation |
Yes conforming to EN 60898-1
Yes conforming to EN 60947-2 Yes conforming to IEC 60898-1 Yes conforming to IEC 60947-2 |
|
standards |
IEC 60947-2
IEC 60898-1 EN 60947-2 EN 60898-1 |
|
quality labels |
NF
|
network frequency |
50/60 Hz
|
|
---|---|---|
magnetic tripping limit |
8 x In +/- 20 %
|
|
[Ics] rated service breaking capacity |
70 kA 100 % conforming to EN 60947-2 – 220…240 V AC 50/60 Hz
70 kA 100 % conforming to IEC 60947-2 – 220…240 V AC 50/60 Hz 70 kA 100 % conforming to EN 60947-2 – 380…415 V AC 50/60 Hz 70 kA 100 % conforming to IEC 60947-2 – 380…415 V AC 50/60 Hz 7500 A 75 % conforming to EN 60898-1 – 400 V AC 50/60 Hz 7500 A 75 % conforming to IEC 60898-1 – 400 V AC 50/60 Hz 70 kA 100 % conforming to IEC 60947-2 – 12…133 V AC 50/60 Hz 70 kA 100 % conforming to EN 60947-2 – 12…133 V AC 50/60 Hz 50 kA 100 % conforming to EN 60947-2 – 440 V AC 50/60 Hz 50 kA 100 % conforming to IEC 60947-2 – 440 V AC 50/60 Hz 15 kA 100 % conforming to IEC 60947-2 – 72…125 V DC 15 kA 100 % conforming to EN 60947-2 – 72…125 V DC |
|
limitation class |
3 conforming to EN 60898-1
3 conforming to IEC 60898-1 |
|
[Ui] rated insulation voltage |
500 V AC 50/60 Hz conforming to EN 60947-2
500 V AC 50/60 Hz conforming to IEC 60947-2 |
|
[Uimp] rated impulse withstand voltage |
6 kV conforming to EN 60947-2
6 kV conforming to IEC 60947-2 |
|
contact position indicator |
Yes
|
|
control type |
Toggle
|
|
local signalling |
Trip indicator
|
|
mounting mode |
Fixed
|
|
mounting support |
DIN rail
|
|
comb busbar and distribution block compatibility |
Top or bottom: YES
|
|
9 mm pitches |
4
|
|
height |
85 mm
|
|
width |
36 mm
|
|
depth |
78.5 mm
|
|
net weight |
0.25 kg
|
|
colour |
White
|
|
mechanical durability |
20000 cycles
|
|
electrical durability |
10000 cycles
|
|
connections – terminals |
Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexible |
|
wire stripping length |
14 mm for top or bottom connection
|
|
tightening torque |
2 N.m top or bottom
|
|
earth-leakage protection |
Separate block
|
₦12,999.00
Compare-
-
Electro, LIGHT SWITCHES & ELECTRICAL SOCKETS
Lisse – Blank Plate – 2 gang Stainless Steel GGBL8020SS
Main range Lisseaesthetic name Screwless decoproduct or component type Blank platedevice presentation Complete productcolour tint Stainless steelquantity per set Set of 5Complementary fixing mode Concealed screwsnumber of gangs 2 gangsmaterial Stainless steelsurface finish Brushed finishtype of packing Boxheight 87 mmwidth 148 mmdepth 9 mmnet weight 0.136 kgSKU: n/a -
Schneider Circuit Breakers, SCHNEIDER SECTIONS
Easy9 miniature circuit breaker- 3P – 20 A – C curve – 6000 A – 400 V EZ9F56320
Schneider Circuit Breakers, SCHNEIDER SECTIONSEasy9 miniature circuit breaker- 3P – 20 A – C curve – 6000 A – 400 V EZ9F56320
Main range Easy9device application Distributionproduct or component type Miniature circuit-breakerdevice short name Easy9 MCBPoles 3Pnumber of protected poles 3[In] rated current 20 Anetwork type ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 10000 A Icn at 220 V AC 50/60 Hz conforming to IEC 60898-1
6000 A Icn at 400 V AC 50/60 Hz conforming to IEC 60898-1suitability for isolation Yes conforming to IEC 60898-1Complementary network frequency 50 Hz[Ue] rated operational voltage 220 V AC 50/60 Hz
400 V AC 50/60 Hzmagnetic tripping limit 5…10 x In[Ics] rated service breaking capacity 6 kA 100 % x Icn at 400 V AC 50/60 Hz conforming to IEC 60898-1[Ui] rated insulation voltage 500 V AC 50/60 Hz conforming to IEC 60898-1[Uimp] rated impulse withstand voltage 4 kV conforming to IEC 60898-1contact position indicator Yescontrol type Togglelocal signalling Withoutmounting mode Clip-onmounting support DIN rail9 mm pitches 6height 81 mmwidth 54 mmdepth 66.5 mmcolour Grey (RAL 7035)mechanical durability 10000 cycleselectrical durability 4000 cyclesconnections – terminals Tunnel type terminal (top or bottom) 1…25 mm² rigid
Tunnel type terminal (top or bottom) 1…16 mm² flexibletightening torque 2 N.m top or bottomSKU: n/a -
Schneider Mureva Floodlight, SCHNEIDER SECTIONS
Thorsman, Worklight 30W, IP65 DK Plug 230V IMT47230
Main range Thorsmanrange of product Thorsman Worklightsproduct name Worklightproduct or component type Lampdevice application Mobile equipment
Ware-houses and parking garages
Hospital
Residential
Sports hallComplementary type of installation Outdoor[Ue] rated operational voltage 230 Vnetwork type ACoperational power in W 30 Wplug standard Denmarkluminous flux 3000 lmbulb lifespan 50000 hcolour rendering index Ra=80colour temperature 4000 Kbeam angle 110 °power factor 0.9height 254.5 mmwidth 231.0 mmdepth 20.0 mmnet weight 1.1 kgSKU: n/a
There are no reviews yet.