Miniature circuit breaker, Easy9, 1P, 10 A, C curve, 6000 A
range |
Easy9
|
|
---|---|---|
device application |
Distribution
|
|
product or component type |
Miniature circuit-breaker
|
|
device short name |
Easy9 MCB
|
|
Poles |
1P
|
|
number of protected poles |
1
|
|
[In] rated current |
10 A
|
|
network type |
AC
|
|
trip unit technology |
Thermal-magnetic
|
|
curve code |
C
|
|
breaking capacity |
6000 A Icn at 230 V AC 50/60 Hz conforming to IEC 60898-1
10000 A Icn at 127 V AC 50/60 Hz conforming to IEC 60898-1 |
|
suitability for isolation |
Yes conforming to IEC 60898-1
|
network frequency |
50 Hz
|
|
---|---|---|
[Ue] rated operational voltage |
230 V AC 50 Hz
127 V AC 50 Hz |
|
magnetic tripping limit |
5…10 x In
|
|
[Ics] rated service breaking capacity |
6 kA 100 % x Icn at 230 V AC 50/60 Hz conforming to IEC 60898-1
|
|
[Ui] rated insulation voltage |
500 V AC 50/60 Hz conforming to IEC 60898-1
|
|
[Uimp] rated impulse withstand voltage |
4 kV conforming to IEC 60898-1
|
|
contact position indicator |
Yes
|
|
control type |
Toggle
|
|
local signalling |
Without
|
|
mounting mode |
Clip-on
|
|
mounting support |
DIN rail
|
|
9 mm pitches |
2
|
|
height |
81 mm
|
|
width |
18 mm
|
|
depth |
66.5 mm
|
|
colour |
Grey (RAL 7035)
|
|
mechanical durability |
10000 cycles
|
|
electrical durability |
4000 cycles
|
|
connections – terminals |
Tunnel type terminal (top or bottom) 1…25 mm² rigid
Tunnel type terminal (top or bottom) 1…16 mm² flexible |
|
tightening torque |
2 N.m top or bottom
|
₦1,390.00
Compare-
CABLE AND CABLE MANAGEMENT, Electro, SINGLE CORE WIRE
KABLEMETAL 4mm Single Core – Red
We offer other range of products across various categories and sub categories and our services are Procurement, installation and Management etc of electrical products, should you have any inquiry we are always here to do our best to promptly answer you.
SKU: 400 -
ELECTRICAL FITTINGS, Electro, HOME&OFFICE LIGHTING, LED LIGHTS, LIGHTING, OUTDOOR FITTINGS, OUTDOOR LIGHTS, SOLAR POWERED, WALL LIGHTS
Mornray SOLAR FLOOD LIGHT 150W
ELECTRICAL FITTINGS, Electro, HOME&OFFICE LIGHTING, LED LIGHTS, LIGHTING, OUTDOOR FITTINGS, OUTDOOR LIGHTS, SOLAR POWERED, WALL LIGHTSMornray SOLAR FLOOD LIGHT 150W
Solar Square Floodlight: Seven working modes for your convenience 1. Sensor mode 2. Half induction mode 3. 100% lighting mode 4. 50% lighting mode 5. 3 hour lighting mode 6. 5 hour lighting mode 7. 8 hour lighting mode Application: 1. Indoor use: indoor emergency lighting, home security lighting; 2. Outdoor use: courtyard lighting, landscape lighting, corridor lighting, door lighting, port lighting, container courtyard lighting, stadium lighting, courtyard lighting, plaza lighting, plant and beautification lighting, fountain waterscape lighting and other places; 3. Special event use: adventure lighting, camping lighting, fishing lighting, on-site maintenance lighting, barbecue lighting
SKU: n/a -
Electro, SOCKETS & SWITCHES, SWITCHES
FBN74 – 45AMP WATER HEATER SWITCH
BG Electrical are confident in the quality of our workmanship and materials, the guarantee stated applies from the date of delivery.
45A Rated
Easy to install supplied with fixing screws and installation instructions
Ideal for cookers and ovens
Double Pole switching for the peace of mind of a safer installation
Twin earth fitted as standard for high integrity circuits
Captive screws prevent screw loss
Flush power indicator
Screwless front plate clips on and off easily and has a sleek flat profile, with no visible plastic around the switch.
Moisture control gasket prevents tarnishing from new plaster
Minimum mounting box depth 47mm
SKU: n/a -
Schneider Circuit Breakers, SCHNEIDER SECTIONS
Acti9 iC60N 1P 3A C Miniature Circuit breaker A9F44103
Schneider Circuit Breakers, SCHNEIDER SECTIONSActi9 iC60N 1P 3A C Miniature Circuit breaker A9F44103
Main range Acti 9product name Disbo iC60product or component type Miniature circuit-breakerdevice short name IC60Npoles description 1Pnumber of protected poles 1[In] rated current 3 Anetwork type ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 50 kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2
50 kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2
50 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
15 kA Icu at 12…48 V DC conforming to EN/IEC 60947-2
6 kA Icu at 72 V DC conforming to EN/IEC 60947-2
6000 A Icn at 240 V AC 50/60 Hz conforming to EN/IEC 60898-1utilisation category Category A conforming to EN/IEC 60947-2Complementary network frequency 50/60 Hz[Ue] rated operational voltage 240 V AC 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 50 kA 100 % conforming to EN/IEC 60947-2 – 12…60 V AC 50/60 Hz
50 kA 100 % conforming to EN/IEC 60947-2 – 100…133 V AC 50/60 Hz
50 kA 100 % conforming to EN/IEC 60947-2 – 220…240 V AC 50/60 Hz
6000 A 100 % conforming to EN/IEC 60898-1 – 240 V AC 50/60 Hz
15 kA 100 % conforming to EN/IEC 60947-2 – 12…48 V DC
6 kA 100 % conforming to EN/IEC 60947-2 – 72 V DClimitation class 3 conforming to EN/IEC 60947-2[Ui] rated insulation voltage 500 V AC 50/60 Hz[Uimp] rated impulse withstand voltage 6 kV conforming to EN/IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Clip-onmounting support Rail9 mm pitches 2height 85 mmwidth 18 mmdepth 78.5 mmnet weight 0.125 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesprovision for padlocking Padlockableconnections – terminals Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 2 N.m top or bottomearth-leakage protection Separate blockSKU: n/a -
CABLE AND CABLE MANAGEMENT, Electro, SINGLE CORE WIRE
Doncaster Cables 2.5mm Single Core – Red
Product Description
Manufactured to BS 6004:2012 Table 3
Annealed Stranded Copper Conductor / PVC Insulated / PVC Sheathed. 300/500V
Designed for use in light industrial and domestic wiring. These cables are particularly suited for installation as meter tails and are intended for fixed installation in dry or damp premises.
These cables can be installed in conduit, in cable trunking and in cable ducting. Or where there is deemed little risk of mechanical damage these cables can be clipped direct, on cable tray, embedded or in free air. These cables are not intended to be laid underground.
Product Details
Harmonisation Code Nominal Cross Sectional Area of Conductor (mm2) Nominal Stranding of Conductor (mm) Nominal Radial Thickness of insulation (mm) Nominal Radial Thickness of sheath (mm) Overall Diameter Lower Limit (mm) Overall Diameter Upper Limit (mm) Approximate Weight(kg/km) National Type 1.0 1 / 1.13 0.6 0.8 3.8 4.5 26 National Type 1.5 1 / 1.38 0.7 0.8 4.2 4.9 35 National Type 2.5 1 / 1.78 0.8 0.8 4.8 5.8 55 National Type 4.0 7 / 0.85 0.8 0.9 5.4 6.8 75 National Type 6.0 7 / 1.04 0.8 0.9 6.0 7.4 95 National Type 10.0 7 / 1.35 1.0 0.9 7.2 8.8 155 National Type 16.0 7 / 1.70 1.0 1.0 8.4 10.5 225 National Type 25.0 7 / 2.14 1.2 1.1 10.0 12.5 340 National Type 35.0 7 / 2.52 1.2 1.1 11.0 13.5 445 SKU: n/a -
LIGHT SWITCHES & ELECTRICAL SOCKETS, SCHNEIDER SECTIONS
Ultimate Screwless flat plate – TV/FM socket – coaxial – 1 gang – stainles steel GU7410BSS
LIGHT SWITCHES & ELECTRICAL SOCKETS, SCHNEIDER SECTIONSUltimate Screwless flat plate – TV/FM socket – coaxial – 1 gang – stainles steel GU7410BSS
Main range of product Ultimateaesthetic name Screwless flat plateproduct or component type TV/FM socketTV socket type TV/FMquantity per set Set of 1Complementary radio connector Malenumber of gangs 1 gangfixing mode By screwsmaterial Steelheight 88 mmwidth 88 mmdepth 24 mmSKU: n/a
There are no reviews yet.