Switch disconnector iSW – 2P – 100 A – 415 V A9S65291 ISOLATOR SWITCH
range |
Acti 9
|
|
---|---|---|
product name |
Acti 9 iSW
|
|
product or component type |
Switch disconnector
|
|
device short name |
ISW
|
|
device application |
Isolation
Control |
|
poles description |
2P
|
|
utilisation category |
AC-22A
|
|
suitability for isolation |
Yes
|
[Ie] rated operational current |
100Â A at 415 V AC 50/60 Hz
|
|
---|---|---|
[Ue] rated operational voltage |
415 V AC 50/60 Hz
|
|
[Icm] rated short-circuit making capacity |
5Â kA switch-disconnector alone
|
|
[Icw] rated short-time withstand current |
1500Â A
|
|
[Ui] rated insulation voltage |
500Â V AC 50/60 Hz
|
|
[Uimp] rated impulse withstand voltage |
6Â kV
|
|
control type |
Toggle
|
|
local signalling |
ON/OFF indication
|
|
contact position indicator |
Yes
|
|
mounting mode |
Fixed
|
|
mounting support |
DIN rail
|
|
comb busbar and distribution block compatibility |
Top or bottom: YES
|
|
9 mm pitches |
4
|
|
height |
85Â mm
|
|
width |
36Â mm
|
|
depth |
73Â mm
|
|
colour |
White
|
|
mechanical durability |
20000Â cycles
|
|
electrical durability |
10000Â cycles
|
|
connections – terminals |
Tunnel type terminals (top or bottom) – <= 1 x 50 mm² – rigid
Tunnel type terminals (top or bottom) – <= 1 x 35 mm² – flexible Tunnel type terminals (top or bottom) – <= 1 x 35 mm² – flexible with ferrule |
|
wire stripping length |
9Â mm
|
|
tightening torque |
3.5Â N.m
|
₦28,000.00
Compare-
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONS
IC60H – miniature circuit breaker – 1P – 4A – C curve A9F84104
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONSIC60H – miniature circuit breaker – 1P – 4A – C curve A9F84104
Main device application Distributionrange Acti 9product name Acti 9 iC60product or component type Miniature circuit-breakerdevice short name IC60Hpoles description 1Pnumber of protected poles 1[In] rated current 4Â Anetwork type DC
ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 10000Â A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
15Â kA Icu at 60…72 V DC conforming to EN/IEC 60947-2
20Â kA Icu at 12…60 V DC conforming to EN/IEC 60947-2
70Â kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2
70Â kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
70Â kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2utilisation category Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2suitability for isolation Yes conforming to EN 60898-1
Yes conforming to EN 60947-2
Yes conforming to IEC 60898-1
Yes conforming to IEC 60947-2standards IEC 60898-1
EN 60947-2
EN 60898-1
IEC 60947-2Complementary network frequency 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 70Â kA 100Â % conforming to EN 60947-2 – 12…60 V AC 50/60 Hz
70Â kA 100Â % conforming to EN 60947-2 – 220…240 V AC 50/60 Hz
70Â kA 100Â % conforming to IEC 60947-2 – 12…60 V AC 50/60 Hz
70Â kA 100Â % conforming to IEC 60947-2 – 220…240 V AC 50/60 Hz
7500Â A 75Â % conforming to EN 60898-1 – 230 V AC 50/60 Hz
7500Â A 75Â % conforming to IEC 60898-1 – 230 V AC 50/60 Hz
70Â kA 100Â % conforming to IEC 60947-2 – 100…133 V AC 50/60 Hz
70Â kA 100Â % conforming to EN 60947-2 – 100…133 V AC 50/60 Hz
15Â kA 100Â % conforming to EN 60947-2 – 72 V DC
15Â kA 100Â % conforming to IEC 60947-2 – 72 V DC
20Â kA 100Â % conforming to EN 60947-2 – 12…60 V DC
20Â kA 100Â % conforming to IEC 60947-2 – 12…60 V DClimitation class 3 conforming to EN 60898-1
3 conforming to IEC 60898-1[Ui] rated insulation voltage 500Â V AC 50/60 Hz conforming to EN 60947-2
500Â V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6Â kV conforming to EN 60947-2
6 kV conforming to IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Fixedmounting support DIN railcomb busbar and distribution block compatibility Top or bottom: YES9 mm pitches 2height 85 mmwidth 18 mmdepth 78.5 mmnet weight 0.215 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesconnections – terminals Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 2 N.m top or bottomearth-leakage protection WithoutSKU: n/a -
Electro, LED LIGHTS, LIGHTING, OUTDOOR LIGHTS, SOLAR POWERED
LED All in One Solar Street Light 6eyes
- High-efficiency monocrystalline solar panel with fast charging and longer lifespan
- Environmental friendly long-life Po4 Batteries with overcharge and over discharge protection, solar and more reliable
- Built-in battery indicator light to check the battery capacity
- High-efficiency LED chip for working over than 20,000 hours lighting
SKU: n/a -
CHANGEOVER SWITCHES, Electro, GEAR SWITCHES & CHANGEOVER
ABB CHANGEOVER SWITCH 630A with Enclosure
Including a black plastic IP65 I-0-II pistol type handle (see the table below), shaft and bolt set for the cable connection. Handle padlockable in the 0-position, door interlock in the I- and Iipositions and when padlocked.
Categories
- Products » Low Voltage Products and Systems » Switches » Change-over and Transfer Switches » Manual Change-over Switches
Dimensions
-
- Product Net Width:Â 376Â mm
-
- Product Net Height:Â 250Â mm
-
- Product Net Depth / Length:Â 280Â mm
-
- Product Net Weight:Â Â 18.51 kg
- Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â Â 40.81 lb
Technical
-
- Rated Operational Current AC-21A (Ie):
- (380 … 415 V) 630 A
(500 V) 630 A
(690 V) 630 A
-
- Rated Operational Current AC-22A (Ie):
- (380 … 415 V) 630 A
(500 V) 630 A
(690 V) 630 A
-
- Rated Operational Current AC-23A (Ie):
- (380 … 415 V) 630 A
(500 V) 630 A
(690 V) 630 A
-
- Rated Operational Current AC-31B (Ie):
- (380 … 415 V) 630 A
-
- Rated Operational Current AC-33B (Ie):
- (380 … 415 V) 630 A
-
- Rated Operational Power AC-23A (Pe):
- (380 … 415 V) 355 kW
(500 V) 400 kW
(690 V) 630 kW
SKU: n/a -
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONS
Miniature circuit-breaker, Acti9 iC60H, 2P, 50 A, C curve, 10000 A (IEC 60898-1), 15 kA (IEC 60947-2) A9F84250
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONSMiniature circuit-breaker, Acti9 iC60H, 2P, 50 A, C curve, 10000 A (IEC 60898-1), 15 kA (IEC 60947-2) A9F84250
Main device application Distributionrange Acti 9product name Acti 9 iC60product or component type Miniature circuit-breakerdevice short name IC60Hpoles description 2Pnumber of protected poles 2[In] rated current 50Â Anetwork type AC
DCtrip unit technology Thermal-magneticcurve code Cbreaking capacity 10000Â A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
42Â kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2
10Â kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2
15Â kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2
30Â kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
15Â kA Icu at <= 125 V DC conforming to EN/IEC 60947-2
42Â kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2utilisation category Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2suitability for isolation Yes conforming to EN 60898-1
Yes conforming to EN 60947-2
Yes conforming to IEC 60898-1
Yes conforming to IEC 60947-2standards IEC 60947-2
EN 60947-2
EN 60898-1
IEC 60898-1Complementary network frequency 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 15Â kA 50Â % conforming to EN 60947-2 – 220…240 V AC 50/60 Hz
7.5Â kA 50Â % conforming to EN 60947-2 – 380…415 V AC 50/60 Hz
5Â kA 50Â % conforming to EN 60947-2 – 440 V AC 50/60 Hz
15Â kA 50Â % conforming to IEC 60947-2 – 220…240 V AC 50/60 Hz
7.5Â kA 50Â % conforming to IEC 60947-2 – 380…415 V AC 50/60 Hz
5Â kA 50Â % conforming to IEC 60947-2 – 440 V AC 50/60 Hz
7500Â A 75Â % conforming to EN 60898-1 – 400 V AC 50/60 Hz
7500Â A 75Â % conforming to IEC 60898-1 – 400 V AC 50/60 Hz
21Â kA 50Â % conforming to IEC 60947-2 – 12…133 V AC 50/60 Hz
21Â kA 50Â % conforming to EN 60947-2 – 12…133 V AC 50/60 Hz
15Â kA 100Â % conforming to IEC 60947-2 – 72…125 V DC
15Â kA 100Â % conforming to EN 60947-2 – 72…125 V DC[Ui] rated insulation voltage 500Â V AC 50/60 Hz conforming to EN 60947-2
500Â V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6Â kV conforming to EN 60947-2
6 kV conforming to IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Fixedmounting support DIN railcomb busbar and distribution block compatibility Top or bottom: YES9 mm pitches 4height 85 mmwidth 36 mmdepth 78.5 mmnet weight 0.25 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesconnections – terminals Single terminal (top or bottom) 1…35 mm² rigid
Single terminal (top or bottom) 1…25 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 3.5 N.m top or bottomearth-leakage protection Separate blockSKU: n/a -
CABLE AND CABLE MANAGEMENT, Electro, SINGLE CORE WIRE
Doncaster Cables 10mm Single Core – Black
Product Description
Manufactured to BS 6004:2012 Table 3
Annealed Stranded Copper Conductor / PVC Insulated / PVC Sheathed. 300/500V
Designed for use in light industrial and domestic wiring. These cables are particularly suited for installation as meter tails and are intended for fixed installation in dry or damp premises.
These cables can be installed in conduit, in cable trunking and in cable ducting. Or where there is deemed little risk of mechanical damage these cables can be clipped direct, on cable tray, embedded or in free air. These cables are not intended to be laid underground.
Product Details
 Harmonisation Code Nominal Cross Sectional Area of Conductor (mm2) Nominal Stranding of Conductor (mm) Nominal Radial Thickness of insulation (mm) Nominal Radial Thickness of sheath (mm) Overall Diameter Lower Limit (mm) Overall Diameter Upper Limit (mm) Approximate Weight(kg/km) National Type 1.0 1 / 1.13 0.6 0.8 3.8 4.5 26 National Type 1.5 1 / 1.38 0.7 0.8 4.2 4.9 35 National Type 2.5 1 / 1.78 0.8 0.8 4.8 5.8 55 National Type 4.0 7 / 0.85 0.8 0.9 5.4 6.8 75 National Type 6.0 7 / 1.04 0.8 0.9 6.0 7.4 95 National Type 10.0 7 / 1.35 1.0 0.9 7.2 8.8 155 National Type 16.0 7 / 1.70 1.0 1.0 8.4 10.5 225 National Type 25.0 7 / 2.14 1.2 1.1 10.0 12.5 340 National Type 35.0 7 / 2.52 1.2 1.1 11.0 13.5 445 SKU: n/a -
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONS
Switch disconnector iSW – 3P – 100 A – 415 V A9S65391
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONSSwitch disconnector iSW – 3P – 100 A – 415 V A9S65391
Main range Acti 9product name Acti 9 iSWproduct or component type Switch disconnectordevice short name ISWdevice application Control
Isolationpoles description 3Putilisation category AC-22Asuitability for isolation YesComplementary [Ie] rated operational current 100 A at 415 V AC 50/60 Hz[Ue] rated operational voltage 415 V AC 50/60 Hz[Icm] rated short-circuit making capacity 5 kA switch-disconnector alone[Icw] rated short-time withstand current 1500 A[Ui] rated insulation voltage 500 V AC 50/60 Hz[Uimp] rated impulse withstand voltage 6 kVcontrol type Togglelocal signalling ON/OFF indicationcontact position indicator Yesmounting mode Fixedmounting support DIN railcomb busbar and distribution block compatibility Top or bottom: YES9 mm pitches 6height 85 mmwidth 54 mmdepth 73 mmcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesconnections – terminals Tunnel type terminals (top or bottom) – <= 1 x 50 mm² – rigid
Tunnel type terminals (top or bottom) – <= 1 x 35 mm² – flexible
Tunnel type terminals (top or bottom) – <= 1 x 35 mm² – flexible with ferrulewire stripping length 9 mmtightening torque 3.5 N.mEnvironment standards IEC 60947-3
EN 60947-3IP degree of protection IP20pollution degree 3tropicalisation 2relative humidity 95 % at 55 °Cambient air temperature for operation -25…60 °Cambient air temperature for storage -40…85 °CSKU: n/a
There are no reviews yet.