Schneider Circuit Breakers, SCHNEIDER SECTIONS
Switch disconnector iSW – 2P – 63 A – 415 V ISOLATOR SWITCH A9S65263
range |
Acti 9
|
|
---|---|---|
product name |
Acti 9 iSW
|
|
product or component type |
Switch disconnector
|
|
device short name |
ISW
|
|
device application |
Isolation
Control |
|
poles description |
2P
|
|
utilisation category |
AC-22A
|
|
suitability for isolation |
Yes
|
[Ie] rated operational current |
63 A at 415 V AC 50/60 Hz
|
|
---|---|---|
[Ue] rated operational voltage |
415 V AC 50/60 Hz
|
|
[Icm] rated short-circuit making capacity |
4.2 kA switch-disconnector alone
|
|
[Icw] rated short-time withstand current |
1260 A
|
|
[Ui] rated insulation voltage |
500 V AC 50/60 Hz
|
|
[Uimp] rated impulse withstand voltage |
6 kV
|
|
control type |
Toggle
|
|
local signalling |
ON/OFF indication
|
|
contact position indicator |
Yes
|
|
mounting mode |
Fixed
|
|
mounting support |
DIN rail
|
|
comb busbar and distribution block compatibility |
Top or bottom: YES
|
|
9 mm pitches |
4
|
|
height |
85 mm
|
|
width |
36 mm
|
|
depth |
73 mm
|
|
colour |
White
|
|
mechanical durability |
20000 cycles
|
|
electrical durability |
15000 cycles
|
|
connections – terminals |
Tunnel type terminals (top or bottom) – <= 1 x 50 mm² – rigid
Tunnel type terminals (top or bottom) – <= 1 x 35 mm² – flexible Tunnel type terminals (top or bottom) – <= 1 x 35 mm² – flexible with ferrule |
|
wire stripping length |
9 mm
|
|
tightening torque |
3.5 N.m
|
₦6,500.00
Compare-
CHINT
CHINT NXC Series 3 pole AC Contactor
The new NXC AC contactors feature a novel appearance and a compact structure. They are mainly used for frequent starts and control of AC motors as well as remote circuit making /breaking. They can also be combined with appropriate thermal overload relays to form electromagnetic starters.
DESCRIPTION
- The new NXC AC contactors feature a novel appearance and a compact structure. They are mainly used for frequent starts and control of AC motors as well as remote circuit making /breaking.
- They can also be combined with appropriate thermal overload relays to form electromagnetic starters.
- Compliant standards: IEC/EN 60947-1, IEC/EN 60947-4-1, IEC/EN 60947-5-1
- Coll Voltage : 240V
SKU: n/a -
ELECTRICAL FITTINGS, Electro, HOME&OFFICE LIGHTING, INDOOR LIGHTS, INTERIOR LIGHTING, LED LIGHTS, LIGHTING, OUTDOOR FITTINGS
PHILIPS BULKHEAD WT045C LED12/CW PSU CFW L1065 (Cool White) Essential Smartbright Bulkhead
ELECTRICAL FITTINGS, Electro, HOME&OFFICE LIGHTING, INDOOR LIGHTS, INTERIOR LIGHTING, LED LIGHTS, LIGHTING, OUTDOOR FITTINGSPHILIPS BULKHEAD WT045C LED12/CW PSU CFW L1065 (Cool White) Essential Smartbright Bulkhead
Light Technical
- Luminous Flux – 960 lm
- Correlated Color Temperature (Nom) – 6500 K
- Luminous Efficacy (rated) (Nom) – 80 lm/W
- Color rendering index (CRI) – >70
- Beam angle of light source – 120 degree(s)
- Light source color – cool white
- Optical cover type – Polycarbonate bowl/cover
- Luminaire light beam spread – 100° x 120°
Mechanical and Housing
- Housing Material – Polypropylene
- Reflector material – Polycarbonate
- Optic material – Polycarbonate
- Optical cover material – Polycarbonate
- Fixation material – Polypropylene
- Housing Color – White
- Optical cover finish – Opal
- Overall height – 76 mm
- Overall diameter – 170 mm
SKU: n/a -
-
Schneider Circuit Breakers, SCHNEIDER SECTIONS
Acti9 iC60N 3P 3A C Miniature Circuit breaker A9F44303
Schneider Circuit Breakers, SCHNEIDER SECTIONSActi9 iC60N 3P 3A C Miniature Circuit breaker A9F44303
Main range Acti 9product name Disbo iC60product or component type Miniature circuit-breakerdevice short name IC60Npoles description 3Pnumber of protected poles 3[In] rated current 3 Anetwork type ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 50 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
50 kA Icu at 12…133 V AC 50/60 Hz conforming to EN/IEC 60947-2
50 kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2
25 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2
6000 A Icn at 415 V AC 50/60 Hz conforming to EN/IEC 60898-1
15 kA Icu at 100…133 V DC conforming to EN/IEC 60947-2utilisation category Category A conforming to EN/IEC 60947-2Complementary network frequency 50/60 Hz[Ue] rated operational voltage 440 V AC 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 50 kA 100 % conforming to EN/IEC 60947-2 – 220…240 V AC 50/60 Hz
50 kA 100 % conforming to EN/IEC 60947-2 – 12…133 V AC 50/60 Hz
50 kA 100 % conforming to EN/IEC 60947-2 – 380…415 V AC 50/60 Hz
25 kA 100 % conforming to EN/IEC 60947-2 – 440 V AC 50/60 Hz
6000 A 100 % conforming to EN/IEC 60898-1 – 415 V AC 50/60 Hz
15 kA 100 % conforming to EN/IEC 60947-2 – 100…133 V DClimitation class 3 conforming to EN/IEC 60947-2[Ui] rated insulation voltage 500 V AC 50/60 Hz[Uimp] rated impulse withstand voltage 6 kV conforming to EN/IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Clip-onmounting support Rail9 mm pitches 6height 85 mmwidth 54 mmdepth 78.5 mmnet weight 0.375 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesprovision for padlocking Padlockableconnections – terminals Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 2 N.m top or bottomearth-leakage protection Separate blockSKU: n/a -
CHINT
CHINT NXB63 Miniature Circuit Breaker 2pole
Overload protection, short circuit protection and isolation. It is widely used in building power distribution, industrial power distribution, as well as control and protection for a variety of equipment with operating current not exceeding 125A.
DESCRIPTION
- Compliance standard : IEC60898-1
- Rated Current : 6~63A Rated Voltage (V~) : 240/415
- Rated Frequency : 50/60 Hz
SKU: n/a -
There are no reviews yet.