Acti9 iC60N 2P 10A C Miniature Circuit breaker A9F44210
range |
Acti 9
|
|
---|---|---|
product name |
Disbo iC60
|
|
product or component type |
Miniature circuit-breaker
|
|
device short name |
IC60N
|
|
poles description |
2P
|
|
number of protected poles |
2
|
|
[In] rated current |
10 A
|
|
network type |
AC
|
|
trip unit technology |
Thermal-magnetic
|
|
curve code |
C
|
|
breaking capacity |
6 kA Icu at 100…133 V DC conforming to EN/IEC 60947-2
6000 A Icn at 415 V AC 50/60 Hz conforming to EN/IEC 60898-1 36 kA Icu at 12…133 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
|
utilisation category |
Category A conforming to EN/IEC 60947-2
|
network frequency |
50/60 Hz
|
|
---|---|---|
[Ue] rated operational voltage |
440 V AC 50/60 Hz
|
|
magnetic tripping limit |
8 x In +/- 20 %
|
|
[Ics] rated service breaking capacity |
27 kA 75 % conforming to EN/IEC 60947-2 – 12…133 V AC 50/60 Hz
15 kA 75 % conforming to EN/IEC 60947-2 – 220…240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 – 380…415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 – 440 V AC 50/60 Hz 6000 A 100 % conforming to EN/IEC 60898-1 – 415 V AC 50/60 Hz 6 kA 100 % conforming to EN/IEC 60947-2 – 100…133 V DC |
|
limitation class |
3 conforming to EN/IEC 60947-2
|
|
[Ui] rated insulation voltage |
500 V AC 50/60 Hz
|
|
[Uimp] rated impulse withstand voltage |
6 kV conforming to EN/IEC 60947-2
|
|
contact position indicator |
Yes
|
|
control type |
Toggle
|
|
local signalling |
Trip indicator
|
|
mounting mode |
Clip-on
|
|
mounting support |
Rail
|
|
9 mm pitches |
4
|
|
height |
85 mm
|
|
width |
36 mm
|
|
depth |
78.5 mm
|
|
net weight |
0.25 kg
|
|
colour |
White
|
|
mechanical durability |
20000 cycles
|
|
electrical durability |
10000 cycles
|
|
provision for padlocking |
Padlockable
|
|
connections – terminals |
Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexible |
|
wire stripping length |
14 mm for top or bottom connection
|
|
tightening torque |
2 N.m top or bottom
|
|
earth-leakage protection |
Separate block
|
standards |
EN/IEC 60947-2
EN/IEC 60898-1 |
|
---|---|---|
IP degree of protection |
IP20 conforming to IEC 60529
|
|
pollution degree |
3 conforming to EN/IEC 60947-2
|
|
tropicalisation |
2 conforming to IEC 60068-1
|
|
relative humidity |
95 % at 55 °C
|
|
ambient air temperature for operation |
-35…70 °C
|
|
ambient air temperature for storage |
-40…85 °C
|
₦20,800.00
Compare-
Schneider "Consort Dado" Trunking, SCHNEIDER SECTIONS
Mita – Consort Dado – flat tee – 100 x 50 mm CTT105W
Schneider "Consort Dado" Trunking, SCHNEIDER SECTIONSMita – Consort Dado – flat tee – 100 x 50 mm CTT105W
Main range of product Mitaproduct name Consort Dadoproduct or component type T-piececolour tint Whitequantity per set Set of 1Complementary fixing mode Clip-onmaterial with surface finish UPVC (unplasticized polyvinyl chloride)Environment ambient air temperature for operation -5…60 °CPacking Units Unit Type of Package 1 PCENumber of Units in Package 1 1Package 1 Weight 117 gPackage 1 Height 14 cmPackage 1 width 5.5 cmPackage 1 Length 17.5 cmSKU: n/a -
Electro, SOCKETS, SOCKETS & SWITCHES
BG Nexus FP 45A Cooker Unit c/w Skt./Neon-B/Steel (FBS70)
About BG
BG Electrical is an integral part of the Luceco plc group of companies.
Other brands include Luceco, Masterplug and Ross, together they provide a “One Stop Shop” for lighting and electrical accessories. With over 70 years of experience in the manufacture and distribution of electrical accessories, BG has gained an enviable reputation.- Switch Types: 45A Double Pole Switch,13A Single Plug Socket
- Mounting Box Depth: 47mm minimum
- Finish: Brushed Steel
- Style: Metal Plate
SKU: n/a -
ELECTRICAL INDUSTRIAL, TRANSFORMER
MEKSAN Transformer 200kVA 11/415kV
Meksan Transformer manufacture distribution and power transformer from 50 kVA up to 50 MVA. Our products are produced in accordance with the TS 267 and the IEC60076 standards. Our production is documented with the TSE (Türkish Standard Institue) standards confortmity, ISO 9001:2000 quality system and ISO 14001 environmental management system certificates.
SKU: n/a -
CIRCUIT BREAKERS
Circuit breaker Easypact EZC100H – TMD – 63 A – 4 poles 3d
Main range of product EasyPactproduct or component type Circuit breakerdevice short name Easypact EZC100Hcircuit breaker name Easypact EZC100Hdevice application Distributionpoles description 4Pprotected poles description 3tnetwork type AC
DCnetwork frequency 50/60 Hz[In] rated current 100 A at 40 °C[Ui] rated insulation voltage 690 V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947-2[Ue] rated operational voltage 550 V AC 50/60 Hz conforming to IEC 60947-2
250 V DC conforming to IEC 60947-2breaking capacity code Hbreaking capacity 10 kA Icu at 125 V DC 1P conforming to IEC 60947-2
10 kA Icu at 250 V DC 2P conforming to IEC 60947-2
10 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2
100 kA Icu at 110…130 V AC 50/60 Hz conforming to IEC 60947-2
20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
30 kA Icu at 380…400 V AC 50/60 Hz conforming to IEC 60947-2
30 kA Icu at 415 V AC 50/60 Hz conforming to IEC 60947-2[Ics] rated service breaking capacity 5 kA at 125 V DC conforming to IEC 60947-2
5 kA at 250 V DC conforming to IEC 60947-2
5 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
2.5 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2
15 kA at 380…400 V AC 50/60 Hz conforming to IEC 60947-2
25 kA at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
50 kA at 110…130 V AC 50/60 Hz conforming to IEC 60947-2
7.5 kA at 415 V AC 50/60 Hz conforming to IEC 60947-2suitability for isolation Yes conforming to IEC 60947-2utilisation category Category Atrip unit name TM-Dtrip unit technology Thermal-magnetictrip unit rating 63 A at 50 °Cprotection type Overload protection
Short-circuit protectionpollution degree 3 conforming to IEC 60947Complementary control type Togglemounting mode Fixedmounting support Backplateupside connection Frontdownside connection Frontmechanical durability 8500 cycleselectrical durability Category A: 1500 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2connection pitch 25 mmlocal signalling Positive contact indicationneutral protection setting Without protectionearth-leakage protection Withoutheight 130 mmwidth 100 mmdepth 60 mmSKU: n/a -
Electro, Low Voltage Products and Systems, SCHNEIDER SECTIONS
EZC250N3160 Circuit breaker Easypact EZC250N – TMD – 160 A – 3 poles 3d
Electro, Low Voltage Products and Systems, SCHNEIDER SECTIONSEZC250N3160 Circuit breaker Easypact EZC250N – TMD – 160 A – 3 poles 3d
Main range of product EasyPactproduct or component type Circuit breakerdevice short name Easypact EZC250Ncircuit breaker name Easypact EZC250Ndevice application Distributionpoles description 3Pprotected poles description 3tnetwork type DC
ACnetwork frequency 50/60 Hz[In] rated current 250 A at 40 °C[Ui] rated insulation voltage 690 V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947-2[Ue] rated operational voltage 550 V AC 50/60 Hz conforming to IEC 60947-2
250 V DC conforming to IEC 60947-2breaking capacity code Nbreaking capacity 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 110…130 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
20 kA Icu at 125 V DC 1P conforming to IEC 60947-2
20 kA Icu at 250 V DC 2P conforming to IEC 60947-2
25 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2
25 kA Icu at 400…415 V AC 50/60 Hz conforming to IEC 60947-2
8 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2[Ics] rated service breaking capacity 10 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
25 kA at 110/130 V AC 50/60 Hz conforming to IEC 60947-2
10 kA at 125 V DC conforming to IEC 60947-2
10 kA at 250 V DC conforming to IEC 60947-2
25 kA at 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2
4 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2
12.5 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2
12.5 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2suitability for isolation Yes conforming to IEC 60947-2utilisation category Category Atrip unit name TM-Dtrip unit technology Thermal-magnetictrip unit rating 160 A at 50 °Cprotection type Overload protection
Short-circuit protectionpollution degree 3 conforming to IEC 60664-1
3 conforming to IEC 947-1Complementary control type Togglemounting mode Fixedmounting support Backplateupside connection Frontdownside connection Frontmechanical durability 10000 cycleselectrical durability Category A: 5000 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2connection pitch 35 mmlocal signalling Positive contact indicationneutral protection setting Without protectionearth-leakage protection Withoutheight 165 mmwidth 105 mmdepth 60 mmSKU: n/a -
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONS
Miniature circuit-breaker, Acti9 iC60H, 2P, 6 A, C curve, 10000 A (IEC 60898-1), 15 kA (IEC 60947-2) A9F84206
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONSMiniature circuit-breaker, Acti9 iC60H, 2P, 6 A, C curve, 10000 A (IEC 60898-1), 15 kA (IEC 60947-2) A9F84206
Main device application Distributionrange Acti 9product name Acti 9 iC60product or component type Miniature circuit-breakerdevice short name IC60Hpoles description 2Pnumber of protected poles 2[In] rated current 6 Anetwork type DC
ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
42 kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2
10 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2
15 kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2
30 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
15 kA Icu at <= 125 V DC conforming to EN/IEC 60947-2
42 kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2utilisation category Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2suitability for isolation Yes conforming to EN 60898-1
Yes conforming to EN 60947-2
Yes conforming to IEC 60898-1
Yes conforming to IEC 60947-2standards IEC 60947-2
IEC 60898-1
EN 60947-2
EN 60898-1Complementary network frequency 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 15 kA 50 % conforming to EN 60947-2 – 220…240 V AC 50/60 Hz
7.5 kA 50 % conforming to EN 60947-2 – 380…415 V AC 50/60 Hz
5 kA 50 % conforming to EN 60947-2 – 440 V AC 50/60 Hz
15 kA 50 % conforming to IEC 60947-2 – 220…240 V AC 50/60 Hz
7.5 kA 50 % conforming to IEC 60947-2 – 380…415 V AC 50/60 Hz
5 kA 50 % conforming to IEC 60947-2 – 440 V AC 50/60 Hz
7500 A 75 % conforming to EN 60898-1 – 400 V AC 50/60 Hz
7500 A 75 % conforming to IEC 60898-1 – 400 V AC 50/60 Hz
21 kA 50 % conforming to IEC 60947-2 – 12…133 V AC 50/60 Hz
21 kA 50 % conforming to EN 60947-2 – 12…133 V AC 50/60 Hz
15 kA 100 % conforming to IEC 60947-2 – 72…125 V DC
15 kA 100 % conforming to EN 60947-2 – 72…125 V DClimitation class 3 conforming to EN 60898-1
3 conforming to IEC 60898-1[Ui] rated insulation voltage 500 V AC 50/60 Hz conforming to EN 60947-2
500 V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6 kV conforming to EN 60947-2
6 kV conforming to IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Fixedmounting support DIN railcomb busbar and distribution block compatibility Top or bottom: YES9 mm pitches 4height 85 mmwidth 36 mmdepth 78.5 mmnet weight 0.25 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesconnections – terminals Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 2 N.m top or bottomearth-leakage protection Separate blockSKU: n/a
There are no reviews yet.