Acti9 iC60N 2P 25A C Miniature Circuit breaker A9F44225
range |
Acti 9
|
|
---|---|---|
product name |
Disbo iC60
|
|
product or component type |
Miniature circuit-breaker
|
|
device short name |
IC60N
|
|
poles description |
2P
|
|
number of protected poles |
2
|
|
[In] rated current |
25 A
|
|
network type |
AC/DC
|
|
trip unit technology |
Thermal-magnetic
|
|
curve code |
C
|
|
breaking capacity |
6 kA Icu at 100…133 V DC conforming to EN/IEC 60947-2
6000 A Icn at 415 V AC 50/60 Hz conforming to EN/IEC 60898-1 36 kA Icu at 12…133 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
|
utilisation category |
Category A conforming to EN/IEC 60947-2
|
network frequency |
50/60 Hz
|
|
---|---|---|
[Ue] rated operational voltage |
440 V AC 50/60 Hz
|
|
magnetic tripping limit |
8 x In +/- 20 %
|
|
[Ics] rated service breaking capacity |
27 kA 75 % conforming to EN/IEC 60947-2 – 12…133 V AC 50/60 Hz
15 kA 75 % conforming to EN/IEC 60947-2 – 220…240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 – 380…415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 – 440 V AC 50/60 Hz 6000 A 100 % conforming to EN/IEC 60898-1 – 415 V AC 50/60 Hz 6 kA 100 % conforming to EN/IEC 60947-2 – 100…133 V DC |
|
limitation class |
3 conforming to EN/IEC 60947-2
|
|
[Ui] rated insulation voltage |
500 V AC 50/60 Hz
|
|
[Uimp] rated impulse withstand voltage |
6 kV conforming to EN/IEC 60947-2
|
|
contact position indicator |
Yes
|
|
control type |
Toggle
|
|
local signalling |
Trip indicator
|
|
mounting mode |
Clip-on
|
|
mounting support |
Rail
|
|
9 mm pitches |
4
|
|
height |
85 mm
|
|
width |
36 mm
|
|
depth |
78.5 mm
|
|
net weight |
0.25 kg
|
|
colour |
White
|
|
mechanical durability |
20000 cycles
|
|
electrical durability |
10000 cycles
|
|
provision for padlocking |
Padlockable
|
|
connections – terminals |
Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexible |
|
wire stripping length |
14 mm for top or bottom connection
|
|
tightening torque |
2 N.m top or bottom
|
|
earth-leakage protection |
Separate block
|
₦20,800.00
Compare-
Electro, INDOOR LIGHTS, LED LIGHTS, LIGHTING
Philips Ecofit Ledtubes T8 5ft LEDtube 1500mm 20W 765 T8 AP SL G Philip
Electro, INDOOR LIGHTS, LED LIGHTS, LIGHTINGPhilips Ecofit Ledtubes T8 5ft LEDtube 1500mm 20W 765 T8 AP SL G Philip
Ecofit Ledtubes T8
LEDtube 1500mm 20W 765 T8 AP SL G
Upgrade to efficient, long-lasting LED tubes with the Ecofit LED tubes. Ecofit LED tubes are a fast and easy way to replace your old fluorescent tubes with modern, efficient LED technology. Good quality of light with a natural lighting effect for use in general lighting applications with low initial investment – an environmentally friendly solution.
Light Technical
Colour Code – 765 [ CCT of 6,500 K]
Technical Beam Angle (Nom) – 240 °
Lamp Luminous Flux 25°C EL (Nom) – 2000 lm
Colour Designation – Cool Daylight
Colour Temperature, horizontal (Nom) – 6500 K
Lamp Luminous Ecacy EM (Nom) – 100.00 lm/W
Colour consistency – <7
Colour Rendering Index,horiz (Nom) – 70
LLMF at end of nominal lifetime (nom.) – 70 %SKU: n/a -
Electro, LIGHT SWITCHES & ELECTRICAL SOCKETS
Lisse – Fuse connection unit – 1 gang – 13 A – white moulded GGBL5000
Electro, LIGHT SWITCHES & ELECTRICAL SOCKETSLisse – Fuse connection unit – 1 gang – 13 A – white moulded GGBL5000
Main range Lisseaesthetic name White mouldedproduct or component type Fuse connection unitdevice presentation Complete productcolour tint white mouldedquantity per set Set of 10Complementary pilot light without LEDnumber of gangs 1 gangmaterial Urea (carbamide)device mounting Wall mountedfixing mode By screwsrated current 13 A at 250 V ACconnections – terminals Screw terminalstype of packing Cartonwidth 87 mmheight 87 mmdepth 25 mmnet weight 0.091 kgSKU: n/a -
ELECTRICAL INDUSTRIAL, TRANSFORMER
MEKSAN Transformer 750kVA 33/415kV
Meksan Transformer manufacture distribution and power transformer from 50 kVA up to 50 MVA. Our products are produced in accordance with the TS 267 and the IEC60076 standards. Our production is documented with the TSE (Türkish Standard Institue) standards confortmity, ISO 9001:2000 quality system and ISO 14001 environmental management system certificates.
SKU: n/a -
-
CHINT
Voltage Monitoring Relay XJ3-D
XJ3 series phase failure phase sequence protection relay
www.finglai.comModel number ad parametersModel number XJ3-G XJ3-S XJ3-D Related product Order Order Visiting… Phase failure protection √ √ √ Phase wrong protection √ √ √ Overvoltage protection Χ Χ 380V-460V 1.5s-4s(Adjustable) Undervoltage protection Χ Χ 300V-380V 2s-9s (Adjustable) Contact form SPST-NO and SPST-NC SPST-NO and SPST-NC SPDT Action delay time 2s max 2s max 2s max External dimensions 85x46x110 mm 85x46x110 mm 70.5×45.5×115 mm Mounting type Device or din rail Device or din rail 35mm din rail or punch Model number XJ3 series Supply voltage 380VAC 50Hz Contact rating Ue/le AC-15 380V/0.95A Ith 5A Electrical life 1×105 Mechanical life 1×106 Operational temperature -5°C-40°C SKU: n/a -
LIGHT SWITCHES & ELECTRICAL SOCKETS
32A 1 Gang Full-Flat Double Rocker Switch with Neon, Sliver Bronze E8431D32_SZ
LIGHT SWITCHES & ELECTRICAL SOCKETS32A 1 Gang Full-Flat Double Rocker Switch with Neon, Sliver Bronze E8431D32_SZ
Main range ZENceloproduct or component type Switchload type Resistivecolour tint Silver bronzecover frame colour tint Silver bronzeComplementary device mounting Surface
Flushrated current 32 A at 250 V AC 50/60 Hzlocal signalling Indicator light, neon (amber)number of gangs 1 gangmaterial Polycarbonate + GF 20 %: grid plate
Polycarbonate: base
Polycarbonate: cover
Polycarbonate: surroundconnections – terminals Brass rod terminalsembedding depth 22 mmwidth 87 mmheight 87 mmdepth 30.2 mmSKU: n/a
There are no reviews yet.