Schneider Circuit Breakers, SCHNEIDER SECTIONS
Acti9 iC60N 2P 2A C Miniature Circuit breaker A9F44202
range |
Acti 9
|
|
---|---|---|
product name |
Disbo iC60
|
|
product or component type |
Miniature circuit-breaker
|
|
device short name |
IC60N
|
|
poles description |
2P
|
|
number of protected poles |
2
|
|
[In] rated current |
2 A
|
|
network type |
AC
|
|
trip unit technology |
Thermal-magnetic
|
|
curve code |
C
|
|
breaking capacity |
50 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
50 kA Icu at 12…133 V AC 50/60 Hz conforming to EN/IEC 60947-2 50 kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2 25 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 6 kA Icu at 100…133 V DC conforming to EN/IEC 60947-2 6000 A Icn at 415 V AC 50/60 Hz conforming to EN/IEC 60898-1 |
|
utilisation category |
Category A conforming to EN/IEC 60947-2
|
network frequency |
50/60 Hz
|
|
---|---|---|
[Ue] rated operational voltage |
440 V AC 50/60 Hz
|
|
magnetic tripping limit |
8 x In +/- 20 %
|
|
[Ics] rated service breaking capacity |
50 kA 100 % conforming to EN/IEC 60947-2 – 220…240 V AC 50/60 Hz
50 kA 100 % conforming to EN/IEC 60947-2 – 12…133 V AC 50/60 Hz 50 kA 100 % conforming to EN/IEC 60947-2 – 380…415 V AC 50/60 Hz 25 kA 100 % conforming to EN/IEC 60947-2 – 440 V AC 50/60 Hz 6000 A 100 % conforming to EN/IEC 60898-1 – 415 V AC 50/60 Hz 6 kA 100 % conforming to EN/IEC 60947-2 – 100…133 V DC |
|
limitation class |
3 conforming to EN/IEC 60947-2
|
|
[Ui] rated insulation voltage |
500 V AC 50/60 Hz
|
|
[Uimp] rated impulse withstand voltage |
6 kV conforming to EN/IEC 60947-2
|
|
contact position indicator |
Yes
|
|
control type |
Toggle
|
|
local signalling |
Trip indicator
|
|
mounting mode |
Clip-on
|
|
mounting support |
Rail
|
|
9 mm pitches |
4
|
|
height |
85 mm
|
|
width |
36 mm
|
|
depth |
78.5 mm
|
|
net weight |
0.25 kg
|
|
colour |
White
|
|
mechanical durability |
20000 cycles
|
|
electrical durability |
10000 cycles
|
|
provision for padlocking |
Padlockable
|
|
connections – terminals |
Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexible |
|
wire stripping length |
14 mm for top or bottom connection
|
|
tightening torque |
2 N.m top or bottom
|
|
earth-leakage protection |
Separate block
|
standards |
EN/IEC 60898-1
EN/IEC 60947-2 |
|
---|---|---|
IP degree of protection |
IP20 conforming to IEC 60529
|
|
pollution degree |
3 conforming to EN/IEC 60947-2
|
|
tropicalisation |
2 conforming to IEC 60068-1
|
|
relative humidity |
95 % at 55 °C
|
|
ambient air temperature for operation |
-35…70 °C
|
|
ambient air temperature for storage |
-40…85 °C
|
₦11,960.00
Compare-
Electro, LED LIGHTS, LIGHTING, OUTDOOR LIGHTS
PHILIP CANOPY LIGHT BBP500 G2 LED125/NW PSU S-WB 90W Philips
Electro, LED LIGHTS, LIGHTING, OUTDOOR LIGHTSPHILIP CANOPY LIGHT BBP500 G2 LED125/NW PSU S-WB 90W Philips
Specifications
- General Information
-
Beam angle of light source – °Light source color 840 neutral whiteLight source replaceable NoNumber of gear units 1 unitDriver/power unit/transformer Power supply unitDriver included YesOptic type Wide beamOptical cover/lens type Tempered glassLuminaire light beam spread 110°Control interface –Connection Flying leads/wiresCable Cable 0.3 m without plugProtection class IEC Safety class IGlow-wire test Temperature 650 °C, duration 5 sFlammability mark For mounting on normally flammable surfacesCE mark CE markENEC mark –Warranty period 3 yearsConstant light output NoNumber of products on MCB of 16 A type B 4EU RoHS compliant NoLight source engine type LED - Operating and Electrical
-
Input Voltage 220 to 240 VInput Frequency 50 to 60 HzInrush current 46 AInrush time 440 msPower Factor (Min) 0.95 - Controls and Dimming
-
Dimmable No - Mechanical and Housing
-
Housing Material Aluminum die castReflector material –Optic material PolycarbonateOptical cover/lens material Tempered glassFixation material –Optical cover/lens finish ClearOverall length 400 mmOverall width 400 mmColor White - Approval and Application
-
Ingress protection code IP65 [ Dust penetration-protected, jet-proof]Mech. impact protection code IK07 [ 2 J reinforced] - Initial Performance (IEC Compliant)
-
Initial luminous flux (system flux) 12500 lmLuminous flux tolerance +/-10%Initial LED luminaire efficacy 139 lm/WInit. Corr. Color Temperature 4000 KInit. Color Rendering Index >80Initial chromaticity (0.38.0.38)SDCM<5Initial input power 90 WPower consumption tolerance +/-10% - Over Time Performance (IEC Compliant)
-
Median useful life L70B50 50000 hMedian useful life L80B50 40000 hMedian useful life L90B50 30000 h - Application Conditions
-
Ambient temperature range -40 to +45 °CMaximum dim level Not applicableSuitable for random switching No - Product Data
-
Full product code 911401538751Order product name BBP500 G2 LED125/NW PSU S-WBOrder code 911401538751Numerator – Quantity Per Pack 1Numerator – Packs per outer box 1Material Nr. (12NC) 911401538751Net Weight (Piece) 6.099 kg
SKU: n/a -
Electro, SOCKETS & SWITCHES, SWITCHES
BG BRASS GEORGIAN LIGHT SWITCH PLATE – DOUBLE 3 GANG 2 WAY
BRASS GEORGIAN LIGHT SWITCH PLATE – DOUBLE 3 GANG 2 WAY
AT A GLANCE…- Top quality Brass finish – lightly lacquered to prevent finger marks
- Matching Brass rocker switch
- No visible plastic around switches
- Specification: 3 Gang, 2 Way (10AX)
- Requires a 16mm metal wall box
- Supplied with colour coded fixing screws
SKU: Kalo ABB 4 Gang 1 Way Switch, 4 Gang 2 Way Switch -
ACCESSORIES, ELECTRICAL INDUSTRIAL
Xpelair 4inches Window Mounted Extractor Fan
Extractor Fan
Suitable for both single and double glazed windows
Feature a pullcord for easy on/off operation.
Shutters can be set partially open to provide background trickle ventilation
Motor isolated when the cover is removed
Brilliant white interior and brown exterior grille
Quick release front cover and impeller
Auto shutter model has a thermo actuator opening/closing operation which is ideal for use with a remote humidistat. Actuator time delay 30s on opening, 3min. on closing
On-site warranty
230 Vac mains powered.SKU: Xpelair 90800AW Window Mounted Extractor Fan-1-1 -
LIGHT SWITCHES & ELECTRICAL SOCKETS
20A 1 Gang Full-Flat Double Pole Switch with Neon, Sliver Bronze E8431D20_SZ
LIGHT SWITCHES & ELECTRICAL SOCKETS20A 1 Gang Full-Flat Double Pole Switch with Neon, Sliver Bronze E8431D20_SZ
Main range ZENceloproduct or component type Switchload type Inductivecolour tint Silver bronzecover frame colour tint Silver bronzeComplementary device mounting Surface
Flushrated current 20 A at 250 V AC 50/60 Hznumber of gangs 1 gangmaterial Polycarbonate + GF 20 %: grid plate
Polycarbonate: base
Polycarbonate: cover
Polycarbonate: dolly
Polycarbonate: surroundconnections – terminals Brass rod terminalsembedding depth 23 mmwidth 87 mmheight 87 mmdepth 31.5 mmSKU: n/a -
Schneider Circuit Breakers, SCHNEIDER SECTIONS
Miniature circuit-breaker, Acti9 iC60H, 2P, 20 A, C curve, 10000 A (IEC 60898-1), 15 kA (IEC 60947-2) A9F84220
Schneider Circuit Breakers, SCHNEIDER SECTIONSMiniature circuit-breaker, Acti9 iC60H, 2P, 20 A, C curve, 10000 A (IEC 60898-1), 15 kA (IEC 60947-2) A9F84220
Main device application Distributionrange Acti 9product name Acti 9 iC60product or component type Miniature circuit-breakerdevice short name IC60Hpoles description 2Pnumber of protected poles 2[In] rated current 20 Anetwork type AC
DCtrip unit technology Thermal-magneticcurve code Cbreaking capacity 10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
42 kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2
10 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2
15 kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2
30 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
15 kA Icu at <= 125 V DC conforming to EN/IEC 60947-2
42 kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2utilisation category Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2suitability for isolation Yes conforming to EN 60898-1
Yes conforming to EN 60947-2
Yes conforming to IEC 60898-1
Yes conforming to IEC 60947-2standards IEC 60898-1
EN 60898-1
IEC 60947-2
EN 60947-2Complementary network frequency 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 15 kA 50 % conforming to EN 60947-2 – 220…240 V AC 50/60 Hz
7.5 kA 50 % conforming to EN 60947-2 – 380…415 V AC 50/60 Hz
5 kA 50 % conforming to EN 60947-2 – 440 V AC 50/60 Hz
15 kA 50 % conforming to IEC 60947-2 – 220…240 V AC 50/60 Hz
7.5 kA 50 % conforming to IEC 60947-2 – 380…415 V AC 50/60 Hz
5 kA 50 % conforming to IEC 60947-2 – 440 V AC 50/60 Hz
7500 A 75 % conforming to EN 60898-1 – 400 V AC 50/60 Hz
7500 A 75 % conforming to IEC 60898-1 – 400 V AC 50/60 Hz
21 kA 50 % conforming to IEC 60947-2 – 12…133 V AC 50/60 Hz
21 kA 50 % conforming to EN 60947-2 – 12…133 V AC 50/60 Hz
15 kA 100 % conforming to IEC 60947-2 – 72…125 V DC
15 kA 100 % conforming to EN 60947-2 – 72…125 V DClimitation class 3 conforming to EN 60898-1
3 conforming to IEC 60898-1[Ui] rated insulation voltage 500 V AC 50/60 Hz conforming to EN 60947-2
500 V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6 kV conforming to EN 60947-2
6 kV conforming to IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Fixedmounting support DIN railcomb busbar and distribution block compatibility Top or bottom: YES9 mm pitches 4height 85 mmwidth 36 mmdepth 78.5 mmnet weight 0.25 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesconnections – terminals Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 2 N.m top or bottomearth-leakage protection Separate blockSKU: n/a
There are no reviews yet.