Acti9 iC60N 2P 32A C Miniature Circuit breaker A9F44232
range |
Acti 9
|
|
---|---|---|
product name |
Disbo iC60
|
|
product or component type |
Miniature circuit-breaker
|
|
device short name |
IC60N
|
|
poles description |
2P
|
|
number of protected poles |
2
|
|
[In] rated current |
32 A
|
|
network type |
AC/DC
|
|
trip unit technology |
Thermal-magnetic
|
|
curve code |
C
|
|
breaking capacity |
6 kA Icu at 100…133 V DC conforming to EN/IEC 60947-2
6000 A Icn at 415 V AC 50/60 Hz conforming to EN/IEC 60898-1 36 kA Icu at 12…133 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
|
utilisation category |
Category A conforming to EN/IEC 60947-2
|
network frequency |
50/60 Hz
|
|
---|---|---|
[Ue] rated operational voltage |
440 V AC 50/60 Hz
|
|
magnetic tripping limit |
8 x In +/- 20 %
|
|
[Ics] rated service breaking capacity |
27 kA 75 % conforming to EN/IEC 60947-2 – 12…133 V AC 50/60 Hz
15 kA 75 % conforming to EN/IEC 60947-2 – 220…240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 – 380…415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 – 440 V AC 50/60 Hz 6000 A 100 % conforming to EN/IEC 60898-1 – 415 V AC 50/60 Hz 6 kA 100 % conforming to EN/IEC 60947-2 – 100…133 V DC |
|
limitation class |
3 conforming to EN/IEC 60947-2
|
|
[Ui] rated insulation voltage |
500 V AC 50/60 Hz
|
|
[Uimp] rated impulse withstand voltage |
6 kV conforming to EN/IEC 60947-2
|
|
contact position indicator |
Yes
|
|
control type |
Toggle
|
|
local signalling |
Trip indicator
|
|
mounting mode |
Clip-on
|
|
mounting support |
Rail
|
|
9 mm pitches |
4
|
|
height |
85 mm
|
|
width |
36 mm
|
|
depth |
78.5 mm
|
|
net weight |
0.25 kg
|
|
colour |
White
|
|
mechanical durability |
20000 cycles
|
|
electrical durability |
10000 cycles
|
|
provision for padlocking |
Padlockable
|
|
connections – terminals |
Single terminal (top or bottom) 1…35 mm² rigid
Single terminal (top or bottom) 1…25 mm² flexible |
|
wire stripping length |
14 mm for top or bottom connection
|
|
tightening torque |
3.5 N.m top or bottom
|
|
earth-leakage protection |
Separate block
|
₦20,800.00
Compare-
CHINT
CHINT Kwh Meter Single
DDSU666 series three phase three wire electronic energy meter (DIN Rail) Summary :
DDSU666 series electronic energy meter is designed for power monitoring and energy measurement such as power system, communication industry, construction industry, etc. to be a new generation of programmable.
DDSU666 series three phase three wire electronic energy meter (DIN Rail)
Summary:
DDSU666 series electronic energy meter is designed for power monitoring and energy measurement such as power system, communication industry, construction industry, etc. to be a new generation of programmable intelligent instrument, integrated with measurement and communication function, mainly used for real-time measurement and display for the electrical parameters such as voltage, current, active power, reactive power, frequency, power factor, energy in the electrical circuit, etc.
1、Main functions and characteristics
◆DIN35mm Standard DIN-Rail, seven modulus with segment LCD display
◆Measurement function: Characterized with measurement for three phase three wire voltage, current, frequency, active power, power factor, active energy and reactive energy
◆communication function: RS485 communication interface, supporting DL/T645-2007 protocol, customizable for MODBUS-RTU protocol
◆Multi-rate function: it supports four rates including top, peak, flat, valley rate.
SKU: n/a -
CHINT
NX8 – MCB CHINT . ELECTRIC BOX 15way
The MCB CHINT NX8 plastic electrical cabinet box is compact, sturdy, and has a high finish.
Can be used as a wall cabinet or used as a floating cabinet due to its versatile design. There are error lights, power failure.
ABS plastic helps to withstand factors such as heat, sunlight, increasing the life of the cabinet. The lid of the cabinet is made of transparent PC plastic, making it easy to see the equipment inside. Available with 4-sided wiring hole.
Standard DIN Rail, convenient to connect and install equipment
Parameters of MCB CHINT NX8 . plastic electrical cabinet box
- Material: ABS/PC . plastic
- Type: Wall mounted plastic electrical cabinet
- Protection level: IP30
- Meets standards: IEC/EN 60439-3 (IEC/EN 60670-24)
- Application: in civil electricity, industrial electricity, solar power
SKU: n/a -
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONS
Easy9 miniature circuit breaker- 2P – 6 A – C curve – 6000 A – 230 V EZ9F56206
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONSEasy9 miniature circuit breaker- 2P – 6 A – C curve – 6000 A – 230 V EZ9F56206
Main range Easy9device application Distributionproduct or component type Miniature circuit-breakerdevice short name Easy9 MCBPoles 2Pnumber of protected poles 2[In] rated current 6 Anetwork type ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 10000 A Icn at 220 V AC 50/60 Hz conforming to IEC 60898-1
6000 A Icn at 400 V AC 50/60 Hz conforming to IEC 60898-1suitability for isolation Yes conforming to IEC 60898-1Complementary network frequency 50/60 Hz[Ue] rated operational voltage 220 V AC 50/60 Hz
400 V AC 50/60 Hzmagnetic tripping limit 5…10 x In[Ics] rated service breaking capacity 6 kA 100 % x Icn at 230 V AC 50/60 Hz conforming to IEC 60898-1[Ui] rated insulation voltage 500 V AC 50/60 Hz conforming to IEC 60898-1[Uimp] rated impulse withstand voltage 4 kV conforming to IEC 60898-1contact position indicator Yescontrol type Togglelocal signalling Withoutmounting mode Clip-onmounting support DIN rail9 mm pitches 4height 81 mmwidth 36 mmdepth 66.5 mmcolour Grey (RAL 7035)mechanical durability 10000 cycleselectrical durability 4000 cyclesconnections – terminals Tunnel type terminal (top or bottom) 1…25 mm² rigid
Tunnel type terminal (top or bottom) 1…16 mm² flexibletightening torque 2 N.m top or bottomearth-leakage protection WithoutSKU: n/a -
Electro, Low Voltage Products and Systems, SCHNEIDER SECTIONS
EZC100N4020 – Circuit breaker Easypact EZC100N – TMD – 20 A – 4 poles 3d
Electro, Low Voltage Products and Systems, SCHNEIDER SECTIONSEZC100N4020 – Circuit breaker Easypact EZC100N – TMD – 20 A – 4 poles 3d
Main range of product EasyPactproduct or component type Circuit breakerdevice short name Easypact EZC100Ncircuit breaker name Easypact EZC100Ndevice application Distributionpoles description 4Pprotected poles description 3tnetwork type DC
ACnetwork frequency 50/60 Hz[In] rated current 100 A at 40 °C[Ui] rated insulation voltage 690 V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947-2[Ue] rated operational voltage 550 V AC 50/60 Hz conforming to IEC 60947-2
250 V DC conforming to IEC 60947-2breaking capacity code Nbreaking capacity 10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
25 kA Icu at 110…130 V AC 50/60 Hz conforming to IEC 60947-2
25 kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
5 kA Icu at 125 V DC 1P conforming to IEC 60947-2
5 kA Icu at 250 V DC 2P conforming to IEC 60947-2
5 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2
15 kA Icu at 415 V AC 50/60 Hz conforming to IEC 60947-2
18 kA Icu at 380…400 V AC 50/60 Hz conforming to IEC 60947-2[Ics] rated service breaking capacity 5 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
2.5 kA at 125 V DC conforming to IEC 60947-2
2.5 kA at 250 V DC conforming to IEC 60947-2
2.5 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2
12.5 kA at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
12.5 kA at 110…130 V AC 50/60 Hz conforming to IEC 60947-2
9 kA at 380…400 V AC 50/60 Hz conforming to IEC 60947-2
7.5 kA at 415 V AC 50/60 Hz conforming to IEC 60947-2suitability for isolation Yes conforming to IEC 60947-2utilisation category Category Atrip unit name TM-Dtrip unit technology Thermal-magnetictrip unit rating 20 A at 50 °Cprotection type Short-circuit protection
Overload protectionpollution degree 3 conforming to IEC 60947Complementary control type Togglemounting mode Fixedmounting support Backplateupside connection Frontdownside connection Frontmechanical durability 8500 cycleselectrical durability Category A: 1500 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2connection pitch 25 mmlocal signalling Positive contact indicationneutral protection setting Without protectionearth-leakage protection Withoutheight 130 mmwidth 100 mmdepth 60 mmSKU: n/a -
Electro, SOCKETS & SWITCHES, SURGE PROTECTOR
Himel Single Phase Voltage Stabilizers 5kVA
Voltage stabilizer, HAVRL, relay type, 5 kVA, British type plug, 110/220 V output, 85..250 V input, with time delay
Main
Range of product – HAVRLProduct or component type – Voltage stabilizerTechnology type – RelayOutlet standard – BritishProvided equipment – User manualComplementary
Rated power in VA – 5 kVAMinimum insulating resistance – 5 MOhmMaximum [In] rated current – 22.7 AEfficiency – 90 %Input voltage limits – 85…250 VOptional feature – Bypass
Cooling fan – Input undervoltage protectionProtection type – Overvoltage
Overcurrent – Temperature rise protection
Time delay – Display typeLED – Output voltage220 V AC +/- 8 % – 110 V AC +/- 10 %Network frequency – 50/60 HzEnvironment
Ambient air temperature for operation -5…40 °CRelative humidity 0…90 %Humidity storage 0…90 %Operating altitude 0…2000 mStorage altitude 0…2000 mStandards EN 61000-6-2
EN 61000-6-4 EN 61558-1Packing Units
Unit Type of Package 1 PCENumber of Units in Package 1 1SKU: n/a
There are no reviews yet.