Schneider Circuit Breakers, SCHNEIDER SECTIONS
Acti9 iC60N 4P 2A C Miniature Circuit breaker A9F44402
range |
Acti 9
|
|
---|---|---|
product name |
Disbo iC60
|
|
product or component type |
Miniature circuit-breaker
|
|
device short name |
IC60N
|
|
poles description |
4P
|
|
number of protected poles |
4
|
|
[In] rated current |
2 A
|
|
network type |
AC
|
|
trip unit technology |
Thermal-magnetic
|
|
curve code |
C
|
|
breaking capacity |
50 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
50 kA Icu at 12…133 V AC 50/60 Hz conforming to EN/IEC 60947-2 50 kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2 25 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 6 kA Icu at 100…133 V DC conforming to EN/IEC 60947-2 6000 A Icn at 415 V AC 50/60 Hz conforming to EN/IEC 60898-1 |
|
utilisation category |
Category A conforming to EN/IEC 60947-2
|
network frequency |
50/60 Hz
|
|
---|---|---|
[Ue] rated operational voltage |
440 V AC 50/60 Hz
|
|
magnetic tripping limit |
8 x In +/- 20 %
|
|
[Ics] rated service breaking capacity |
50 kA 100 % conforming to EN/IEC 60947-2 – 220…240 V AC 50/60 Hz
50 kA 100 % conforming to EN/IEC 60947-2 – 12…133 V AC 50/60 Hz 50 kA 100 % conforming to EN/IEC 60947-2 – 380…415 V AC 50/60 Hz 25 kA 100 % conforming to EN/IEC 60947-2 – 440 V AC 50/60 Hz 6000 A 100 % conforming to EN/IEC 60898-1 – 415 V AC 50/60 Hz 6 kA 100 % conforming to EN/IEC 60947-2 – 100…133 V DC |
|
limitation class |
3 conforming to EN/IEC 60947-2
|
|
[Ui] rated insulation voltage |
500 V AC 50/60 Hz
|
|
[Uimp] rated impulse withstand voltage |
6 kV conforming to EN/IEC 60947-2
|
|
contact position indicator |
Yes
|
|
control type |
Toggle
|
|
local signalling |
Trip indicator
|
|
mounting mode |
Clip-on
|
|
mounting support |
Rail
|
|
9 mm pitches |
8
|
|
height |
85 mm
|
|
width |
72 mm
|
|
depth |
78.5 mm
|
|
net weight |
0.5 kg
|
|
colour |
White
|
|
mechanical durability |
20000 cycles
|
|
electrical durability |
10000 cycles
|
|
provision for padlocking |
Padlockable
|
|
connections – terminals |
Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexible |
|
wire stripping length |
14 mm for top or bottom connection
|
|
tightening torque |
2 N.m top or bottom
|
|
earth-leakage protection |
Separate block
|
standards |
EN/IEC 60898-1
EN/IEC 60947-2 |
|
---|---|---|
IP degree of protection |
IP20 conforming to IEC 60529
|
|
pollution degree |
3 conforming to EN/IEC 60947-2
|
|
tropicalisation |
2 conforming to IEC 60068-1
|
|
relative humidity |
95 % at 55 °C
|
|
ambient air temperature for operation |
-35…70 °C
|
|
ambient air temperature for storage |
-40…85 °C
|
₦18,999.00
Compare-
Schneider Circuit Breakers, SCHNEIDER SECTIONS
IC60H – miniature circuit breaker – 1P – 20A – C curve A9F84120
Schneider Circuit Breakers, SCHNEIDER SECTIONSIC60H – miniature circuit breaker – 1P – 20A – C curve A9F84120
Main device application Distributionrange Acti 9product name Acti 9 iC60product or component type Miniature circuit-breakerdevice short name IC60Hpoles description 1Pnumber of protected poles 1[In] rated current 20 Anetwork type AC
DCtrip unit technology Thermal-magneticcurve code Cbreaking capacity 10000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
15 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
42 kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2
30 kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2
15 kA Icu at 60…72 V DC conforming to EN/IEC 60947-2
20 kA Icu at 12…60 V DC conforming to EN/IEC 60947-2utilisation category Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2suitability for isolation Yes conforming to EN 60898-1
Yes conforming to EN 60947-2
Yes conforming to IEC 60898-1
Yes conforming to IEC 60947-2standards IEC 60898-1
IEC 60947-2
EN 60898-1
EN 60947-2Complementary network frequency 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 21 kA 50 % conforming to EN 60947-2 – 12…60 V AC 50/60 Hz
7.5 kA 50 % conforming to EN 60947-2 – 220…240 V AC 50/60 Hz
21 kA 50 % conforming to IEC 60947-2 – 12…60 V AC 50/60 Hz
7.5 kA 50 % conforming to IEC 60947-2 – 220…240 V AC 50/60 Hz
7500 A 75 % conforming to EN 60898-1 – 230 V AC 50/60 Hz
7500 A 75 % conforming to IEC 60898-1 – 230 V AC 50/60 Hz
15 kA 50 % conforming to IEC 60947-2 – 100…133 V AC 50/60 Hz
15 kA 50 % conforming to EN 60947-2 – 100…133 V AC 50/60 Hz
15 kA 100 % conforming to EN 60947-2 – 72 V DC
15 kA 100 % conforming to IEC 60947-2 – 72 V DC
20 kA 100 % conforming to EN 60947-2 – 12…60 V DC
20 kA 100 % conforming to IEC 60947-2 – 12…60 V DClimitation class 3 conforming to EN 60898-1
3 conforming to IEC 60898-1[Ui] rated insulation voltage 500 V AC 50/60 Hz conforming to EN 60947-2
500 V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6 kV conforming to EN 60947-2
6 kV conforming to IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Fixedmounting support DIN railcomb busbar and distribution block compatibility Top or bottom: YES9 mm pitches 2height 85 mmwidth 18 mmdepth 78.5 mmnet weight 0.215 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesconnections – terminals Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 2 N.m top or bottomearth-leakage protection WithoutSKU: n/a -
CABLE AND CABLE MANAGEMENT, Electro, SINGLE CORE WIRE
KABLEMETAL 1.5mm Single Core – Black
We offer other range of products across various categories and sub categories and our services are Procurement, installation and Management etc of electrical products, should you have any inquiry we are always here to do our best to promptly answer you.
SKU: Kablemetal4 -
Schneider Circuit Breakers, SCHNEIDER SECTIONS
IC60H – miniature circuit breaker – 1P – 63A – C curve A9F84163
Schneider Circuit Breakers, SCHNEIDER SECTIONSIC60H – miniature circuit breaker – 1P – 63A – C curve A9F84163
Main device application Distributionrange Acti 9product name Acti 9 iC60product or component type Miniature circuit-breakerdevice short name IC60Hpoles description 1Pnumber of protected poles 1[In] rated current 63 Anetwork type DC
ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 10000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
15 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
42 kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2
30 kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2
15 kA Icu at 60…72 V DC conforming to EN/IEC 60947-2
20 kA Icu at 12…60 V DC conforming to EN/IEC 60947-2utilisation category Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2suitability for isolation Yes conforming to EN 60898-1
Yes conforming to EN 60947-2
Yes conforming to IEC 60898-1
Yes conforming to IEC 60947-2standards EN 60947-2
EN 60898-1
IEC 60898-1
IEC 60947-2Complementary network frequency 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 21 kA 50 % conforming to EN 60947-2 – 12…60 V AC 50/60 Hz
7.5 kA 50 % conforming to EN 60947-2 – 220…240 V AC 50/60 Hz
21 kA 50 % conforming to IEC 60947-2 – 12…60 V AC 50/60 Hz
7.5 kA 50 % conforming to IEC 60947-2 – 220…240 V AC 50/60 Hz
7500 A 75 % conforming to EN 60898-1 – 230 V AC 50/60 Hz
7500 A 75 % conforming to IEC 60898-1 – 230 V AC 50/60 Hz
15 kA 50 % conforming to IEC 60947-2 – 100…133 V AC 50/60 Hz
15 kA 50 % conforming to EN 60947-2 – 100…133 V AC 50/60 Hz
15 kA 100 % conforming to EN 60947-2 – 72 V DC
15 kA 100 % conforming to IEC 60947-2 – 72 V DC
20 kA 100 % conforming to EN 60947-2 – 12…60 V DC
20 kA 100 % conforming to IEC 60947-2 – 12…60 V DC[Ui] rated insulation voltage 500 V AC 50/60 Hz conforming to EN 60947-2
500 V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6 kV conforming to EN 60947-2
6 kV conforming to IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Fixedmounting support DIN railcomb busbar and distribution block compatibility Top or bottom: YES9 mm pitches 2height 85 mmwidth 18 mmdepth 78.5 mmnet weight 0.215 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesconnections – terminals Single terminal (top or bottom) 1…35 mm² rigid
Single terminal (top or bottom) 1…25 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 3.5 N.m top or bottomearth-leakage protection WithoutSKU: n/a -
CABLE AND CABLE MANAGEMENT, Electro, SINGLE CORE WIRE
KABLEMETAL 4mm Single Core – Red
We offer other range of products across various categories and sub categories and our services are Procurement, installation and Management etc of electrical products, should you have any inquiry we are always here to do our best to promptly answer you.
SKU: 400 -
Schneider Circuit Breakers, SCHNEIDER SECTIONS
Acti9 iC60N 3P 4A C Miniature Circuit breaker A9F44304
Schneider Circuit Breakers, SCHNEIDER SECTIONSActi9 iC60N 3P 4A C Miniature Circuit breaker A9F44304
Main range Acti 9product name Disbo iC60product or component type Miniature circuit-breakerdevice short name IC60Npoles description 3Pnumber of protected poles 3[In] rated current 4 Anetwork type ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 50 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
50 kA Icu at 12…133 V AC 50/60 Hz conforming to EN/IEC 60947-2
50 kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2
25 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2
6000 A Icn at 415 V AC 50/60 Hz conforming to EN/IEC 60898-1
15 kA Icu at 100…133 V DC conforming to EN/IEC 60947-2utilisation category Category A conforming to EN/IEC 60947-2Complementary network frequency 50/60 Hz[Ue] rated operational voltage 440 V AC 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 50 kA 100 % conforming to EN/IEC 60947-2 – 220…240 V AC 50/60 Hz
50 kA 100 % conforming to EN/IEC 60947-2 – 12…133 V AC 50/60 Hz
50 kA 100 % conforming to EN/IEC 60947-2 – 380…415 V AC 50/60 Hz
25 kA 100 % conforming to EN/IEC 60947-2 – 440 V AC 50/60 Hz
6000 A 100 % conforming to EN/IEC 60898-1 – 415 V AC 50/60 Hz
15 kA 100 % conforming to EN/IEC 60947-2 – 100…133 V DClimitation class 3 conforming to EN/IEC 60947-2[Ui] rated insulation voltage 500 V AC 50/60 Hz[Uimp] rated impulse withstand voltage 6 kV conforming to EN/IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Clip-onmounting support Rail9 mm pitches 6height 85 mmwidth 54 mmdepth 78.5 mmnet weight 0.375 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesprovision for padlocking Padlockableconnections – terminals Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 2 N.m top or bottomearth-leakage protection Separate blockSKU: n/a -
LIGHT SWITCHES & ELECTRICAL SOCKETS
Lisse – Universal dimmer – 1 gang – 2 way – 400W/VA GGBL6012CS
Main range Lisseaesthetic name White mouldedproduct or component type Dimmerdevice presentation Complete productload type 230 V AC halogen lamp
Incandescent lamp: 400 Wcolour tint White mattquantity per set Set of 1Complementary device mounting Wall mounteddimmer application Inductive load
Resistive load[Ue] rated operational voltage 230 V AC 50 Hznumber of gangs 1 gangmaterial Urea (carbamide)connections – terminals Screw terminalsfixing mode By screws M3.5 x 25 mmtype of packing Bagheight 87 mmwidth 87 mmdepth 43.6 mmnet weight 0.072 kgSKU: n/a
There are no reviews yet.