CIRCUIT BREAKERS
C120H – circuit breaker – 3P – 100A – C curve
range of product |
C120
|
|
---|---|---|
range |
Acti 9
|
|
product name |
C120
|
|
product or component type |
Miniature circuit-breaker
|
|
device short name |
C120H
|
|
device application |
Distribution
|
|
poles description |
3P
|
|
number of protected poles |
3
|
|
[In] rated current |
100Â A
|
|
network type |
AC
|
|
trip unit technology |
Thermal-magnetic
|
|
curve code |
C
|
|
breaking capacity |
15Â kA Icu at <= 375 V DC conforming to EN/IEC 60947-2
15Â kA Icu at 230…400 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
network frequency |
50/60 Hz
|
|
---|---|---|
[Ue] rated operational voltage |
<= 375 V DC
230…400 V AC 50/60 Hz |
|
magnetic tripping limit |
8 x In +/- 20 %
|
|
[Ics] rated service breaking capacity |
15Â kA 100Â % conforming to EN/IEC 60947-2 – <= 375 V DC
7.5Â kA 50Â % conforming to EN/IEC 60947-2 – 230…400 V AC 50/60 Hz |
|
limitation class |
3 conforming to EN/IEC 60947-2
|
|
[Ui] rated insulation voltage |
500Â V AC 50/60 Hz conforming to EN/IEC 60947-2
|
|
[Uimp] rated impulse withstand voltage |
6Â kV conforming to EN/IEC 60947-2
|
|
control type |
Toggle
|
|
local signalling |
ON/OFF indication
|
|
mounting mode |
Clip-on
|
|
mounting support |
35 mm symmetrical DIN rail
|
|
9 mm pitches |
9
|
|
height |
81Â mm
|
|
width |
81Â mm
|
|
depth |
73Â mm
|
|
net weight |
0.615Â kg
|
|
colour |
White
|
|
mechanical durability |
20000Â cycles
|
|
electrical durability |
5000Â cycles
|
|
connections – terminals |
Tunnel type terminals1…50 mm² rigid
Tunnel type terminals1.5…35 mm² flexible |
|
wire stripping length |
15Â mm
|
|
tightening torque |
3.5Â N.m
|
|
earth-leakage protection |
Separate block
|
standards |
EN/IEC 60947-2
|
|
---|---|---|
IP degree of protection |
IP20 conforming to IEC 60529
|
|
pollution degree |
3 conforming to IEC 60947-2
|
|
overvoltage category |
III
|
|
tropicalisation |
2 conforming to IEC 60068-1
|
|
relative humidity |
95 % at 55 °C
|
|
ambient air temperature for operation |
-30…70 °C
|
|
ambient air temperature for storage |
-40…80 °C
|
₦53,000.00
Compare-
ACCESSORIES, ELECTRICAL INDUSTRIAL
Thermal Overload Relay – TA25DU4.0
TA25DU-4.0
General Information
-
- Extended Product Type:Â TA25DU-4.0
-
- Product ID:Â 1SAZ211201R1033
-
- EAN:Â Â 4013614216565
-
- Catalog Description:Â Â TA25DU-4.0 Thermal Overload Relay
-
- Long Description:
- The TA25DU-4.0 thermal overload relay is an economic electromechanical protection device for the main circuit. It offers reliable and fast protection for motors in the event of overload or phase failure. The device has trip class 10A. Further features are the temperature compensation, trip contact (NC), signal contact (NO), automatic- or manual reset selectable, trip-free mechanism, STOP- and Test function and a trip indication. The overload relays are connected directly to the block contactors. Single mounting kits are available as accessory.
SKU: n/a -
-
-
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONS
IC60H – miniature circuit breaker – 1P – 16A – C curve A9F84116
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONSIC60H – miniature circuit breaker – 1P – 16A – C curve A9F84116
Main device application Distributionrange Acti 9product name Acti 9 iC60product or component type Miniature circuit-breakerdevice short name IC60Hpoles description 1Pnumber of protected poles 1[In] rated current 16Â Anetwork type DC
ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 10000Â A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
15Â kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
42Â kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2
30Â kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2
15Â kA Icu at 60…72 V DC conforming to EN/IEC 60947-2
20Â kA Icu at 12…60 V DC conforming to EN/IEC 60947-2utilisation category Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2suitability for isolation Yes conforming to EN 60898-1
Yes conforming to EN 60947-2
Yes conforming to IEC 60898-1
Yes conforming to IEC 60947-2standards IEC 60947-2
IEC 60898-1
EN 60947-2
EN 60898-1Complementary network frequency 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 21Â kA 50Â % conforming to EN 60947-2 – 12…60 V AC 50/60 Hz
7.5Â kA 50Â % conforming to EN 60947-2 – 220…240 V AC 50/60 Hz
21Â kA 50Â % conforming to IEC 60947-2 – 12…60 V AC 50/60 Hz
7.5Â kA 50Â % conforming to IEC 60947-2 – 220…240 V AC 50/60 Hz
7500Â A 75Â % conforming to EN 60898-1 – 230 V AC 50/60 Hz
7500Â A 75Â % conforming to IEC 60898-1 – 230 V AC 50/60 Hz
15Â kA 50Â % conforming to IEC 60947-2 – 100…133 V AC 50/60 Hz
15Â kA 50Â % conforming to EN 60947-2 – 100…133 V AC 50/60 Hz
15Â kA 100Â % conforming to EN 60947-2 – 72 V DC
15Â kA 100Â % conforming to IEC 60947-2 – 72 V DC
20Â kA 100Â % conforming to EN 60947-2 – 12…60 V DC
20Â kA 100Â % conforming to IEC 60947-2 – 12…60 V DClimitation class 3 conforming to EN 60898-1
3 conforming to IEC 60898-1[Ui] rated insulation voltage 500Â V AC 50/60 Hz conforming to EN 60947-2
500Â V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6Â kV conforming to EN 60947-2
6 kV conforming to IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Fixedmounting support DIN railcomb busbar and distribution block compatibility Top or bottom: YES9 mm pitches 2height 85 mmwidth 18 mmdepth 78.5 mmnet weight 0.215 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesconnections – terminals Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 2 N.m top or bottomearth-leakage protection WithoutSKU: n/a -
Electro, Low Voltage Products and Systems, SCHNEIDER SECTIONS
EZC100F3050 – Circuit breaker Easypact EZC100F – TMD – 50 A – 3 poles 3d
Electro, Low Voltage Products and Systems, SCHNEIDER SECTIONSEZC100F3050 – Circuit breaker Easypact EZC100F – TMD – 50 A – 3 poles 3d
Main range of product EasyPactproduct or component type Circuit breakerdevice short name Easypact EZC100Fcircuit breaker name Easypact EZC100Fdevice application Distributionpoles description 3Pprotected poles description 3tnetwork type DC
ACnetwork frequency 50/60 Hz[In] rated current 100 A at 40 °C[Ui] rated insulation voltage 690 V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947-2[Ue] rated operational voltage 550 V AC 50/60 Hz conforming to IEC 60947-2
250 V DC conforming to IEC 60947-2breaking capacity code Fbreaking capacity 25Â kA Icu at 110…130 V AC 50/60 Hz conforming to IEC 60947-2
25Â kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
5Â kA Icu at 125 V DC 1P conforming to IEC 60947-2
5Â kA Icu at 250 V DC 2P conforming to IEC 60947-2
5Â kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2
10Â kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2
10Â kA Icu at 400…415 V AC 50/60 Hz conforming to IEC 60947-2
7.5Â kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2[Ics] rated service breaking capacity 12.5Â kA at 110/130 V AC 50/60 Hz conforming to IEC 60947-2
12.5Â kA at 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2
2.5Â kA at 125 V DC conforming to IEC 60947-2
2.5Â kA at 250 V DC conforming to IEC 60947-2
2.5Â kA at 550 V AC 50/60 Hz conforming to IEC 60947-2
5Â kA at 380 V AC 50/60 Hz conforming to IEC 60947-2
5Â kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
3.75 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2suitability for isolation Yes conforming to IEC 60947-2utilisation category Category Atrip unit name TM-Dtrip unit technology Thermal-magnetictrip unit rating 50 A at 50 °Cprotection type Overload protection
Short-circuit protectionpollution degree 3 conforming to IEC 60664-1
3 conforming to IEC 947-1Complementary control type Togglemounting mode Fixedmounting support Backplateupside connection Frontdownside connection Frontmechanical durability 8500Â cycleselectrical durability Category A: 1500Â cycles 415 V AC 50/60 Hz conforming to IEC 60947-2connection pitch 25Â mmlocal signalling Positive contact indicationneutral protection setting Without protectionearth-leakage protection Withoutheight 130Â mmwidth 75Â mmdepth 60Â mmSKU: n/a -