C120N – circuit breaker – 4P – 100A – C curve
range of product |
C120
|
|
---|---|---|
range |
Acti 9
|
|
product name |
C120
|
|
product or component type |
Miniature circuit-breaker
|
|
device short name |
C120N
|
|
device application |
Distribution
|
|
poles description |
4P
|
|
number of protected poles |
4
|
|
[In] rated current |
100 A at 30 °C
|
|
network type |
AC
|
|
trip unit technology |
Thermal-magnetic
|
|
curve code |
C
|
|
breaking capacity |
10000Â A Icn at 230…400 V AC 50/60 Hz conforming to EN/IEC 60898-1
6Â kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 20Â kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10Â kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2 10Â kA Icu at <= 500 V DC conforming to EN/IEC 60947-2 |
|
suitability for isolation |
Yes conforming to IEC 60947-2
|
network frequency |
50/60 Hz
|
|
---|---|---|
[Ue] rated operational voltage |
380…415 V AC 50/60 Hz
<= 500 V DC 220…240 V AC 50/60 Hz 440 V AC 50/60 Hz 230…400 V AC 50/60 Hz |
|
magnetic tripping limit |
5…10 x In
|
|
[Ics] rated service breaking capacity |
7500Â A 75Â % conforming to EN/IEC 60898-1 – 230…400 V AC 50/60 Hz
4.5Â kA 75Â % conforming to EN/IEC 60947-2 – 440 V AC 50/60 Hz 7.5Â kA 75Â % conforming to EN/IEC 60947-2 – 380…415 V AC 50/60 Hz 15Â kA 75Â % conforming to EN/IEC 60947-2 – 220…240 V AC 50/60 Hz 10Â kA 100Â % conforming to EN/IEC 60947-2 – <= 500 V DC |
|
limitation class |
3 conforming to EN/IEC 60947-2
|
|
[Ui] rated insulation voltage |
500Â V AC 50/60 Hz conforming to EN/IEC 60947-2
|
|
[Uimp] rated impulse withstand voltage |
6Â kV conforming to EN/IEC 60947-2
|
|
contact position indicator |
Yes
|
|
control type |
Toggle
|
|
local signalling |
ON/OFF indication
|
|
mounting mode |
Clip-on
|
|
mounting support |
35 mm symmetrical DIN rail
|
|
comb busbar and distribution block compatibility |
NO
|
|
9 mm pitches |
12
|
|
height |
81Â mm
|
|
width |
108Â mm
|
|
depth |
73Â mm
|
|
net weight |
0.82Â kg
|
|
colour |
White
|
|
mechanical durability |
20000Â cycles
|
|
electrical durability |
5000Â cycles conforming to IEC 60947-2
|
|
connections – terminals |
Tunnel type terminals1…50 mm² rigid
Tunnel type terminals1.5…35 mm² flexible |
|
wire stripping length |
15Â mm
|
|
tightening torque |
3.5Â N.m
|
|
earth-leakage protection |
Separate block
|
₦60,000.00
Compare-
Electro, INDOOR LIGHTS, LED LIGHTS, LIGHTING
Vtac 2ft LED Tube SAMSUNG Chip
Product benefits
- Cost effective, safe retrofit for T8 Tubes
- Perfectly matches with the traditional daylight tube fixture
- Easy Installation
- No Lead or Mercury content hence Environment friendly
- No Ultraviolet or Infrared rays
- No flickering
- Long Lifespan, Low maintenance and energy saving
- Available in 60 cm, 120 cm, 150 cm
- Ballast or Starter NOT REQUIRED – DIRECT AC POWER
Applications
- Domestic and Commercial Lighting
- Offices
- Supermarkets
- Shops, Hotels & similar environment
SKU: n/a -
Low Voltage Products and Systems, SCHNEIDER SECTIONS
EZC250N4200 Circuit breaker Easypact EZC250N – TMD – 200 A – 4 poles 3d
Low Voltage Products and Systems, SCHNEIDER SECTIONSEZC250N4200 Circuit breaker Easypact EZC250N – TMD – 200 A – 4 poles 3d
Main range of product EasyPactproduct or component type Circuit breakerdevice short name Easypact EZC250Ncircuit breaker name Easypact EZC250Ndevice application Distributionpoles description 4Pprotected poles description 3tnetwork type DC
ACnetwork frequency 50/60 Hz[In] rated current 250 A at 40 °C[Ui] rated insulation voltage 690 V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947-2[Ue] rated operational voltage 550 V AC 50/60 Hz conforming to IEC 60947-2
250 V DC conforming to IEC 60947-2breaking capacity code Nbreaking capacity 20Â kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
50Â kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
20Â kA Icu at 125 V DC 1P conforming to IEC 60947-2
20Â kA Icu at 250 V DC 2P conforming to IEC 60947-2
8Â kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2
25Â kA Icu at 380…415 V AC 50/60 Hz conforming to IEC 60947-2[Ics] rated service breaking capacity 10Â kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
25Â kA at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
10Â kA at 125 V DC conforming to IEC 60947-2
10Â kA at 250 V DC conforming to IEC 60947-2
4Â kA at 550 V AC 50/60 Hz conforming to IEC 60947-2
12.5 kA at 380…415 V AC 50/60 Hz conforming to IEC 60947-2suitability for isolation Yes conforming to IEC 60947-2utilisation category Category Atrip unit name TM-Dtrip unit technology Thermal-magnetictrip unit rating 200 A at 50 °Cprotection type Short-circuit protection
Overload protectionpollution degree 3 conforming to IEC 60947Complementary control type Togglemounting mode Fixedmounting support Backplateupside connection Frontdownside connection Frontmechanical durability 10000Â cycleselectrical durability Category A: 5000Â cycles 415 V AC 50/60 Hz conforming to IEC 60947-2connection pitch 35Â mmlocal signalling Positive contact indicationneutral protection setting Without protectionearth-leakage protection Withoutheight 165Â mmwidth 140Â mmdepth 60Â mmSKU: n/a -
SOLAR POWERED
Solar Panel YL270W Poly
The 60-cell polycrystalline module is currently one of the strongest in the market with 270 Wp output power. Compliant with advanced load tests – meets the load requirement of 5400 Pa. By optimizing the design of solar cells and selecting the right materials, the module achieves high efficiency even in a weaker light. Due to high corrosion resistance due to salt (fog) and ammonia, the modules are also suitable for agricultural and coastal surfaces.
Package includes:
Connection cable (L) with a width of 4.0 mm2 and a length of 900 mm; the toughened glass front has low iron content and is resistant to high temperatures; frame made of anodized aluminum alloy.
SKU: n/a -
Schneider Circuit Breakers, SCHNEIDER SECTIONS
Easy9 miniature circuit breaker- 3P – 25 A – C curve – 6000 A – 400 V EZ9F56325
Schneider Circuit Breakers, SCHNEIDER SECTIONSEasy9 miniature circuit breaker- 3P – 25 A – C curve – 6000 A – 400 V EZ9F56325
Main range Easy9device application Distributionproduct or component type Miniature circuit-breakerdevice short name Easy9 MCBPoles 3Pnumber of protected poles 3[In] rated current 25Â Anetwork type ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 10000Â A Icn at 220 V AC 50/60 Hz conforming to IEC 60898-1
6000Â A Icn at 400 V AC 50/60 Hz conforming to IEC 60898-1suitability for isolation Yes conforming to IEC 60898-1Complementary network frequency 50 Hz[Ue] rated operational voltage 220 V AC 50/60 Hz
400 V AC 50/60 Hzmagnetic tripping limit 5…10 x In[Ics] rated service breaking capacity 6 kA 100 % x Icn at 400 V AC 50/60 Hz conforming to IEC 60898-1[Ui] rated insulation voltage 500 V AC 50/60 Hz conforming to IEC 60898-1[Uimp] rated impulse withstand voltage 4 kV conforming to IEC 60898-1contact position indicator Yescontrol type Togglelocal signalling Withoutmounting mode Clip-onmounting support DIN rail9 mm pitches 6height 81 mmwidth 54 mmdepth 66.5 mmcolour Grey (RAL 7035)mechanical durability 10000 cycleselectrical durability 4000 cyclesconnections – terminals Tunnel type terminal (top or bottom) 1…25 mm² rigid
Tunnel type terminal (top or bottom) 1…16 mm² flexibletightening torque 2 N.m top or bottomSKU: n/a -
Schneider Circuit Breakers, SCHNEIDER SECTIONS
Acti9 iC60N 1P 10A C Miniature Circuit breaker A9F44110
Schneider Circuit Breakers, SCHNEIDER SECTIONSActi9 iC60N 1P 10A C Miniature Circuit breaker A9F44110
Main range Acti 9product name Disbo iC60product or component type Miniature circuit-breakerdevice short name IC60Npoles description 1Pnumber of protected poles 1[In] rated current 10Â Anetwork type ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 15Â kA Icu at 12…48 V DC conforming to EN/IEC 60947-2
6Â kA Icu at 72 V DC conforming to EN/IEC 60947-2
6000Â A Icn at 240 V AC 50/60 Hz conforming to EN/IEC 60898-1
36Â kA Icu at 10…60 V AC 50/60 Hz conforming to EN/IEC 60947-2
20Â kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2
10Â kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2utilisation category Category A conforming to EN/IEC 60947-2Complementary network frequency 50/60 Hz[Ue] rated operational voltage 240 V AC 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 27Â kA 75Â % conforming to EN/IEC 60947-2 – 10…60 V AC 50/60 Hz
15Â kA 75Â % conforming to EN/IEC 60947-2 – 100…133 V AC 50/60 Hz
7.5Â kA 75Â % conforming to EN/IEC 60947-2 – 220…240 V AC 50/60 Hz
6000Â A 100Â % conforming to EN/IEC 60898-1 – 240 V AC 50/60 Hz
15Â kA 100Â % conforming to EN/IEC 60947-2 – 12…48 V DC
6 kA 100 % conforming to EN/IEC 60947-2 – 72 V DClimitation class 3 conforming to EN/IEC 60947-2[Ui] rated insulation voltage 500 V AC 50/60 Hz[Uimp] rated impulse withstand voltage 6 kV conforming to EN/IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Clip-onmounting support Rail9 mm pitches 2height 85 mmwidth 18 mmdepth 78.5 mmnet weight 0.125 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesprovision for padlocking Padlockableconnections – terminals Single terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 2 N.m top or bottomearth-leakage protection Separate blockSKU: n/a -
LIGHT SWITCHES & ELECTRICAL SOCKETS, SCHNEIDER SECTIONS
AvatarOn, switch, 16AX, 250V, 1 way, LED, Dark Grey E8331L1LED_DG
LIGHT SWITCHES & ELECTRICAL SOCKETS, SCHNEIDER SECTIONSAvatarOn, switch, 16AX, 250V, 1 way, LED, Dark Grey E8331L1LED_DG
Main product or component type Switchdevice application Controlload type Fluorescent lamp
Incandescent lamp
Resistive
Inductivecolour tint Dark greyComplementary device presentation Complete productrated current 16 AX at 250 V AC 50/60 Hzswitch function 1-pole 1-waynumber of gangs 1 gangnumber of rocker 1clamping connection capacity 3 x 2.5 mm² for solid cable(s)
3 x 2.5 mm² for stranded cable(s)
4 x 1.5 mm² for solid cable(s)
4 x 1.5 mm² for stranded cable(s)connections – terminals Brass terminallocal signalling Off: LED indicator, LEDMaterial Polycarbonate: grid plate
Polycarbonate: base
Polycarbonate: dolly
Polycarbonate: frame
Polycarbonate + GF 20 %: actuatordevice mounting Surface
Flushwidth 86Â mmheight 86Â mmdepth 34.2Â mmembedding depth 24.5Â mmSKU: n/a