CIRCUIT BREAKERS
C120N – circuit breaker – 4P – 100A – C curve
range of product |
C120
|
|
---|---|---|
range |
Acti 9
|
|
product name |
C120
|
|
product or component type |
Miniature circuit-breaker
|
|
device short name |
C120N
|
|
device application |
Distribution
|
|
poles description |
4P
|
|
number of protected poles |
4
|
|
[In] rated current |
100 A at 30 °C
|
|
network type |
AC
|
|
trip unit technology |
Thermal-magnetic
|
|
curve code |
C
|
|
breaking capacity |
10000Â A Icn at 230…400 V AC 50/60 Hz conforming to EN/IEC 60898-1
6Â kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 20Â kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10Â kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2 10Â kA Icu at <= 500 V DC conforming to EN/IEC 60947-2 |
|
suitability for isolation |
Yes conforming to IEC 60947-2
|
network frequency |
50/60 Hz
|
|
---|---|---|
[Ue] rated operational voltage |
380…415 V AC 50/60 Hz
<= 500 V DC 220…240 V AC 50/60 Hz 440 V AC 50/60 Hz 230…400 V AC 50/60 Hz |
|
magnetic tripping limit |
5…10 x In
|
|
[Ics] rated service breaking capacity |
7500Â A 75Â % conforming to EN/IEC 60898-1 – 230…400 V AC 50/60 Hz
4.5Â kA 75Â % conforming to EN/IEC 60947-2 – 440 V AC 50/60 Hz 7.5Â kA 75Â % conforming to EN/IEC 60947-2 – 380…415 V AC 50/60 Hz 15Â kA 75Â % conforming to EN/IEC 60947-2 – 220…240 V AC 50/60 Hz 10Â kA 100Â % conforming to EN/IEC 60947-2 – <= 500 V DC |
|
limitation class |
3 conforming to EN/IEC 60947-2
|
|
[Ui] rated insulation voltage |
500Â V AC 50/60 Hz conforming to EN/IEC 60947-2
|
|
[Uimp] rated impulse withstand voltage |
6Â kV conforming to EN/IEC 60947-2
|
|
contact position indicator |
Yes
|
|
control type |
Toggle
|
|
local signalling |
ON/OFF indication
|
|
mounting mode |
Clip-on
|
|
mounting support |
35 mm symmetrical DIN rail
|
|
comb busbar and distribution block compatibility |
NO
|
|
9 mm pitches |
12
|
|
height |
81Â mm
|
|
width |
108Â mm
|
|
depth |
73Â mm
|
|
net weight |
0.82Â kg
|
|
colour |
White
|
|
mechanical durability |
20000Â cycles
|
|
electrical durability |
5000Â cycles conforming to IEC 60947-2
|
|
connections – terminals |
Tunnel type terminals1…50 mm² rigid
Tunnel type terminals1.5…35 mm² flexible |
|
wire stripping length |
15Â mm
|
|
tightening torque |
3.5Â N.m
|
|
earth-leakage protection |
Separate block
|
₦60,000.00
Compare-
Schneider Circuit Breakers, SCHNEIDER SECTIONS
IC60H – miniature circuit breaker – 1P – 50A – C curve A9F84150
Schneider Circuit Breakers, SCHNEIDER SECTIONSIC60H – miniature circuit breaker – 1P – 50A – C curve A9F84150
Main device application Distributionrange Acti 9product name Acti 9 iC60product or component type Miniature circuit-breakerdevice short name IC60Hpoles description 1Pnumber of protected poles 1[In] rated current 50Â Anetwork type DC
ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 10000Â A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
15Â kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
42Â kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2
30Â kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2
15Â kA Icu at 60…72 V DC conforming to EN/IEC 60947-2
20Â kA Icu at 12…60 V DC conforming to EN/IEC 60947-2utilisation category Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2suitability for isolation Yes conforming to EN 60898-1
Yes conforming to EN 60947-2
Yes conforming to IEC 60898-1
Yes conforming to IEC 60947-2standards IEC 60898-1
EN 60898-1
IEC 60947-2
EN 60947-2Complementary network frequency 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 21Â kA 50Â % conforming to EN 60947-2 – 12…60 V AC 50/60 Hz
7.5Â kA 50Â % conforming to EN 60947-2 – 220…240 V AC 50/60 Hz
21Â kA 50Â % conforming to IEC 60947-2 – 12…60 V AC 50/60 Hz
7.5Â kA 50Â % conforming to IEC 60947-2 – 220…240 V AC 50/60 Hz
7500Â A 75Â % conforming to EN 60898-1 – 230 V AC 50/60 Hz
7500Â A 75Â % conforming to IEC 60898-1 – 230 V AC 50/60 Hz
15Â kA 50Â % conforming to IEC 60947-2 – 100…133 V AC 50/60 Hz
15Â kA 50Â % conforming to EN 60947-2 – 100…133 V AC 50/60 Hz
15Â kA 100Â % conforming to EN 60947-2 – 72 V DC
15Â kA 100Â % conforming to IEC 60947-2 – 72 V DC
20Â kA 100Â % conforming to EN 60947-2 – 12…60 V DC
20Â kA 100Â % conforming to IEC 60947-2 – 12…60 V DC[Ui] rated insulation voltage 500Â V AC 50/60 Hz conforming to EN 60947-2
500Â V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6Â kV conforming to EN 60947-2
6 kV conforming to IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Fixedmounting support DIN railcomb busbar and distribution block compatibility Top or bottom: YES9 mm pitches 2height 85 mmwidth 18 mmdepth 78.5 mmnet weight 0.215 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesconnections – terminals Single terminal (top or bottom) 1…35 mm² rigid
Single terminal (top or bottom) 1…25 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 3.5 N.m top or bottomearth-leakage protection WithoutSKU: n/a -
SOLAR POWERED
Solar Panel SG80W MONO
High Quality Monocrystalline solar panel
• Perfect for 12-volt battery charging or multiple panels can be wired in series for 24/48-volt battery charging or for grid-tied or off-grid solar applications.
• Diodes are pre-installed in junction box and a pair of 28 inches cables with MC4 connectors comes with the panel automatically.SKU: n/a -
CIRCUIT BREAKERS
IC60N – miniature circuit breaker – 3P – 63A – C curve
Main device application Distributionrange Acti 9product name Acti 9 iC60product or component type Miniature circuit-breakerdevice short name IC60Npoles description 3Pnumber of protected poles 3[In] rated current 63Â Anetwork type DC
ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 6000Â A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
36Â kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2
10Â kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2
20Â kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
6Â kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2
36Â kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2
10Â kA Icu at <= 180 V DC conforming to EN/IEC 60947-2utilisation category Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2suitability for isolation Yes conforming to EN 60898-1
Yes conforming to EN 60947-2
Yes conforming to IEC 60898-1
Yes conforming to IEC 60947-2standards EN 60898-1
EN 60947-2
IEC 60898-1
IEC 60947-2Complementary network frequency 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 15Â kA 75Â % conforming to EN 60947-2 – 220…240 V AC 50/60 Hz
7.5Â kA 75Â % conforming to EN 60947-2 – 380…415 V AC 50/60 Hz
4.5Â kA 75Â % conforming to EN 60947-2 – 440 V AC 50/60 Hz
15Â kA 75Â % conforming to IEC 60947-2 – 220…240 V AC 50/60 Hz
7.5Â kA 75Â % conforming to IEC 60947-2 – 380…415 V AC 50/60 Hz
4.5Â kA 75Â % conforming to IEC 60947-2 – 440 V AC 50/60 Hz
27Â kA 75Â % conforming to IEC 60947-2 – 12…133 V AC 50/60 Hz
27Â kA 75Â % conforming to EN 60947-2 – 12…133 V AC 50/60 Hz
6000Â A 100Â % conforming to EN 60898-1 – 400 V AC 50/60 Hz
6000Â A 100Â % conforming to IEC 60898-1 – 400 V AC 50/60 Hz
10Â kA 100Â % conforming to IEC 60947-2 – 125…180 V DC
10Â kA 100Â % conforming to EN 60947-2 – 125…180 V DC[Ui] rated insulation voltage 500Â V AC 50/60 Hz conforming to EN 60947-2
500Â V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6Â kV conforming to EN 60947-2
6 kV conforming to IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Fixedmounting support DIN railcomb busbar and distribution block compatibility Top or bottom: YES9 mm pitches 6height 85 mmwidth 54 mmdepth 78.5 mmnet weight 0.375 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesconnections – terminals Single terminal (top or bottom) 1…35 mm² rigid
Single terminal (top or bottom) 1…25 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 3.5 N.m top or bottomearth-leakage protection Separate blockSKU: n/a -
Schneider Circuit Breakers, SCHNEIDER SECTIONS
Easy9 miniature circuit breaker- 1P – 25 A – C curve – 6000 A – 230 V EZ9F56125
Schneider Circuit Breakers, SCHNEIDER SECTIONSEasy9 miniature circuit breaker- 1P – 25 A – C curve – 6000 A – 230 V EZ9F56125
Main range Easy9device application Distributionproduct or component type Miniature circuit-breakerdevice short name Easy9 MCBPoles 1Pnumber of protected poles 1[In] rated current 25Â Anetwork type ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 6000Â A Icn at 230 V AC 50/60 Hz conforming to IEC 60898-1
10000Â A Icn at 127 V AC 50/60 Hz conforming to IEC 60898-1suitability for isolation Yes conforming to IEC 60898-1Complementary network frequency 50 Hz[Ue] rated operational voltage 230 V AC 50 Hz
127 V AC 50 Hzmagnetic tripping limit 5…10 x In[Ics] rated service breaking capacity 6 kA 100 % x Icn at 230 V AC 50/60 Hz conforming to IEC 60898-1[Ui] rated insulation voltage 500 V AC 50/60 Hz conforming to IEC 60898-1[Uimp] rated impulse withstand voltage 4 kV conforming to IEC 60898-1contact position indicator Yescontrol type Togglelocal signalling Withoutmounting mode Clip-onmounting support DIN rail9 mm pitches 2height 81 mmwidth 18 mmdepth 66.5 mmcolour Grey (RAL 7035)mechanical durability 10000 cycleselectrical durability 4000 cyclesconnections – terminals Tunnel type terminal (top or bottom) 1…25 mm² rigid
Tunnel type terminal (top or bottom) 1…16 mm² flexibletightening torque 2 N.m top or bottomSKU: n/a -
Schneider Mureva Floodlight, SCHNEIDER SECTIONS
Thorsman, Worklight 30W, IP65 DK Plug 230V IMT47230
Main range Thorsmanrange of product Thorsman Worklightsproduct name Worklightproduct or component type Lampdevice application Mobile equipment
Ware-houses and parking garages
Hospital
Residential
Sports hallComplementary type of installation Outdoor[Ue] rated operational voltage 230 Vnetwork type ACoperational power in W 30 Wplug standard Denmarkluminous flux 3000 lmbulb lifespan 50000 hcolour rendering index Ra=80colour temperature 4000 Kbeam angle 110 °power factor 0.9height 254.5 mmwidth 231.0 mmdepth 20.0 mmnet weight 1.1 kgSKU: n/a
There are no reviews yet.