C120N – circuit breaker – 4P – 100A – C curve
range of product |
C120
|
|
---|---|---|
range |
Acti 9
|
|
product name |
C120
|
|
product or component type |
Miniature circuit-breaker
|
|
device short name |
C120N
|
|
device application |
Distribution
|
|
poles description |
4P
|
|
number of protected poles |
4
|
|
[In] rated current |
100 A at 30 °C
|
|
network type |
AC
|
|
trip unit technology |
Thermal-magnetic
|
|
curve code |
C
|
|
breaking capacity |
10000Â A Icn at 230…400 V AC 50/60 Hz conforming to EN/IEC 60898-1
6Â kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 20Â kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10Â kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2 10Â kA Icu at <= 500 V DC conforming to EN/IEC 60947-2 |
|
suitability for isolation |
Yes conforming to IEC 60947-2
|
network frequency |
50/60 Hz
|
|
---|---|---|
[Ue] rated operational voltage |
380…415 V AC 50/60 Hz
<= 500 V DC 220…240 V AC 50/60 Hz 440 V AC 50/60 Hz 230…400 V AC 50/60 Hz |
|
magnetic tripping limit |
5…10 x In
|
|
[Ics] rated service breaking capacity |
7500Â A 75Â % conforming to EN/IEC 60898-1 – 230…400 V AC 50/60 Hz
4.5Â kA 75Â % conforming to EN/IEC 60947-2 – 440 V AC 50/60 Hz 7.5Â kA 75Â % conforming to EN/IEC 60947-2 – 380…415 V AC 50/60 Hz 15Â kA 75Â % conforming to EN/IEC 60947-2 – 220…240 V AC 50/60 Hz 10Â kA 100Â % conforming to EN/IEC 60947-2 – <= 500 V DC |
|
limitation class |
3 conforming to EN/IEC 60947-2
|
|
[Ui] rated insulation voltage |
500Â V AC 50/60 Hz conforming to EN/IEC 60947-2
|
|
[Uimp] rated impulse withstand voltage |
6Â kV conforming to EN/IEC 60947-2
|
|
contact position indicator |
Yes
|
|
control type |
Toggle
|
|
local signalling |
ON/OFF indication
|
|
mounting mode |
Clip-on
|
|
mounting support |
35 mm symmetrical DIN rail
|
|
comb busbar and distribution block compatibility |
NO
|
|
9 mm pitches |
12
|
|
height |
81Â mm
|
|
width |
108Â mm
|
|
depth |
73Â mm
|
|
net weight |
0.82Â kg
|
|
colour |
White
|
|
mechanical durability |
20000Â cycles
|
|
electrical durability |
5000Â cycles conforming to IEC 60947-2
|
|
connections – terminals |
Tunnel type terminals1…50 mm² rigid
Tunnel type terminals1.5…35 mm² flexible |
|
wire stripping length |
15Â mm
|
|
tightening torque |
3.5Â N.m
|
|
earth-leakage protection |
Separate block
|
₦60,000.00
Compare-
ELECTRICAL INDUSTRIAL, TRANSFORMER
BETA 300KVA/33/0.415V COPPER/COPPER WINDING TRANSFORMER
Produced within a power range between 10 – 100.000 kVA , up to 170 kV high voltage level, three phase or single phase, oil immersed, ONAN, ONAF, OFWF, with Off-Load or On-Load Tap Changer, used both external and internal.
Dimensions of transformer conservator are determined and designed after several heat calculations of the oil stored in expansion tank and oil level changes by heat.
Being open to atmosphere, oil pressure changes continuously in Conservator Type Transformers due to thermal effects and exchange of air is dehumidified via air breather silicagel.SKU: n/a -
Electro, Low Voltage Products and Systems, SCHNEIDER SECTIONS
EZC250N4160 Circuit breaker Easypact EZC250N – TMD – 160 A – 4 poles 3d
Electro, Low Voltage Products and Systems, SCHNEIDER SECTIONSEZC250N4160 Circuit breaker Easypact EZC250N – TMD – 160 A – 4 poles 3d
Main range of product EasyPact Product or component typee Circuit breaker Device short name Easypact EZC250N circuit breaker name Easypact EZC250N Device application Distribution Poles description 4P Protected poles description 3t Network type AC
DCNetwork frequency 50/60 Hz [In] rated current 160 A at 40 °C [Ui] rated insulation voltage 690 V AC 50/60 Hz conforming to IEC 60947-2 [Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947-2 [Ue] rated operational voltage 550 V AC 50/60 Hz conforming to IEC 60947-2
250 V DC conforming to IEC 60947-2Breaking capacity code N Breaking capacity 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
20 kA Icu at 125 V DC 1P conforming to IEC 60947-2
20 kA Icu at 250 V DC 2P conforming to IEC 60947-2
8 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2
25 kA Icu at 380…415 V AC 50/60 Hz conforming to IEC 60947-2[Ics] rated service breaking capacity 10 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
25 kA at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
10 kA at 125 V DC conforming to IEC 60947-2
10 kA at 250 V DC conforming to IEC 60947-2
4 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2
12.5 kA at 380…415 V AC 50/60 Hz conforming to IEC 60947-2Suitability for isolation Yes conforming to IEC 60947-2 utilisation category Category A Trip unit name TM-D Trip unit technology Thermal-magnetic Trip unit rating 160 A at 50 °C Protection type Short-circuit protection
Overload protectionPollution degree 3 conforming to IEC 60947 Complementary control type Toggle Mounting mode Fixed mounting support Backplate Upside connection Front downside connection Front Mechanical durability 10000 cycles Electrical durability Category A: 5000 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2 Connection pitch 35 mm local signalling Positive contact indication Neutral protection setting Without protection earth-leakage protection Without height 165 mm Width 140 mm Depth 60 mm Environment Standards JIS C8201-2-2
EN/IEC 60947-2
GB/T 14048.2
EN/IEC 60947-1IP degree of protection IP20 conforming to IEC 60529 IK degree of protection IK07 conforming to EN 50102 ambient air temperature for operation -25…70 °C Ambient air temperature for storage -35…85 °C Packing Units Unit Type of Package 1 PCE Number of Units in Package 1 1 Package 1 Height 11.0 cm Package 1 Width 14.5 cm Package 1 Length 18.5 cm Package 1 Weight 2.24 kg Unit Type of Package 2 S03 Number of Units in Package 2 6 Package 2 Height 30.0 cm Package 2 Width 30.0 cm Package 2 Length 40.0 cm Package 2 Weight 13.927 kg Unit Type of Package 3 PAL Number of Units in Package 3 96 Package 3 Height 72.0 cm Package 3 Width 125.0 cm Package 3 Length 96.0 cm Package 3 Weight 215.04 kg SKU: n/a -
Electro, LIGHT SWITCHES & ELECTRICAL SOCKETS
Lisse – Switched Socket – 2 gang – 13A SP 2USB Mocha Bronze with Black Interior GGBL30202USBABMBS
Electro, LIGHT SWITCHES & ELECTRICAL SOCKETSLisse – Switched Socket – 2 gang – 13A SP 2USB Mocha Bronze with Black Interior GGBL30202USBABMBS
Main range Lisseaesthetic name Screwless decoproduct or component type Switched socket with USB chargerdevice presentation Complete productoutlet standard Britishcolour tint Cover plate: mocha bronze
Interior: blackearth circuit Standard earthquantity per set Set of 1type of packing BagComplementary switch function 1-polerated current 13 A at 250 V AC 50/60 Hzintegrated connection type 2 USB port 5 V DC 2.1 Aactuator Rockernumber of gangs 2 gangspilot light without LEDfixing mode Concealed screwsconnections – terminals Screw terminalsmaterial Stainless steeltype of installation Indoordepth 31Â mmwidth 148Â mmheight 87Â mmnet weight 0.239Â kgSKU: n/a -
CEILING LIGHTS, ELECTRICAL FITTINGS, HOME&OFFICE LIGHTING
Philip LED Down Light Surface-mounted SmartBright 23watt Philips
CEILING LIGHTS, ELECTRICAL FITTINGS, HOME&OFFICE LIGHTINGPhilip LED Down Light Surface-mounted SmartBright 23watt Philips
Benefits
• Reliability and safety: meets national and international regulation
• Energy saving: High system efficacy with lower power consumption
• Diversity: One stop shopping with multiple choices of recess round, square as well
as surface-mount to fit your dedicated applications
• Easy to install with slim designFeatures
• Long life time: 20Khrs (L70B50@25°C)
• System efficiency: up to 85lm/W
• One family offers recess round, square and surface mount options
• Slim design: 33mm housing body heightApplication
• Retail
• Office
• ResidentialSKU: n/a