CIRCUIT BREAKERS
C120N – circuit breaker – 4P – 100A – C curve
range of product |
C120
|
|
---|---|---|
range |
Acti 9
|
|
product name |
C120
|
|
product or component type |
Miniature circuit-breaker
|
|
device short name |
C120N
|
|
device application |
Distribution
|
|
poles description |
4P
|
|
number of protected poles |
4
|
|
[In] rated current |
100 A at 30 °C
|
|
network type |
AC
|
|
trip unit technology |
Thermal-magnetic
|
|
curve code |
C
|
|
breaking capacity |
10000Â A Icn at 230…400 V AC 50/60 Hz conforming to EN/IEC 60898-1
6Â kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 20Â kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10Â kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2 10Â kA Icu at <= 500 V DC conforming to EN/IEC 60947-2 |
|
suitability for isolation |
Yes conforming to IEC 60947-2
|
network frequency |
50/60 Hz
|
|
---|---|---|
[Ue] rated operational voltage |
380…415 V AC 50/60 Hz
<= 500 V DC 220…240 V AC 50/60 Hz 440 V AC 50/60 Hz 230…400 V AC 50/60 Hz |
|
magnetic tripping limit |
5…10 x In
|
|
[Ics] rated service breaking capacity |
7500Â A 75Â % conforming to EN/IEC 60898-1 – 230…400 V AC 50/60 Hz
4.5Â kA 75Â % conforming to EN/IEC 60947-2 – 440 V AC 50/60 Hz 7.5Â kA 75Â % conforming to EN/IEC 60947-2 – 380…415 V AC 50/60 Hz 15Â kA 75Â % conforming to EN/IEC 60947-2 – 220…240 V AC 50/60 Hz 10Â kA 100Â % conforming to EN/IEC 60947-2 – <= 500 V DC |
|
limitation class |
3 conforming to EN/IEC 60947-2
|
|
[Ui] rated insulation voltage |
500Â V AC 50/60 Hz conforming to EN/IEC 60947-2
|
|
[Uimp] rated impulse withstand voltage |
6Â kV conforming to EN/IEC 60947-2
|
|
contact position indicator |
Yes
|
|
control type |
Toggle
|
|
local signalling |
ON/OFF indication
|
|
mounting mode |
Clip-on
|
|
mounting support |
35 mm symmetrical DIN rail
|
|
comb busbar and distribution block compatibility |
NO
|
|
9 mm pitches |
12
|
|
height |
81Â mm
|
|
width |
108Â mm
|
|
depth |
73Â mm
|
|
net weight |
0.82Â kg
|
|
colour |
White
|
|
mechanical durability |
20000Â cycles
|
|
electrical durability |
5000Â cycles conforming to IEC 60947-2
|
|
connections – terminals |
Tunnel type terminals1…50 mm² rigid
Tunnel type terminals1.5…35 mm² flexible |
|
wire stripping length |
15Â mm
|
|
tightening torque |
3.5Â N.m
|
|
earth-leakage protection |
Separate block
|
₦60,000.00
Compare-
CABLE AND CABLE MANAGEMENT, Electro, SINGLE CORE WIRE
Doncaster Cables 10mm Single Core – Black
Product Description
Manufactured to BS 6004:2012 Table 3
Annealed Stranded Copper Conductor / PVC Insulated / PVC Sheathed. 300/500V
Designed for use in light industrial and domestic wiring. These cables are particularly suited for installation as meter tails and are intended for fixed installation in dry or damp premises.
These cables can be installed in conduit, in cable trunking and in cable ducting. Or where there is deemed little risk of mechanical damage these cables can be clipped direct, on cable tray, embedded or in free air. These cables are not intended to be laid underground.
Product Details
 Harmonisation Code Nominal Cross Sectional Area of Conductor (mm2) Nominal Stranding of Conductor (mm) Nominal Radial Thickness of insulation (mm) Nominal Radial Thickness of sheath (mm) Overall Diameter Lower Limit (mm) Overall Diameter Upper Limit (mm) Approximate Weight(kg/km) National Type 1.0 1 / 1.13 0.6 0.8 3.8 4.5 26 National Type 1.5 1 / 1.38 0.7 0.8 4.2 4.9 35 National Type 2.5 1 / 1.78 0.8 0.8 4.8 5.8 55 National Type 4.0 7 / 0.85 0.8 0.9 5.4 6.8 75 National Type 6.0 7 / 1.04 0.8 0.9 6.0 7.4 95 National Type 10.0 7 / 1.35 1.0 0.9 7.2 8.8 155 National Type 16.0 7 / 1.70 1.0 1.0 8.4 10.5 225 National Type 25.0 7 / 2.14 1.2 1.1 10.0 12.5 340 National Type 35.0 7 / 2.52 1.2 1.1 11.0 13.5 445 SKU: n/a -
Electro, LIGHT SWITCHES & ELECTRICAL SOCKETS
Schneider 10A 250V Bell Press Switch with Bell Icon KB31BPB
Electro, LIGHT SWITCHES & ELECTRICAL SOCKETSSchneider 10A 250V Bell Press Switch with Bell Icon KB31BPB
Main range Vivaceproduct or component type Switchdevice short name KB31device presentation Complete mechanismAdditional switch application Bell switchComplementary switch function 1-wayactuator Rockernumber of gangs 1 gangcolour tint Whitematerial Polycarbonate: grid plate
Polycarbonate: surround
Polycarbonate: baseprojecting depth 8Â mmdevice mounting Flushmounting support Wall mountedfixing mode By screw M3.5fixing center 60.3 mmembedding depth 35Â mmrated current 10 A at 250 V AC, inductive[Ue] rated operational voltage 250 V ACnetwork frequency 50 Hzcontacts material Brass and phosphor bronzeconnections – terminals pillar terminalterminal identifier L1
L2
COMtightening torque 0.4 N.mclamping connection capacity 1.5 mm²width 87 mmheight 87 mmSKU: n/a -
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONS
Easy9 Residual Current Circuit Breaker – 2P – 63 A – 30 mA – AC type – 230 V EZ9R34263
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONSEasy9 Residual Current Circuit Breaker – 2P – 63 A – 30 mA – AC type – 230 V EZ9R34263
Main range of product Easy9product or component type Residual current circuit breaker (RCCB)device short name Easy9 RCCBPoles 2Pneutral position Left[In] rated current 63 Anetwork type ACearth-leakage sensitivity 30 mAearth-leakage protection time delay Instantaneousearth-leakage protection class Type ACrated breaking and making capacity 630 Arated conditional short-circuit current Easy9 MCB: 4500 A 63 AComplementary device location in system Outgoernetwork frequency 50 Hz[Ue] rated operational voltage 230 V AC 50 Hzresidual current tripping technology Voltage dependent[Ui] rated insulation voltage 440 V AC[Uimp] rated impulse withstand voltage 4 kVsurge current 250 Acontact position indicator Yescontrol type Togglemounting mode Clip-onmounting support DIN railcomb busbar and distribution block compatibility Top: YES9 mm pitches 4height 82 mmwidth 36 mmdepth 72 mmcolour Grey (RAL 7035)mechanical durability 5000 cycleselectrical durability AC: 2000 cycles 230 V AC 50 Hzconnections – terminals Tunnel type terminal (top or bottom) 1…25 mm² rigid
Tunnel type terminal (top or bottom) 1…16 mm² flexibletightening torque 2.5 N.m top or bottommarket segment Small commercial
ResidentialSKU: n/a -
FLUORESENT TUBES, LIGHTING
Sylvania Instant Rapid Start F40W T12 640 120cm | Cool White
Product overview
Product name F40W/33-640-IRS Technology Fluorescent Watt (Rated) (W) 39.50 Lamp shape Tubular shape Cap/Base G13 Lamp finish Frosted/Coated Fixture rating Open General application Education, Hospitality, Logistics & Industry, Museums & Galleries, Office, Retail, Residential & Consumer ETIM Class EC000108 E-number FI 4941536 E-number Norway 3815455 Luminous flux (lm) 3000 Colour temperature (K) 4000 Light colour Cool White CRI (Ra) 64 Wattage (W) 40.00 Product Voltage (V) 103 Dimmable No Average life (Nominal) (h) 10000 SKU: n/a -
-
Electro, Low Voltage Products and Systems, SCHNEIDER SECTIONS
EZC250N3160 Circuit breaker Easypact EZC250N – TMD – 160 A – 3 poles 3d
Electro, Low Voltage Products and Systems, SCHNEIDER SECTIONSEZC250N3160 Circuit breaker Easypact EZC250N – TMD – 160 A – 3 poles 3d
Main range of product EasyPactproduct or component type Circuit breakerdevice short name Easypact EZC250Ncircuit breaker name Easypact EZC250Ndevice application Distributionpoles description 3Pprotected poles description 3tnetwork type DC
ACnetwork frequency 50/60 Hz[In] rated current 250 A at 40 °C[Ui] rated insulation voltage 690 V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947-2[Ue] rated operational voltage 550 V AC 50/60 Hz conforming to IEC 60947-2
250 V DC conforming to IEC 60947-2breaking capacity code Nbreaking capacity 20Â kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
50Â kA Icu at 110…130 V AC 50/60 Hz conforming to IEC 60947-2
50Â kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
20Â kA Icu at 125 V DC 1P conforming to IEC 60947-2
20Â kA Icu at 250 V DC 2P conforming to IEC 60947-2
25Â kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2
25Â kA Icu at 400…415 V AC 50/60 Hz conforming to IEC 60947-2
8Â kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2[Ics] rated service breaking capacity 10Â kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
25Â kA at 110/130 V AC 50/60 Hz conforming to IEC 60947-2
10Â kA at 125 V DC conforming to IEC 60947-2
10Â kA at 250 V DC conforming to IEC 60947-2
25Â kA at 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2
4Â kA at 550 V AC 50/60 Hz conforming to IEC 60947-2
12.5Â kA at 380 V AC 50/60 Hz conforming to IEC 60947-2
12.5 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2suitability for isolation Yes conforming to IEC 60947-2utilisation category Category Atrip unit name TM-Dtrip unit technology Thermal-magnetictrip unit rating 160 A at 50 °Cprotection type Overload protection
Short-circuit protectionpollution degree 3 conforming to IEC 60664-1
3 conforming to IEC 947-1Complementary control type Togglemounting mode Fixedmounting support Backplateupside connection Frontdownside connection Frontmechanical durability 10000Â cycleselectrical durability Category A: 5000Â cycles 415 V AC 50/60 Hz conforming to IEC 60947-2connection pitch 35Â mmlocal signalling Positive contact indicationneutral protection setting Without protectionearth-leakage protection Withoutheight 165Â mmwidth 105Â mmdepth 60Â mmSKU: n/a
There are no reviews yet.