CHINT Kwh Meter Single
DDSU666 series three phase three wire electronic energy meter (DIN Rail) Summary :
DDSU666 series electronic energy meter is designed for power monitoring and energy measurement such as power system, communication industry, construction industry, etc. to be a new generation of programmable.
DDSU666 series three phase three wire electronic energy meter (DIN Rail)
Summary:
DDSU666 series electronic energy meter is designed for power monitoring and energy measurement such as power system, communication industry, construction industry, etc. to be a new generation of programmable intelligent instrument, integrated with measurement and communication function, mainly used for real-time measurement and display for the electrical parameters such as voltage, current, active power, reactive power, frequency, power factor, energy in the electrical circuit, etc.
1、Main functions and characteristics
◆DIN35mm Standard DIN-Rail, seven modulus with segment LCD display
◆Measurement function: Characterized with measurement for three phase three wire voltage, current, frequency, active power, power factor, active energy and reactive energy
◆communication function: RS485 communication interface, supporting DL/T645-2007 protocol, customizable for MODBUS-RTU protocol
◆Multi-rate function: it supports four rates including top, peak, flat, valley rate.
₦73,500.00
Compare-
ELECTRICAL INDUSTRIAL, TRANSFORMER
MEKSAN Transformer 300kVA 11/415kV
Meksan Transformer manufacture distribution and power transformer from 50 kVA up to 50 MVA. Our products are produced in accordance with the TS 267 and the IEC60076 standards. Our production is documented with the TSE (Türkish Standard Institue) standards confortmity, ISO 9001:2000 quality system and ISO 14001 environmental management system certificates.
SKU: n/a -
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONS
Easy9 MCB miniature circuit breaker- 1P – 40 A – C curve – 6000 A – 230 V EZ9F56140
Electro, Schneider Circuit Breakers, SCHNEIDER SECTIONSEasy9 MCB miniature circuit breaker- 1P – 40 A – C curve – 6000 A – 230 V EZ9F56140
Main range Easy9device application Distributionproduct or component type Miniature circuit-breakerdevice short name Easy9 MCBPoles 1Pnumber of protected poles 1[In] rated current 40 Anetwork type ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 6000 A Icn at 230 V AC 50/60 Hz conforming to IEC 60898-1
10000 A Icn at 127 V AC 50/60 Hz conforming to IEC 60898-1suitability for isolation Yes conforming to IEC 60898-1Complementary network frequency 50/60 Hz[Ue] rated operational voltage 230 V AC 50 Hz
127 V AC 50 Hzmagnetic tripping limit 5…10 x In[Ics] rated service breaking capacity 6 kA 100 % x Icn at 230 V AC 50/60 Hz conforming to IEC 60898-1[Ui] rated insulation voltage 500 V AC 50/60 Hz conforming to IEC 60898-1[Uimp] rated impulse withstand voltage 4 kV conforming to IEC 60898-1contact position indicator Yescontrol type Togglelocal signalling Withoutmounting mode Clip-onmounting support DIN rail9 mm pitches 2height 81 mmwidth 18 mmdepth 66.5 mmcolour Grey (RAL 7035)mechanical durability 10000 cycleselectrical durability 4000 cyclesconnections – terminals Tunnel type terminal (top or bottom) 1…25 mm² flexible
Tunnel type terminal (top or bottom) 1…35 mm² rigidtightening torque 3.5 N.m top or bottomearth-leakage protection WithoutSKU: n/a -
Electro, LED LIGHTS, LIGHTING, OUTDOOR LIGHTS
12W Underground Light Lamps Outdoor Buried Recessed Floor LED Waterproof IP67
Electro, LED LIGHTS, LIGHTING, OUTDOOR LIGHTS12W Underground Light Lamps Outdoor Buried Recessed Floor LED Waterproof IP67
Applications:
square, restaurant, Private, villas, garden, meeting room, exhibition hall, District environment beautification, Stage bar, supermarket, Parking sculpture, Tourist attractions and other placesSKU: n/a -
-
Schneider Circuit Breakers, SCHNEIDER SECTIONS
Miniature circuit-breaker, Acti9 iC60H, 2P, 63 A, C curve, 10000 A (IEC 60898-1), 15 kA (IEC 60947-2) A9F84263
Schneider Circuit Breakers, SCHNEIDER SECTIONSMiniature circuit-breaker, Acti9 iC60H, 2P, 63 A, C curve, 10000 A (IEC 60898-1), 15 kA (IEC 60947-2) A9F84263
Main device application Distributionrange Acti 9product name Acti 9 iC60product or component type Miniature circuit-breakerdevice short name IC60Hpoles description 2Pnumber of protected poles 2[In] rated current 63 Anetwork type DC
ACtrip unit technology Thermal-magneticcurve code Cbreaking capacity 10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
42 kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2
10 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2
15 kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2
30 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
15 kA Icu at <= 125 V DC conforming to EN/IEC 60947-2
42 kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2utilisation category Category A conforming to EN 60947-2
Category A conforming to IEC 60947-2suitability for isolation Yes conforming to EN 60898-1
Yes conforming to EN 60947-2
Yes conforming to IEC 60898-1
Yes conforming to IEC 60947-2standards IEC 60947-2
IEC 60898-1
EN 60947-2
EN 60898-1Complementary network frequency 50/60 Hzmagnetic tripping limit 8 x In +/- 20 %[Ics] rated service breaking capacity 15 kA 50 % conforming to EN 60947-2 – 220…240 V AC 50/60 Hz
7.5 kA 50 % conforming to EN 60947-2 – 380…415 V AC 50/60 Hz
5 kA 50 % conforming to EN 60947-2 – 440 V AC 50/60 Hz
15 kA 50 % conforming to IEC 60947-2 – 220…240 V AC 50/60 Hz
7.5 kA 50 % conforming to IEC 60947-2 – 380…415 V AC 50/60 Hz
5 kA 50 % conforming to IEC 60947-2 – 440 V AC 50/60 Hz
7500 A 75 % conforming to EN 60898-1 – 400 V AC 50/60 Hz
7500 A 75 % conforming to IEC 60898-1 – 400 V AC 50/60 Hz
21 kA 50 % conforming to IEC 60947-2 – 12…133 V AC 50/60 Hz
21 kA 50 % conforming to EN 60947-2 – 12…133 V AC 50/60 Hz
15 kA 100 % conforming to IEC 60947-2 – 72…125 V DC
15 kA 100 % conforming to EN 60947-2 – 72…125 V DC[Ui] rated insulation voltage 500 V AC 50/60 Hz conforming to EN 60947-2
500 V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6 kV conforming to EN 60947-2
6 kV conforming to IEC 60947-2contact position indicator Yescontrol type Togglelocal signalling Trip indicatormounting mode Fixedmounting support DIN railcomb busbar and distribution block compatibility Top or bottom: YES9 mm pitches 4height 85 mmwidth 36 mmdepth 78.5 mmnet weight 0.25 kgcolour Whitemechanical durability 20000 cycleselectrical durability 10000 cyclesconnections – terminals Single terminal (top or bottom) 1…35 mm² rigid
Single terminal (top or bottom) 1…25 mm² flexiblewire stripping length 14 mm for top or bottom connectiontightening torque 3.5 N.m top or bottomearth-leakage protection Separate blockSKU: n/a